Manning GM -1 Gas Mo nitoring A larm Syste m 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 1 07/09 Release D Draft Honeywell Confidential & Proprietary This work contains valuable, confide ntial, and proprietary information.
Notices and Trademarks Copyright 2009 by Honeyw ell International In c. Release D July 2009 While this infor mation is presented in go od faith and believed to b e accurate, Ho neywell disclaims the i.
About This Document World Wide Web The following Hon eywell web sites may b e of interest. Honeywell Organization WWW Address (URL) Corporate www.honeywe ll.com Honeywel l Analyt ics www.honeywe llanalytic s.com Manning Gas Detect ion www.manning systems.
Contents Serial number: Secti on Title Page 1 System Description 5 2 Installation 7 3 Operation 10 4 Limited Warranty 13 Introduction This manual has b een prepared to h elp in the use and installatio n of the Manning GM- 1 Gas Monitoring Alarm System.
1 System Description The Manning GM-1 is designed to accept a sing le 4/20 mA curre nt input signal, plu s provide a regula ted 24 VDC supply to operat e all sensors manu factured by Honeywel l Analyt ics. The Manning GM-1 is housed in a r ugged 14 gauge gasketed steel enc losure.
1 System Description continue d System Specific ations Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp (230 VAC 50/60 Hz is available as an option) Signal input: 4/20 mA DC Power available for sensors.
2 Installation A Locating the Manning GM-1 Figure 1: Mounting dimensions for the Manning GM-1 Gas Monitoring Alarm System When unpacking the unit, ins pect all boxes and contents for sh ipping damage.
2 Installation continued B Wiring Relay Wiring: All three relays have Form C, dry contacts. An y required power source must be within the 3 amp rating and fused or current limited to keep from damaging the contacts. Electrical wiring must co mply with all applicable codes.
2 Installation continued Figure 2: Wiring diagram for the Mann ing GM-1 Gas Monitoring Alarm System NO NC C NO NC C NO NC C LN WARNING RELA Y* 120 V AC WARNING RELA Y WARNING ADJUST ALARM ADJUST TP WA.
3 Operation A Display Panel C DIP Switch Setting A 20-segment Bargr aph Display indicates the gas concentration leve l. The bottom LED is always lit to indicate power to the display. The two position DIP switch in the center of the bottom board control s the latching of t he alarm ligh t and alarm relay.
3 Operation continued D Signal and Setpoints The voltage between TP Gnd and TP Sig indicates the current sig nal received from t he sensor. Th e normal range is 0 .4 volts to 2.0 volts, which corresponds with 4/20 mA. This m anual will use the voltage at TP Sig t o describe the input signal.
3 Operation continued G Maintenance The Manning GM-1 is designed for lon g life and high reliability. Honeywell Analytics recomm ends checking signal vo ltages monthly and log ging them on the data sheet included with your M anning GM-1.
4 Limited Warranty 1. Limited Warranty Honeywell Analy tics, Inc. warrant s to the original purchaser and/or ultimat e customer (“Purchaser”) of M anning produc ts (“Product”) that if any part.
デバイスHoneywell GM-1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell GM-1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell GM-1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell GM-1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell GM-1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell GM-1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell GM-1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell GM-1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell GM-1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。