02/04 4034-102 Rev F 1 CAUTION: Do not expose the appliance to the elements (such as rain, etc.). IMPORT ANT! Before installation, the inst aller must give careful consider- ation to how this HRV200PLUS system will operate if con- nected to any other piece of mechanical air movement equip- ment, i.
2 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS The Heatilator Home Products Heat Recovery V entilator 200 Plus (HRV200PLUS) works as a power ventilator for the Fresh Air Firep laces (F AF) from Heatilator and Heat-N-Glo, and is designed to provide fresh air into a building while exhausting an equal amount of st ale air .
02/04 4034-102 Rev F 3 HRV200PLUS INST ALLA TION INSTRUCTIONS C. ENGINEERING DA T A Efficient, Patented Aluminum Core The cross-flow heat recovery core transfers heat between the intake and exhaust airstreams. The core removes easily for cleanin g or service.
4 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS Appliance Dimensions e c n a m r o f r e P S U L P 0 0 2 V R H D E I F I T R E C I V H y r e v o c e R e r u t a r e p m e T m u m i x a .
02/04 4034-102 Rev F 5 HRV200PLUS INST ALLA TION INSTRUCTIONS D. DEFROST OPTIONS The HRV200PLUS performs as a whole house heat recovery ventilator during Fresh Air Fireplace operation and continuous ventilati on operation.
6 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 2. Room Air Defrost a. When the HR V200PLUS system is installed in climates that normally have more than five days a year with an out sid.
02/04 4034-102 Rev F 7 HRV200PLUS INST ALLA TION INSTRUCTIONS E. INST ALLA TION DIAGRAMS Note: Minimum and maximum clearances must be maintained at all times. Illustrations throughout these instructions reflect typical installations and are for design purposes only .
8 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS X b. Fresh Air Fresh air supplied to main living areas of the home (bedroom, family room). S tale air drawn from furnace return. HRV must be balanced. 2. Partially Dedicated Installation a.
02/04 4034-102 Rev F 9 HRV200PLUS INST ALLA TION INSTRUCTIONS x 3. Fully Dedicated Inst allation S tale air drawn from key areas of the home (bathroom, kitchen, laundry).
10 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 1. Location The HRV200PLUS must be located in a heated sp ace where it will be possible to conveniently service the ventilator . T ypically th e HRV200PLUS would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted.
02/04 4034-102 Rev F 11 HRV200PLUS INST ALLA TION INSTRUCTIONS G . VENT AND DUCT INST ALLA TION The HRV200PLUS (HRV) not only serves as the fresh air ventilator for the home, but is also the power venting device for the Fre sh Air Fireplace (F AF).
12 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS b. Inst all Fresh Air Supply Ducting The inner and outer liners of the insulated duct must be clamped to the sleeve of the weatherhood as close to the outside as possible and to the plastic inlet port on the HRV200PLUS.
02/04 4034-102 Rev F 13 HRV200PLUS INST ALLA TION INSTRUCTIONS Note: When using the existing furnace duct work for air distribu- tion, the furnace blower must be set to run continuously or inter- locked with the HRV200PLUS. The interlock may be easily achieved using the Furnace Interface Relay terminals on the HRV200PLUS control board.
14 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS b. Att aching the CoolV ent to the Fresh Air Fireplace Flue Collar 1) Secure a CoolV ent appliance connector to the CoolVent insulated flexible pipe per the manufacturer s instructions.
02/04 4034-102 Rev F 15 HRV200PLUS INST ALLA TION INSTRUCTIONS 4. HRV Exhaust - S t ale air/combustion products from the HRV to the Flue Exhaust Duct Materials: CoolV ent Flexible Pipe - Zero Clear.
16 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 5. St ale Air from the Living Area to the HRV (Alternate Exhaust) Duct Materials: Alternate Exhaust Damper Assembly Air Duct - flexible .
02/04 4034-102 Rev F 17 HRV200PLUS INST ALLA TION INSTRUCTIONS Figure 6 - T ypical Horizontal T ermination Figure 5 Horizontal T ermination.
18 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS Figure 7 - T ermination Cap Locations 2. Horizont al T ermination Locations (flue exhaust and fresh air inlets) Figure 8 - Alcove Cleara.
02/04 4034-102 Rev F 19 HRV200PLUS INST ALLA TION INSTRUCTIONS Dimension Descriptions A Clearance above the ground, a veranda, porch, deck or balcony - 12 inches (30 cm) minimum.
20 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS f. T ypical Vertical T ermination (see Figure 10) At least 10 (3m) from the ventilation air intake. At least 18 (457mm) above the roof line or above the depth of expected snow accumulation.
02/04 4034-102 Rev F 21 HRV200PLUS INST ALLA TION INSTRUCTIONS Figure 1 1 T ypical V ertical T ermination.
22 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 4. Chase/T ermination Inst allation Figure 12 and T able 1 specify minimum vent heights for various pitched roofs. These vent heights are necessary for safety and do not ensure draft-free operation.
02/04 4034-102 Rev F 23 HRV200PLUS INST ALLA TION INSTRUCTIONS 5. Firestop Sp acer/V ent Installation Following code requirements, frame an opening and inst all a firestop spacer whenever the vent penetrates a ceiling, wall or floor area, as shown in Figure13.
24 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS I. SELECTING BLOWER SPEEDS The HRV200PLUS versatile design allows flexibility for a variety of installations by providing one high bl.
02/04 4034-102 Rev F 25 HRV200PLUS INST ALLA TION INSTRUCTIONS 2. Air Flow Balancing J. BALANCING 1. Balancing Collar Instructions Figure 14 WARNING! Risk of carbon monoxide! Negative air pressure may cause back drafting of gas appliances. Proper balanc- ing of the HRV is required.
