990-7031C, Rev ision 4 12/99 APC Smart-UPS Uninterruptible Pow er Supply Models 1400XLT, 2200XLT, 3000T, 5000T User’s Manual.
Entire con tents copy rig ht ©1999 by Am erican Pow er Con version . All rig hts res erved. Reprodu ction in wh ole or in part w ith out permis sion is prohibited. Sm art-UPS is a reg istered tradem ark of APC. A ll other tradem arks are the property of th eir respectiv e ow ners.
990-7031C, Rev ision 4 12/99 Smart UPS Safety Guide English This Sa fety Guide contains im portant instr uctions that should be follow ed during insta llation and m aintenanc e of the APC equipm ent and batte ries. It is intended f or APC customers w ho setup, install, reloc ate, or m aintain APC equipm ent.
.
990-7031C, Rev ision 4 12/99 Table of Contents Introduction........................................................................................................................................................................... 1 Unpackin g .......
.
990-7031C, Rev ision 4 12/99 1 Introduction This Uninterru ptible Power Supply (UPS) is design ed to prevent black outs, brow nouts, s ags and su rges from reaching your com puter and other valuable electronic equipm ent.
990-7031C, Rev ision 4 12/99 2 Inst allation Install ing your UP S req uires five steps: 1. Position the UPS in the desired locatio n. For rack m ount units this m ay in clude installing the rails in to the rack. 2. Conn ect the batteries . All UPSs ship w ith th e batteries dis connected.
990-7031C, Rev ision 4 12/99 3 Determine the Loca tion of the UPS in the Rack UPSs a re hea vy. Select a rack l ocat ion stur dy enough to handle the weight. Mo unt the UP S at o r near the b otto m of the rack. Select a rack location w ith adequate air f low that is free f rom exces sive dust .
990-7031C, Rev ision 4 12/99 4 3 Expand the rails so that it spans from the front rack post to the back rack post. Replace the tw o screw s (rem oved in step 1) that hold the rail sections together. 4 Bac k Attach th e rail to the back rack post using th e same hardw are (10-32 f lat head screw s and con ical w ashers) u sed in step 2.
990-7031C, Rev ision 4 12/99 5 2. Connect the B atteries Note: All UPSs ship with the b atteries discon nected. In add ition, 5000 VA uni ts have the batteries s hipped outside the UPS case so you m ust install the batteries before connecting them .
990-7031C, Rev ision 4 12/99 6 3U Rack Mount Units 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. 2. Unhook the si de of the cov er from the chass is and lif t it aw ay to expose th e battery door.
990-7031C, Rev ision 4 12/99 7 3. Connect Powe r and Equipment to the UPS • Connect th e UPS line cord (L6-30 plug ) into the electrical outlet. • Use y our equipm ent’s pow er cords to con nect to the UPS. Caution: DO NOT use a standard serial interface cable to connect to the Com puter In terface Port on the UPS.
990-7031C, Rev ision 4 12/99 8 Charge the ba ttery The UPS charges its battery w henever it is conn ected to utility pow er. The battery will ch arge fully during the f irst four hours of norm al operation. Do not expect full runtim e during this in itial charge period.
990-7031C, Rev ision 4 12/99 9 Operating Instructions Switch On — Switch Of f With the UPS p lugged in, press a nd re lease the large up per on/test button t o supp ly power to the load s. T he loa ds are imm ediately powered w hile th e UPS beeps and perform s a self- test.
990-7031C, Rev ision 4 12/99 10 Load Bar Gra ph 85% 67% 50% 33% 17% The 5-LED display on the lef t of the f ront panel represents the pow er drawn from th e UPS as a percentage of total capacity. For exam ple, if three L EDs are lit, the load is drawing betw een 50% and 67% of the UPS’s capacity.
990-7031C, Rev ision 4 12/99 11 Sto r a g e Storage Conditions Store the UPS covered and upright in a cool, dry location, w ith its battery f ully ch arged.
