A TTENTION INST ALLING PERSONNEL As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items. Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual.
2 Safety Instructions Safety Guidelines 1. Allow only qualified, experienced technicians to install or service this unit. 2. Inst all the system in accordance with all local codes. If no local codes exist, follow National Codes (NEC in the U.S., CEC in Canada).
3 3 DO NOT locate the unit: – Directly under a vent termination for a gas appliance. – Within 3 feet of a clothes drier vent. – Where the refreezing of defrost water would create a hazard. – Where water may rise into the unit. – Where the noise would prove to be a nuisance to the customer (i.
4 Safe Refrigerant Handling WARNING To avoid possible explosion, death, or injury; practice safe handling of refrigerants. While these items will not cover every conceivable situa- tion, they should serve as a useful guide. WARNING Refrigerants are heavier than air.
5 5 6. Close the valve on the nitrogen cylinder and discon- nect it from the gauge manifold. 7. Check for leaks. Apply a soap solution on all connec- tions and joints.
6 Step 2. Evacuate Lines And Indoor Coil. a. Open the high and low side valves (B & A) on the gauge manifold. NOTE: Only open the valve (E) on the gauge manifold leading to the cylinder, not the valve on the charging cylinder (F). b. Evacuate the system to about 29 inches Hg as mea- sured by the low side (compound) gauge.
7 7 Electrical Connections 75 60 50 43 37 N/R N/R N/R N/R N/ R N/R N/R N/R 1 1 8 9 57 96 85 95 34 7 N / R N / R N / R N / R N / R N / R 1 8 8 1 5 0 1 2 5 1 0 7 9 58 37 56 86 3 5 85 4 N / R N / R 301 2.
8 IMPORTANT: Hard start components are required when single-phase reciprocating compressors are used with indoor coils which have thermal expansion valves. Some units have hard start components factory installed. See the “Specification Sheet” for hard start component require- ments.
9 9 4 50 60 70 80 90 100 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUP E RHEAT @ O. D. U N IT O UTD OO R TE M P ER AT URE DESIR ED SUPERH EAT vs OU TDOOR TEMP ER AT URE 9 0 ° F I n d o o .
10 ID COIL WITH EXPANSION VALVE At stabilized cooling conditions and with an outdoor tem- perature of 60°F or higher, the subcooling at the outdoor unit liquid line service valve should be as specified in the specification sheet. Add or remove charge as required.
11 11 THERMOST A T* CONNECTIONS T O RH/VH HEA T PUMPS WITH INDOOR BBA/BBC BLOWER COIL Approved Thermostat s: 1213403, 1213404, 1213410, 1213406 NOTE: 1. When installing accessories, wiring may have to be modified. Follow the instructions in the accessory kit’s installation instructions.
12 Sy stem C hecklist 1 Does the cond enser f an blade r otate f reely, and is it tig ht on the s haft? 2 Does the ref rigeran t tubing flex f reely and not touc h anoth er tube to c ause r ub throug .
デバイスGoodman Mfg RHA**B*Dの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Goodman Mfg RHA**B*Dをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGoodman Mfg RHA**B*Dの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Goodman Mfg RHA**B*Dの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Goodman Mfg RHA**B*Dで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Goodman Mfg RHA**B*Dを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGoodman Mfg RHA**B*Dの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Goodman Mfg RHA**B*Dに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGoodman Mfg RHA**B*Dデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。