FlashGuard 2000B Medium Intensity Lighting System Troubleshooting Guide Table of Contents Flashhead (Strobe) Troubleshooting Flowchart pg. 2 Multiple Strobe Troubleshooting Flowchart pg. 3 Flashhead Problems pg. 4 Multiple Strobe Problems pg. 7 Flashhead Isolation Test pg.
FlashGuard 2000B Troubleshooting Guide Page 2 Flashhead (Strobe) Problems START Flashhead works in at least one mode? No Are all of the LEDs OFF? Control Power ON, High Voltage OFF? No Control Power and High Voltage Both ON ? No Yes Day mode strobe is OK, Night strobe out? Section 1, pg.
FlashGuard 2000B Troubleshooting Guide Page 3 Multiple Strobe Problems . No Strobes are flashing out of sync. Yes Section 9, pg. 8 No Strobes have a ‘double flash’ or are flashing faster than 40 FPM? Yes Section 10, pg. 8 Master switches to night, but slaves stay in day mode? Yes Section 11, pg.
FlashGuard 2000B Troubleshooting Guide Page 4 FLASHHEAD (STROBE) PROBLEMS Section 1 Flashhead does not operate in any mode, no LED’s on. Possible Cause : Input power incorrect. Diagnostic Test : Measure input power – it should be 120 VAC ±10%. Corrective Action: Supply correct input power.
FlashGuard 2000B Troubleshooting Guide Page 5 Section 3 Flashhead will not operate in any mode. Control power indicator on, high-voltage board LED indicator on. Possible Cause : Trigger control board defective, or incorrect DIP switch setting. Diagnostic Test : Perform “Flashhead Isolation Test” (pg.
FlashGuard 2000B Troubleshooting Guide Page 6 Possible Cause : Day capacitor/s or 20 Ω resistors faulty, or connection loose/open. Diagnostic Test : With all conductors attached, check resistance across the terminals of any C2 capacitor. Resistance should be @ 40 Ω Ω .
FlashGuard 2000B Troubleshooting Guide Page 7 Section 7 Flashhead flashing slow (15 – 20 flashes per minute), strobe alarm on. Possible Cause : Mis-configured or defective sync monitor board. Diagnostic Test: Ensure the DIP switches on the sync monitor board are set correctly per the manual.
FlashGuard 2000B Troubleshooting Guide Page 8 Section 10 All lights are in sync, but there is a double-flash, or flashing faster than 40 flashes per minute (fpm). Possible Cause : More than one sync monitor board is set as master. Diagnostic Test: Inspect the DIP switches on each sync monitor board.
FlashGuard 2000B Troubleshooting Guide Page 9 Flashhead Isolation Test Disconnect the seven conductor cable from power supply at terminal block TB2. Using an Ohmmeter, check the resistance between the.
FlashGuard 2000B Troubleshooting Guide Page 10 Power Supply Isolation Test Leave the seven conductor strobe cable disconnected from the power supply at terminal block TB2. Install a jumper wire between terminals 5 and 6 to simulate the interlock switch being depressed.
FlashGuard 2000B Troubleshooting Guide Page 11 Status Indicators Control Power ON • Located on the control panel (top center), this indicator is illuminated whenever input power is present and the power supply interlock switch is engaged.
FlashGuard 2000B Troubleshooting Guide Page 12 Recommended Spare Parts Flashhead Spares (Upstairs) Part Number Description 12S00602 Flashtube Assembly: FT1 77-4040K Trigger Transformer: T1 77-2644 Swi.
FlashGuard 2000B Troubleshooting Guide Page 13.
デバイスHoneywell FLASHGUARD 2000Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell FLASHGUARD 2000Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell FLASHGUARD 2000Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell FLASHGUARD 2000Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell FLASHGUARD 2000Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell FLASHGUARD 2000Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell FLASHGUARD 2000Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell FLASHGUARD 2000Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell FLASHGUARD 2000Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。