Honeywell C7015A Infrare d Flame Detector The C7015A Flame Detector includes a lead sulfide photocell that is sensitive to the infrared radiation emitted by the combustion offuels such as natural gas, oil, and coal. n q w n n Particularily suitable for combination or dual-fuel radiation is compatible with a wide range of flame applications.
C7015A SPECIFICATIONS l ORDERING INFORMATION Specifications SUPER TWELINE MODELS SUPER TRADELINE models offer features not available on TRADELINE or standard models, and are designed to replace a wide range of Honeywell and competitive controls.
WIRING CONNECTIONS: Nominal 30, 48 , or 96 in. [0.76, 1.22, or 2.44 ml leadwire+hvoNo. 18 AWG,flexible-tinnedconduc- tom; rated for 194°F [90” C]; twistedpair-onebrown and one white. Underwriters Laboratories Inc. listed: File No. MP268. Canadian Standards Association certified: Master file LR-95329-1.
C7015A OPERATION l INSTALLATION Operation OPERATION OF INFRARED DETECTORS Infrared detectors can be used with gas, oil, coal, or dual- fuel flames. Since more than 90% of the total flame radiation is infrared, these detectors receive ample radiation and can detect weak fkunes as well as flames of higher intensity.
C7015A INSTALLATION is available to facilitate flame sighting after the C7015A is pipe diameter is reduced, the effect is the same as adding an mounted. orifice plate to the pipe as discussed below. FIELD OF VIEW A lead sulfide photocell, like other photocells, views an area rather than a point.
C7015A INSTALLATION INSTALLING AN ORIFICE PLATE AnorificeplatewithahexagonalorificediameterofO.125 in. [3.2 mm] is available for the C7915A Infrared Flame Detector. The orifice can be mounted i n front of the cell in the seal-off adapter or in a standard 314 in.
C7015A INSTALLATION RESPONSE TO HOT REFRACTORY Although the infrared amplifier will not respond to steady radiation, as produced by hot refractory, be careful to protect the infrared detector from hot refractory radiation because of two possible conditions , shimmer and raa’iation saturation.
C7015A INSTALLATION CLEARANCE Make sure there will be enough mom to easily mount the sight pipe, flame detector, and all required accessories, and to remove th e flame detecto r for troubleshooting and servicing. INSTALLING THE SIGHT PIPE Thelocationofthesightpipeisthemostcriticalpartofthe installation.
c701 !?A INSTALLATION Fig. 8-installing lead sulfide photocell. CAP , MOUNTING PLUG-IN LEAD SULFIDE CELL (PART NO. 104662D) METAL CABLE SHIELDS LEADWIRES PHOTOCELL SOCKET EPOA FOCUSING LENS I Fig. O-Mounting C7015A Infrared Flame Detector (and accessories).
C7015A INSTALLATION l ADUSTMENTS AND CHECKOUT Fig. 1 O-Typical wiring of C7015A Infrared Fig. 1 l-Typical wiring of C7015A Infrared Flame Detector to nearby wiring subbase or Flame Detector to distant wiring subbase or terminal strip.
C7015A ADJUSTMENTS AND CHECKOUT and associated flame safeguard controls. Move the detector an d sight pipe around to sight the flame at various positions and angles. Try to get a maximum steady meter reading. The signal must be above the minimum acceptable current/voltage listed in Table 6.
C7015A ADJUSTMENTS AND CHECKOUT PILOT TURNDOWN TEST Ifthedetectorisusedtoproveapilotflamebeforethemain fuel valve( can be opened, perform a Pilot Turndown Test before welding the sight pipe into position. Follow the procedures in the instructions for the appropriate flame safeguard control, and the burner manufacturer instructions.
C7015A ADJUSTMENTS AND CHECKOU T l TROUBLESHOOTING n ! CAUTION FINAL CHECKOUT Before putting the burner into service, check out the installation by using the Checkout procedures in the instruc- tions for the appropriate flame safeguard control.
C7015A SERVICE n 1 CAUTION . 1. Onlyusequalifiedservicetechnicianstoattempt to service or repair flame safeguard controls and burner systems. 2. Open the master switch to disconnect power before removing or installing the detector. 3. If the C7015A is disassembled for any reason (e.
C7015A TABLE OF CONTENTS Table of Contents Page Application and Features 1 .................................................................................................................................................. 1 Specification s ...........
デバイスHoneywell C7015Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell C7015Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell C7015Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell C7015Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell C7015Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell C7015Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell C7015Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell C7015Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell C7015Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。