990-7031C, Rev ision 4 12/99 12 Battery Replacement Proced ure - To wer Unit s 5000 VA 1. Grasp th e top edge of t he bottom front cover and tilt it out. For the 5000 VA u nit: Rem ove the fron t bezel by gras ping the f inger clips on the side of th e bezel and carefu lly loosen ing the f our (4) snaps.
990-7031C, Rev ision 4 12/99 13 Battery Replacement Procedure - 3U Rack Mount Units 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. 2. Unhook the si de of the cov er from the chass is and lif t it aw ay to expose th e battery door.
990-7031C, Rev ision 4 12/99 14 Battery Replacement Procedure - 5U Rack Mount Units 5000 VA 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. For 5000 VA un its: Rem ove the fron t bezel by gras ping the f inger clips on the side of th e bezel and carefu lly loosen ing the f our (4) snaps.
990-7031C, Rev ision 4 12/99 15 User Configur ation Items Note: Settin g th ese items req uires o ptio nal so ftware o r ha rdware. Fun ction Factory Defau lt User Selectabl e Choi ces Descriptio n Au.
990-7031C, Rev ision 4 12/99 16 Tow er and 5U Rack M ount Models - 3000 & 5000 VA Models Typical On-B attery Run Time Versus Load, in Hours Load 3000 VA Internal Battery 3000 VA w/ 1 Battery Pack 5000 VA Intern al Battery 100 VA 3.80 8.18 7.17 150 VA 3.
990-7031C, Rev ision 4 12/99 17 Sp ecifications 1400 VA 2200 VA 3000 VA 5000 VA Acceptable input v oltag e 0 - 325 VAC Inpu t vo ltage (o n-line operation )* 160 - 253 VAC 208 vo lt outpu t range * 17.
990-7031C, Rev ision 4 12/99 18 T roubleshooti ng Use the chart below to solve m inor UPS installa tion problem s. Contact A PC Tec hnical Support Staf f f or assis tance w ith comple x UPS problem s. See APC Contact Inform atio n , page 19 , for a location near you.
990-7031C, Rev ision 4 12/99 19 Service If the UPS requires service do not return it to the dealer! Follow these steps: 1. Revi ew t he problem s discu ssed in Troublesh ooting , page 18, to eli min ate comm on problem s. 2. Verify that no circuit break ers are tripped.
990-7031C, Rev ision 4 12/99 20 A pp endix A : XL Informatio n When used w ith external battery pack s, the extended ru n (XL) UPS offers longer run tim es than a standard UPS and extra load protection during battery replacem ent.
990-7031C, Rev ision 4 12/99 21 Smart-UPS Battery Protocol Smart- UPS XL models are not designed to k now h ow m any external battery packs are conn ected to them . You mu st program the Sm art-UPS XL w ith the appropriate num ber of external batteries in one of four w ay s.
990-7031C, Rev ision 4 12/99 22 Use the HyperTerminal Pro gram to Chang e the Number of External Battery Packs Hy perTermina l is us ed for Window s 95, Window s 98, and Win dow s NT 4.0 1. EXIT out of t he Pow erChu te plus Serv er. In the case of Window s NT, the UPS s ervice m ust be s topped.
990-7031C, Rev ision 4 12/99 23 A ppendix B: T y pes of Racks and Mounting Har dw are This appendix describes th e hardw are required f or the diff erent ty pes of rack s and desc ribes the ty pe of rack s that m ay be used in y our indu stry . All APC rack moun t units are s hipped ready f or 19-inch w ide EIA /IEC rack cabinets .
990-7031C, Rev ision 4 12/99 24 A ppendix C: T ransporti ng Y our Smart-UPS Follow these g uidelines if y ou need to ship the UPS to another location. T hese guidelines apply w heth er you are transporting the UPS alone, rack m ounted in an equipmen t cabinet, or installed in a sys tem.
デバイスAmerican Power Conversion 3000Tの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
American Power Conversion 3000Tをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAmerican Power Conversion 3000Tの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。American Power Conversion 3000Tの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。American Power Conversion 3000Tで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
American Power Conversion 3000Tを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAmerican Power Conversion 3000Tの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、American Power Conversion 3000Tに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAmerican Power Conversion 3000Tデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。