INST ALLA TION INSTRUCTIONS 68-0281-16 L7224A,C; L7248A,C,L Oil and Electric Boiler Electr onic Aquastat ® Contr oller s APPLICA TION The L7224A,C and L72 48A,C,L 2012 Compliant Electronic Aquastat ® Cont rollers provide electronic temperature sensing in a UL limit-rate d control with a single sensing pr obe.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 2 Accessorie s: W8735Y1000 Wire less Outdoor Reset Kit W8735ER1000 Wi reless Outdoor Res et Module C7089.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 3 68-0281—16 New Installation Order well assemblies separate ly; see T able 1 and form no. 68-0040, Immersion Wells and Compre ssion Fittings for T emperatu re Controllers.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 4 Fig. 4. Replace ment sensor inst allation. Replacement Sensor Installation T ur n off all power and: 1. Carefully disconn ect sensor from circuit boar d by pulling gently on the connector.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 5 68-0281—16 A separate electromecha nical high-limit is no t required in a system that u ses this contr ol to meet Underwr iters Laboratorie s Inc. requirem ents for oil-fired boiler assemblies, UL 726.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 6 1 Display shows local setting; not the setting as modified by an external enviracom control. 2 Settings are viewable only if the outdoor reset module and ou t- door temperature sensor are installed and functioning properly.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 7 68-0281—16 NO TE: This feature is b locke d if a Domestic Hot W ater demand occurs.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 8 Fig. 8. L7224A, C; L7248L single hea t zone with indirec t water tank and cir culator s.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 9 68-0281—16 * Error condit ion only available when the Outdoor Reset M odule is installed. T able 6. L7224/L724 8 Controller Opera ting Sequence . Action System Respons e Thermostat calls fo r heat.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 10 . a W ar nings ar e generated to enunciate the system is not operating optimally , b ut t he Aquastat is still o perating and maintaining boiler temperature.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 11 68-0281—16 Fig. 9. L72 24A,C multiz one system with cir culator connec tions. Boiler is hot, house is cold. Display is ON. 120 V ac at C1 -C2 • 120 V ac at C1-C2, check wir ing to pump.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 12 Fig. 10. L7 224A,C sing le zone s ystem with circulator and in direct wate r tank wit h EnviraCOM™ thermosta t. M32025B POWER SUPPL Y . PRO VIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQ UIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 13 68-0281—16 Fig. 11. L72 48L multizon e system with cir culator con nections. M29655A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 14 Fig. 12. L7 224/L7248 m ultizone system wi th Outdoor Reset an d Domestic Hot W ater Modules (indirect tank applicatio ns). M32024A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 15 68-0281—16 Fig. 13. L7248L Ext ernal Low Li mit connec tions. M271 13 POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2013 Honey well International Inc.
デバイスHoneywell Cの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell Cをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell Cの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell Cの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell Cで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell Cを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell Cの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell Cに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell Cデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。