26 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 3. Pitot T ube Balancing Procedure (see Figure 16) The following is a method of field balancing an HRV200PLUS using a pitot tube, advantageous in situations when flow stations are not inst alled in the duct work.
02/04 4034-102 Rev F 27 HRV200PLUS INST ALLA TION INSTRUCTIONS Figure 16 - Pitot T ube Balancing.
28 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 4. Flow S tation Balancing Procedure (see Figure 17) The following is a method of field balancing an HRV using a flow station. The procedure should be performed with the HRV200PLUS on high speed.
02/04 4034-102 Rev F 29 HRV200PLUS INST ALLA TION INSTRUCTIONS K. OPERA TING MODES The operating mode of the HRV200PLUS is determined by the st atus of the control inputs: 1. Fireplace Control Input Group Connector P9 LO, HI, 12V , COM, C1, C2, R2, R1 2.
30 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 2) T ermination a) When the 12VDC signal is removed from the HI input terminal, R1 terminals is immediately de-energized shutting down fireplace operation. b) The blower motor remains on high speed for 20 seconds.
02/04 4034-102 Rev F 31 HRV200PLUS INST ALLA TION INSTRUCTIONS 9 P r o t c e n n o C s l a n i m r e T l o r t n o C e c a l p e r i F t u p n I n o i t c n u F 1 R .
32 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 5. V entilation Operating Modes Connector P1 a. OFF Mode The HRV is idle until an input is sensed. This is the normal st andby state when the HRV Plus is powered but not receiving any command inputs.
02/04 4034-102 Rev F 33 HRV200PLUS INST ALLA TION INSTRUCTIONS t u p n I n o i t c n u F C N Fs t c a t n o C y r D - l a n i m r e T d e s o l C y l l a m r o N M O C Fs t c a t n o C y r D l a n i m r e T n o m m o C O N Fs t c a t n o C y r D l a n i m r e T n e p O y l l a m r o N 7.
34 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS L. WIRING 1. Fireplace Control Wiring (Caliber NXT Plus/6100 Plus) Figure 18 Caliber NXT Plus or 6100 Plus & HRV W ired T ogether Æ.
02/04 4034-102 Rev F 35 HRV200PLUS INST ALLA TION INSTRUCTIONS 2. Fireplace Control Wiring (Novus Plus/6000 Plus) Figure 19 - Novus Plus Control Wiring Figure 20 - 6000 Plus Control Wiring Æ Æ Æ.
36 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS Figure 21 Thermost at Control Wiring (For integrated use with the central furnace and thermostat.
02/04 4034-102 Rev F 37 HRV200PLUS INST ALLA TION INSTRUCTIONS Figure 22 V entilation Control W iring 4. V entilation Control W iring (Controls may vary .
38 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 5. Furnace Interface Wiring Figure 23 - Furnace Interface Wiring Note: HRV board has a built-in isolation relay to ensure thermostat comp atibility .
02/04 4034-102 Rev F 39 HRV200PLUS INST ALLA TION INSTRUCTIONS WARNING! Blockage of weather hoods may cause a pressure imbalance within the house. Severe blockage will cause intermittent operation of the Fresh Air Fireplace! M. MAINTENANCE INSTRUCTIONS Proper maintenance is critical to the proper operation of the HRV200PLUS.
40 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS 4. Annual Maintenance a. Inspect and Clean Drain (condensate) Lines (if required) Inspect the drain line, drain spout and P-trap for blockage, mold or kinks. Flush with warm soapy water .
02/04 4034-102 Rev F 41 HRV200PLUS INST ALLA TION INSTRUCTIONS N. LED DIAGNOSTICS The HRV200PLUS comes equipped with a diagnostic LED mounted in the right side of the cabinet just below the power cord. This LE D indicates the state of the HRV - both normal operating modes as well as abnormal fault conditions.
42 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS O. TROUBLESHOOTING GUIDE.
02/04 4034-102 Rev F 43 HRV200PLUS INST ALLA TION INSTRUCTIONS x Æ.
44 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS x.
02/04 4034-102 Rev F 45 HRV200PLUS INST ALLA TION INSTRUCTIONS 9HQW L O DW L RQ &RQW U RO V 3L W RW 7XEH +5 9 3O XV$FF HVVRU . LW V 9HQ W L QJ $FFHVVR U L HV * U L O O HV * U HDVH ) L O W HU V :HDW K HU KR RG V )O RZ 6W D W L RQ P .
46 4034-102 Rev F 02/04 HR V200PLUS INST ALLA TION INSTRUCTIONS Q. REPLACEMENT PARTS.
02/04 4034-102 Rev F 47 HRV200PLUS INST ALLA TION INSTRUCTIONS INDEX A Accessories 45 Adjustable Grilles 13 Air Filters 3 Air Flow Balancing 25 Air Flows 1 Air Handler 1 Air Supply 1 1 Warmside 12 Alc.
48 4034-102 Rev F 02/04 HR V200PLUS GAS APPLIANCE LIMITED WARRANTY Hearth & Home T echnologies Inc. (HHT) extends the following warranty for Heatilator Home Product s® Heat Recovery V entilator Plus (HRV200PLUS) product s installed in homes in the United S tates of America and Canada.
デバイスHearth and Home Technologies HRV200PLUSの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Hearth and Home Technologies HRV200PLUSをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHearth and Home Technologies HRV200PLUSの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Hearth and Home Technologies HRV200PLUSの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Hearth and Home Technologies HRV200PLUSで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Hearth and Home Technologies HRV200PLUSを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHearth and Home Technologies HRV200PLUSの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Hearth and Home Technologies HRV200PLUSに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHearth and Home Technologies HRV200PLUSデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。