The world's most reliable power protection ® Matrix TM UPS Hard-wire kit accessory MXA001 MXA002 User's Manual American Power Conversion.
Important safety instructions! Please read this manual! V euillez lire ce manuel! Bitte lesen Sie dieses Anleitungshandbuch! ¡Se ruega leer este manual de instrucciones! PLEASE SA VE THIS MANUAL ! It includes important instructions for the safe use and installation of the UPS and its accessories.
Page 1 T able of contents 1.0 Introduction ................................................................................. 2 2.0 Presentation ................................................................................. 3 3. 0 Installation .....
Page 2 1.0 Introduction The hard-wire kit allows the UPS's input and/or output terminals to be permanently secured to building service wiring. This kit is used in place of the power distribution plate and/or input cable plate originally furnished with the UPS.
Page 3 2.0 Presentation Power distribution plate Provides an interface for output hard-wiring of loads. It is used in place of the power distribution plate for cord connected equipment originally furnished with the UPS. Input cable plate Used to replace the input cable plate originally furnished with the UPS.
Page 4 3.0 Installation ■ W arning: Risk of electric shock exists inside the UPS. Input voltage tap selection and power distribution panel replacement should be performed only by qualified service personnel. ■ A vertissement: Un risque de choc électrique existe à lintérieur de lUPS.
Page 5 3.0 Installation T able 3.2.1 Cable Size S tri p Length UP S M ode l Min im um Ma x i m um Input cable Output cable 300 0VA 2. 5 m m 2 12 A W G 1 0 .0 m m 2 8 AW G 12 m m 1/2" 9 m m 3/8" 500 0VA 6. 0 m m 2 10 A W G 1 0 .0 m m 2 8 AW G ■ Cable clamps The UPS is not furnished with cable clamps for strain relief.
Page 6 3.0 Installation Input cable connections 3.3 Input wiring procedure - continued T o remove a knock-out, strike in the area shown with a nail set tool and hammer . Grasp the edge of the knock-out with pliers and twist until the knock-out is separated from the plate.
Page 7 3.0 Installation 3.3 Input wiring procedure - continued 3.3.4 Remove all three input cable wire connections from terminal block labeled L1 , and L2/N . 3.3.5 Remove all screws that secure the input cable plate. Use a pair of wire cutters to remove "tie wraps" binding the input cable to wires inside the Isolation Unit.
Page 8 Unmating of UPS output power connector 3.0 Installation 3.4 Output wiring procedure 3.4.1 Be sure the input circuit breaker is switched off (0) and the input cable is unplugged and/ or has no power applied. Caution: Switching the circuit breaker to off (0) does not remove power to all of the Isolation Unit.
Page 9 Diagram showing power distribution plate earth connection 3.0 Installation 3.4 Output wiring procedure - continued 3.4.4 Use a 3/8" wrench to remove the protective earth wire (green with yellow stripes) ring terminal fastened at the earthing stud on the Isolation Unit.
Page 10 3.0 Installation 3.4 Output wiring procedure - continued 3.4.9 Choose the desired wiring connections from the illustrations on the following pages (Figure 3.4.1 through Figure 3.4.6 ). Insert the stripped wire ends into the appropriate output terminations block terminal and tighten the terminal screws.
Page 11 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.1 1 f , 208 V ac loads only 3000 V A model with MXA002 hard- wire kit: 15 Amp maximum. 5000 V A model with MXA001 hard- wire kit: 24 Amp maximum. Figure 3.4.2 1 f , 240 V ac loads only 3000 V A model with MXA002 hard- wire kit: 12.
Page 12 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.5 1 f , 120/240 V ac loads ■ ■ ■ ■ ■ 3000 V A model with MXA002 hard- wire kit Each 120 V ac output: 25 Amp maxi- mum. 240 V ac output: 12.5 Amp maximum. T otal output: not to exceed 3000 V A .
Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products.
Customer Service Note: Before calling the customer service number , please have available your UPS's serial number (see the label at the rear of the UPS).
デバイスAmerican Power Conversion MXA002の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
American Power Conversion MXA002をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAmerican Power Conversion MXA002の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。American Power Conversion MXA002の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。American Power Conversion MXA002で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
American Power Conversion MXA002を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAmerican Power Conversion MXA002の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、American Power Conversion MXA002に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAmerican Power Conversion MXA002デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。