Application Note: L300P/SJ300 Low Current Trip Function for Pumping Applications

Please refer also to the Inverter Instruction Manual

AN081804-1

Page 2 of the Hitachi hitachi low current trip function for pumping applications user manual — Application Note: L300P/SJ300 Low Current Trip Function for Pumping Applications
2ページ · クリックして拡大
2ページ

L300P/SJ300 Low Current Trip Function for Pumping Applications Sometimes it is desirable to have the inverter trip when running at constant speed and the motor current falls below a certain threshold level. In the case of a pump, this would be indicative of absence of fluid in the pump, and hence no load on the motor. This functionality could also be useful in other applications where it is important to know that there is no load on the motor. L300P Setup The inverter incorporates an intelligent output function called Overload Advance Notice [OL]. This is ordinarily used to detect motor current higher than a user selectable threshold set with parameter C041. This signal can be configured to be active during acceleration, deceleration, and constant speed, by setting parameter C040 set to 00. This means that whether the current is above or below threshold is monitored whenever the inverter is in RUN mode. The [OL] function is configured to one of the outputs by setting either C21 or C22 to a value of “03”. There is another intelligent output function called Frequency Arrival – Type 1 [FA1]. This function turns on when the drive arrives at the set speed, and is off otherwise. This is configured to one of the outputs by setting either C021 or C022 to a value of “01”. Further, there is an intelligent input function called External Trip [EXT]. This will take a signal from outside the inverter and when turned on, will trip the inverter, displaying the unique error code of E12. We can utilize these three functions together to create an undercurrent trip at constant speed function. In this example, we will assume an L300P inverter. In our example, we will use input 5 for the External Trip [EXT] signal, output relay 11 for [FA1], and output relay 12 for [OL]. We will invert the logic of [OL] by setting C032 to “01”. This gives us [OL]. The Table 1 below shows the necessary parameter settings. The Wiring diagram on Page 5 shows the required signal connections. The Timing Chart on Page 3 shows the relationship of the input and output signals. A logical “AND” between [FA1] and [OL] is achieved by connecting the contacts in series. Table 1

ParameterC005C015C021C022C031C032C040C041 Value12000103000100Desired Low Current Threshold Level (A)*

*Parameter C041 is programmed in Amperes, and can be set from 0.1 to 2.0 times rated current for each inverter model.

Page 3 of the Hitachi hitachi low current trip function for pumping applications user manual — [FA1] (N.O.)
3ページ · クリックして拡大
3ページ

TIMING CHART

[OL] AND [FA1]

n

[OL] AND [FA1]

o

[OL] (N.C) n

[OL] (N.C) o

[FA1] (N.O.)

o

n Motor Current

Output Frequency · Time

Page 4 of the Hitachi hitachi low current trip function for pumping applications user manual — [FA1] (N.O.)
4ページ · クリックして拡大
4ページ

TIMING CHART (continued)

[OL] AND [FA1]

p

[OL] AND [FA1]

q

[OL] (N.C) p

[OL] (N.C) q

[FA1] (N.O.)

p q

TRIP

p q

Motor Current · Output Frequency

Page 5 of the Hitachi hitachi low current trip function for pumping applications user manual — 11A
5ページ · クリックして拡大
5ページ

WIRING DIAGRAM

L300P

11A

12A

CM1

Inputs · Outputs

Page 6 of the Hitachi hitachi low current trip function for pumping applications user manual — COM 5
6ページ · クリックして拡大
6ページ

SJ300 Setup Since the intelligent outputs are solid state and share a common connection internally, the SJ300 setup is slightly different. Table 2 shows the SJ300 setup. The wiring diagram is below. Instead of using a logical AND of the two output signals, we use logical OR, which is achieved by paralleling the outputs as shown. We then invert the two output signals ([OL] and [FA1]) and invert the [EXT] input versus the setup for L300P. The resulting Boolean logic provides the identical functionality. Table 2

ParameterC005C015C021C022C031C032C040C041 Value12010103010000Desired Low Current Threshold Level (A)*

WIRING DIAGRAM

SJ300

COM 5

CM1

Inputs · Outputs

Hitachi hitachi low current trip function for pumping applicationsについて質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Hitachi hitachi low current trip function for pumping applicationsに関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

Hitachi hitachi low current trip function for pumping applications 取扱説明書(PDF)

6 ページ·68 KB·ヒートポンプ·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…