APC Silcon 60-80kW 208/480V UPS User Guide Copyright ©2000 APC Denmark ApS Information in this document is subject to change without notice and does not represent a commitment on the part of the vend.
2 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use.
990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 3 Contents: 1.0 Introduction 4 1.1 Display Unit 4 2.0 Stop/Start UPS and Operating the External Service Bypass Panel 5 2.1 Stop UPS (for stand-by) 5 2.2 Start UPS (from stand-by) 5 2.3 Stop UPS (for complete power down) 6 2.
4 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 5 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed.
6 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass 2.3 Stop UPS (for complete power down) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 7 The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out. 2.4 Start UPS (from complete power down) 2.4.
8 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass System start-up now completed. NOTICE! One of the following display messages will appear.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 9 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Utility Load Service Bypass Switch Action 1.
10 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 11 NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input switch (Q001) to position 1 2.
12 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass 2.6 Operating the External Service Bypass Switch (parallel systems) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 13 Action Steps 1-4 apply to all the parallel systems. Note that this will s witch all systems into bypass oper ation 1. Press on the ke yboard 2.
14 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 15 Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input switches (Q001) to position 1 4.
16 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Stop/Start UPS and Operating the External Service Bypass 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.
Stop/Start UPS and Operating the External Service Bypass 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 17 NOTICE! With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed.
18 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Operation 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values.
Operation 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 19 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below.
20 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Operation 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS. It is impossible to adjust or otherwise influence the function of the UPS.
Parameter Settings 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 21 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard.
22 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Parameter Settings 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list .
Parameter Settings 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 23 To return to normal operation Follow same procedure to program other parameters. Action 6. Press to enter parameter stack 7. Press or until 8. Press until 9. Press to store 10.
24 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Alarms and Events 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.
Alarms and Events 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 25 5.3 Possible Alarms NOTICE! Please note mains = utility Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation.
26 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Alarms and Events 19. **Q001 off** UPS input switch position – 20. High temperature of isolation transformer Temperature of isolation input/ output transformer, too high Check fan, check for airflow obstructions, check for overload 21.
Alarms and Events 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 27 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local utility supply.
28 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Alarms and Events 5.5 Parallel Operation Alarms The parallel operation alarm message is: Communication to parallel IF lost In the event of a parallel operation alarm, all parallel operation functions controlled by Advanced Power Management will be inactive.
Maintenance & Testing 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 29 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years.
30 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 Maintenance & Testing If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1.
Warranty 990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 31 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or.
32 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035 How to Contact APC 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-37.
990-4035 User Guide APC Silcon 60-80kW 208V/480V UPS 33 9.0.
34 User Guide APC Silcon 60-80kW 208V/480V UPS 990-4035.
デバイスAmerican Power Conversion 60-80kW 208/480Vの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
American Power Conversion 60-80kW 208/480Vをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAmerican Power Conversion 60-80kW 208/480Vの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。American Power Conversion 60-80kW 208/480Vの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。American Power Conversion 60-80kW 208/480Vで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
American Power Conversion 60-80kW 208/480Vを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAmerican Power Conversion 60-80kW 208/480Vの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、American Power Conversion 60-80kW 208/480Vに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAmerican Power Conversion 60-80kW 208/480Vデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。