Hubbell Electric Heater CompanyメーカーWATER HEATER DFの使用説明書/サービス説明書
ページ先へ移動 of 27
OPERATING AND MAINTENANCE MANUAL FOR POWER BURNER SERIES FORCED DRAFT COMMERCIAL WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL “ DF ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: ht tp://www.hubbe llheat ers .com / -- IMPORTANT -- Always reference the f ull model num ber and serial num ber when calling the factory.
3 FOR YOUR SAFETY WHAT TO DO IF Y OU SM ELL G AS ¾ DO NOT try to light any applianc e. ¾ DO NOT touch any el ectrical swit ch. ¾ DO NOT use any phone in the building. ¾ I mmediately call y our gas supplier from a neig hbor's phone. Follow the g as supplier's instructions.
4 SAFETY TEMPERATURE AND PRES SURE RELI EF VALVE (T&P) A listed and proper ly rated combination temper ature and pre ssure relief valve shall be installed in the opening provided and marked for this purpose at the time of installation. Local codes shall govern installati on of relief devices.
5 TABLE OF C ONTEN TS SECTION TITLE PAGE # I G E N E R A L D E S C R I P T I O N 9 I I I N S T A L L A T I O N 1 0 III S T A R T U P AND OPERATION 16 I V S CHEDULED MAINTENANCE AND SER VI CING 18 V TR.
6.
.
8.
9 SECTION I - GENERAL DESCRIPTION GENERAL DESCRIPTION This i s a commercial storage water heater desi gned and constructed in accordance with UL and ASME requirements. Its thermal efficiency and standby loss ex ceed the levels established by ASHRAE 90.
10 SECTION II – INSTALLATION WARNING / CAUTION For protection against excessive pressures and temperatures, local codes require the installation of a temperatur e-and-pr essure (T&P) relie f val.
11 LOCATION NOTE: Do not run uninsulated water pipes in front of or directly above a fresh air opening. I f an exhaust fan is installed in the mechanical room, the combustion a ir inlet must allow for the fan's exhaust air volume. An undersized opening may cause down drafts resulting in poor combustion, sooting and carbon monoxide.
12 be installed so the he ater may be disconnected for ser vicing if ne cessary . Hot water and return circulation lines should be insulated. The cold water supply line should be insulated if subjected to freezing temperat ures.
13 ELECTRICAL C ONNECTIONS Electrical connections to the water heater should conform to the National Electrical Code or the code legally authorized in your locality .
14 GAS CONNECTION PIPING F O R GAS AND COMBINATION GAS/OIL BURNERS WARNING / CAUTION L P UNITS; liquefied petroleum (L .P.) gas is heavier tha n air and will remain at floor le vel if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of l eaking L.
15 3. A Rule of Thumb to determine total suction for suction line sizing is to add 10% to suction determined from the burner manufacturer's instruction manual. 4. I t is good practice to size the oil pump return-line (to the tank) the same size as the selected suction line.
16 SECTION III – START UP AND OPERATION WARNING / CAUTION Temperatures above 130ºF (54º C) can cause scalding. Scalding temperatures are especially hazardous to y oung children, aged or handicapped persons. A serious or disabling injury can occur.
17 2. The burner manufacturer's installation and operation manual, included with this manual, contains a detailed start up procedure that should be studied and followed precisely . NOTE: Rate d gas input for this water heater can be established by adjusting manifold gas pressure to the value listed on the burner data plate.
18 SECTION IV - SCHEDULE D MAINTENANCE AND SE RVICING WARNING / CAUTION Before performing any maintenance procedure, turn off the water heater main disc onnect switch before performing any cleaning or service. Also close both the pilot and main manual shutoff valves.
19 RECOMMENDED PERIODIC INSPECTION DAILY 1. I nspect area around water heater for moisture. If present, determine if cause is condensation or leakage. a. If cause is condensation - May be due to very cold incoming water. Consider installation of intra-tank circulator; contact manufacturer for details.
20 RECOMMENDED PERIODIC TES TING TESTING ITEM HOW OFTEN COMP LETED BY REMARKS Gauges, m onitors and operating log Daily Operator Make vis ual inspection and record readings Instru men t and equipmen t.
21 SCALE AND S EDIMENT REMOVAL THE MANUFACTURER CANNOT CONTROL USE OF THE WATER HEATER, WATER CONDITIONS OR MAINT ENANCE. THE WATER HEATER WARRANTY DOE S NOT.
22 BURNER SERVICE IMPORTANT IT IS HIGHLY RECOMMENDE D THAT REPLACEME NT PARTS OR ASSEMB LIES BE OBTAINED FROM THE WATER HE ATER OR BURNER MANUFACTURER.
23 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water and boiler water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one.
24 IMMERSION TEMPERATURE HIGH LIMIT CUT-OFF, HIG H, OR LOW THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover. 3. Remove high limit c over screw and cover. Cover Cover Screw Reset Tab (Hig h Limit Only ) 4. Disconnect the two (2) 14 gauge wires.
25 SECTION V – TROUBLESHOOTING (See separate component O &M for add itional d etails.) Symptom Probable Cause Corrective Action / Remedy Flame safeguard locked out. Reset flame safeguard. Manual gas valve closed. Open gas valve and reset flame safeguard.
26 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.
27 METRIC CONVERSIONS.
デバイスHubbell Electric Heater Company WATER HEATER DFの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Hubbell Electric Heater Company WATER HEATER DFをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHubbell Electric Heater Company WATER HEATER DFの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Hubbell Electric Heater Company WATER HEATER DFの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Hubbell Electric Heater Company WATER HEATER DFで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Hubbell Electric Heater Company WATER HEATER DFを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHubbell Electric Heater Company WATER HEATER DFの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Hubbell Electric Heater Company WATER HEATER DFに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHubbell Electric Heater Company WATER HEATER DFデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。