PR O -220 0 Enclosur e Ins tallation Manual P art Number: PRO22ENC 1 PRO22ENC 2 TD1138 rev080 1.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 3 Installation Guide Contents W arnings and Cautions ...................................................................................... 4 Disclaimer .....................................................
4 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide Warnings and Cautions WARNING Bef ore installation, TURN OFF the e xter nal circuit breaker which supplies pow er to the system. Bef ore connecting the de vice to the power supply , verify that the output voltage is within specifications of the power supply .
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 5 Installation Guide CAUTION If any damage to the shipment is noticed, a claim must be filed with the responsible commercial carrier . CAUTION Electro-static discharge can damage CMOS integrated circuits and modules.
6 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide Disclaimer Product Liability; Mutual Indemnification In the event that a Customer receives a claim that a Product or any component thereof has caused personal injur y or damage to proper ty of others, Customer shall immediately notify Engineered Systems in writing of all such claims.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 7 Installation Guide Shipping Instructions T o ship equipment bac k to Engineered Systems: 1. Contact the customer ser vice depar tment bef ore retur ning equipment at 800-323-4576. Please have the following available when calling: • A description of the problem or reason for returning the equipment.
8 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide Confidentiality All software, drawings, diagrams, specifications, catalogs, literature, manuals and other materials furnished by Engin.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 9 Installation Guide PRO-2200 Enclosure Description The PRO-2200 system is designed for maximum efficient use of wall space through the use of a secure metal cabinet (PRO22ENC1/PRO22ENC2) that can hold up to nine modules, a 4 amp power supply (PRO22E1PS) and a self-contained replaceable backup battery .
10 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide Dimensions ENC1 ENC2 Height: 13.9" [0.353 m] 13.9" [0.353 m] Width: 17" [0.4318 m] 18.9" [0.48006 m] Depth: 9 " [ 0 . 2286 m] 9" [0.2286 m] Metal thickness: .
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 11 Installation Guide 7. The remainder of the panels can be manually wired for power and RS-485 communications using 18 A WG wire. The wires will be daisy-chained from one panel to the next so the power and the communications are wired in parallel.
12 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide UL1076 Setup PC Minimum Requirements T wo required: • 500 Mhz • 128Mb RAM • 9.1Gb hard drive • CD ROM • 10/100 TX network card • 17 ” SVGA Monitor Peripheral Hardware Requirements • UL approv ed network HUB with at least 4 por ts.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 13 Installation Guide 4. Watchman tour 5. Fire alarm super vision (N/A) WIN P AK PR O is not cer tified for fire alarm super vision 6.
14 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 7. Use the Quer y Analyzer to connect to the WIN-P AK PR O database using the provided script for attachment. 8. Open up the ODBC application in the Control P anel and create a link to the WIN-P AK PRO SQL database .
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 15 Installation Guide 6. Clic k Ne xt . Change the Server to match the name of the LOCAL PC. The database should be selected as WIN-P AK PRO from that Server . (The destination database). 7. Click Next . Select T ransfer objects and data between SQL Server 7.
16 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide R edundant T est Examples NO TE: Stop watch needed for all three test e xamples . Example #1 1. Use the MAIN PC’ s OFF button to shut it do wn. T ur n on the REDUND ANT PC and star t the stop watch.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 17 Installation Guide Power Supply Enclosure + DC - AL400ULXB L G N ALTRONIX CORP . BKLYN, N.Y. 11220 MADE IN USA PTC3 NO C NC NO C NC + BA T - DC 24V - OP.
18 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide Installation Installation Instructions 1. I ns ta ll th e P RO22ULPS ( A ltronix AL400ULX) power supply and battery enclosure per the supplied instructions. 2. Measure and install four mounting screws with heads smaller than .
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 19 Installation Guide Cable Specifications Application ESG Part No. AWG Description Max. Dist. Im p. Cap. N-485 connections* NC2442- TN N/A Belden 9842 4000' (1200 m) 120 Ω 12.
20 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide ESG Cable Part Numbers Part Number Description Application Length NC1841-GY 18 AWG/4 conductor reader cable 1, 000' [305 m] NC18.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 21 Installation Guide NOTES.
22 PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide NOTES.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 23 Installation Guide.
Honeywell Security & Data Collection 2700 Blankenbak er Pkwy , Suite 150 Louisville, KY 40299 (800) 675-3364 www.honeywellaccess.com.
デバイスHoneywell PRO22ENC1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell PRO22ENC1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell PRO22ENC1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell PRO22ENC1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell PRO22ENC1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell PRO22ENC1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell PRO22ENC1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell PRO22ENC1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell PRO22ENC1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。