ROOM AIR CONDITIONER SERVICE MANUAL CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORIZED SERVICE MODEL: LT143CNR.
—2— 1. PREF A CE 1.1 SAFETY PRECAUTIONS ...............................2 1.2 INSULATION RESISTANCE TEST.................2 1.3 SPECIFICATIONS ..........................................3 1.4 FEATURE S ................................................
—3— 1.3 SPECIFICA TIONS 1.3.1 FOR LT143CNR LT143CNR POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°C) TEMPERATURE OUTDOOR (°C) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
1.4 FEA TURES • Designed for cooling only. • Powerful and quiet cooling. • Top-down chassis for the simple installation and service. 1.5 CONTR OL LOCA TIONS 1.5.1 COOLING ONL Y MODEL • OPERA TION • Side air-intake, side cooled-air discharge.
— 6 — 2.1 MECHANICAL P AR TS 2.1.1 FRONT GRILLE 1. Open the inlet grille downward. 2. Remove the screw which fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. (See Fig. 1) 5. Re-install the component by referring to the removal procedure.
Figure 7 — 7 — 2.2 AIR HANDLING P AR TS 2.2.1 ORIFICE, AND TURBO F AN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the 2 screws which fasten the evaporator at the left side and the right side.
— 8 — 2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Fig. 9) 3. Re-install the components by referring to the removal procedures, above. 2.3 ELECTRICAL P AR TS 2.3.1 MO T OR 1. Remove the cabinet. (Refer to section 2.
— 9 — 2.3.4 PO WER CORD 1. Remove the control box. (Refer to section 2.1.3) 2. Unfold the control box. (Refer to section 2.3.3) 3. Disconnect the grounding screw from the Base pan. 4. Disconnect 2 receptacles. 5. Remove a screw which fastens the clip cord.
— 1 0 — 2.4 REFRIGERA TION CYCLE 2.4.1 CONDENSER 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the brace. (Refer to section 2.2.1) 3. Remove the 7 screws which fasten the condenser. 4. After discharging the refrigerant completely into a Freon TM Recovery System, unbraze the interconnecting tube at the condenser connections.
— 1 1 — — Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a Freon TM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon TM .
— 1 2 — Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
— 1 3 — 3. INST ALLA TION 3.1 INST ALLA TION REQUIREMENTS If you use an existing wall sleeve, you should measure its dimensions. Install the new air conditioner according to these installation instructions to achieve the best performance.
— 1 4 — 3.2 INST ALLA TION • Pick a location which will allow the conditioned air to blow into the area you want. Good installation with special attention to the proper position of the unit will lessen the chance that service will be needed. ITEMS IN INSTALLATION HARDWARE You may not need all parts in the kit.
P R OCEDURE If you are using the new sleeve (optionally A s u pplie d w it h y o u r unit),sk i p t o ste p 3 . Otherwise, install the plastic grille from the kit. Cut the plastic grille to 25-1/2" wide and 15-1/4" high. Place the plastic grille to the inside of the wall sleeve at the rear flange.
— 16 — PR OCEDURE B Redirect the louvers at the back of the wall sleeve to 60 ° angle as shown in the FIG 8 . The use of pliers is recommended. If the wall sleeve already has a rear grille, skip to step 4. If the wall sleeve does not have a rear grille or louvered panel, install the plastic grille from the kit.
— 1 7 — PR OCEDURE B CONTINUED Remove the backing from the support blocks and attach them to the inside of the wall sleeve as shown FIG 29 . Slide the baffle into slots of the support blocks. Install the new unit into the wall sleeve. Assemble trim as described in Step 6, Procedure A.
— 18 — Depth"D" of the e xisting wall slee ve (inches) Length "A" (inches) Suppor t Block Baffle A A 3 / 4 1- 3 / 4 4 18 D 18- 5 / 8 18- 5 / 8 D 19- 3 / 4 19- 3 / 4 D 22 FIG. 3 4 3.5 PR OCEDURE C Redirect the louvers at the back of the wall sleeve to 60 ° angle as shown in the FIG 3 0 .
— 19 — 7 1" high 3 / 4 " High Shim (2EA) 6" 6" FIG. 3 7 • Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.
— 20 — 4. TR OUBLESHOO TING GUIDE 4.1 OUTSIDE DIMENSIONS 20- 3 / 32 " (499mm) 24" (610mm) 14- 13 / 32 " (366mm) MODE TIMER POWER FAN SPEED Fan Energy Saver Cool Timer TEMP ' F F1 LOW F2 MED F3 HIGH CONDENSER COILS EV APORA TOR COILS FA N M OTO R : REFRIGERANT FLOW TURBO F AN CAPILLAR Y TUBE COMPRESSOR 4.
— 21 — 4.3 TR OUBLESHOO TING GUIDE In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
— 22 — Fails to Start Check circuit break er and fuse. Gas leakage at f eeler bulb of ther mostat Check control s witch. Only f an f ails to star t. Improper wiring. Def ect of f an motor capacitor . Irregular motor resistance ( ). Irregular motor insulation ( ).
— 2 — 23 — COMPLAINT CAUSE REMEDY Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for terminal identification.
— 24 — NAME PLATE RATING MINIMUM MAXIMUM 115V 103.5V 126.5V 208/230V 187V 253V COMPLAINT CAUSE REMEDY Check voltage. See the limits on the preceding. page. If not within limits, call an electrician. Check the wire connections, if loose, repair or replace the terminal.
— 25 — COMPLAINT CAUSE REMEDY Check the voltage. See the limits on the preced- ing page. If not within limits, call an electrician. Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.
— 26 — 5. SCHEMA TIC DIA GRAM 5.1 CIRCUIT DIA GRAM • MODEL : BG-101A/LT1010CR/LT121CSG/LT1210CR /LT0810CR/LT080CSG/BG-81A LT1030CR/LT1230CR/BG-123A/LT1430CR.
—2 7 — 6. EXPLODED VIEW • MODEL: 567502 554160 550140 359012 352380 346811 554031 149980 352115 35211A 130410 435300 147582-1 147581 135303 152302 147582-2 135312 349480 352113 552113 W48602 354.
P/No.: 3828A20294 T February, 200 7 Printed in China.
デバイスHotpoint LT143CNRの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Hotpoint LT143CNRをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHotpoint LT143CNRの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Hotpoint LT143CNRの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Hotpoint LT143CNRで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Hotpoint LT143CNRを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHotpoint LT143CNRの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Hotpoint LT143CNRに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHotpoint LT143CNRデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。