April, 2000 Hubbell Industrial Controls, Inc. A subsidiary of Hubbell Incorporated 50 Edwards St. Madison, OH 44057 Telephone (440) 428-1161 FAX (440) 428-7635 Instruction Manual Fire Pump Controller Model LX-1500 Limited Service Electric Publication No.
Limited Service Fire Pump Controller Page 2 of 12 Table of Contents I Introduction .................................................................................................................................. 3 II Specifications and Certifications .
Limited Service Fire Pump Controller Page 3 of 12 I Introduction The Hubbell Limited Service Fire Pump Controller provides automatic and manual control of small electric motor driven fire pumps and booster pumps of 30 horsepower or less.
Limited Service Fire Pump Controller Page 4 of 12 Undervoltage Trip 15% below set point Time Delays Pick-up, 1.5 s, fixed Drop-out, 1.5 s, fixed Output Relays 10 A, 120 VAC 5 A, 240 VAC Indication gre.
Limited Service Fire Pump Controller Page 5 of 12 Caution: Before drilling and punching holes in the cabinet for wiring connections, cover the components inside the cabinet with a protective covering. Debris may cause shorts or prevent operation of components.
Limited Service Fire Pump Controller Page 6 of 12 still timing, the CR relay remains energized and the motor continues to run for the duration of the timer setting. Pressing the STOP push button stops the motor even if TR1 is timing. If the Controller does not have a TR1 timing relay, the pump motor runs until the STOP push button is pressed.
Limited Service Fire Pump Controller Page 7 of 12 VI Start Up Procedure Danger: Shocks, burns, or death may result from high voltage. Caution: Only personnel who are familiar with the power distribution system and this manual should be allowed to perform this procedure.
Limited Service Fire Pump Controller Page 8 of 12 11. Press the STOP push button to stop the motor. 12. Start and stop the motor with the EMERGENCY MANUAL CONTROL handle. Push and rotate the T-handle in a quick motion to lock the contactor in the ON position to start.
Limited Service Fire Pump Controller Page 9 of 12 VII Maintenance Danger: Do not open the Controller cabinet until ALL power is disconnected. Shocks, burns, or death may result from high voltage.
Limited Service Fire Pump Controller Page 10 of 12 Coil and Contact Replacement Coil Retainers Coil Spring Clip Magnet Assembly Figure VI -1 Magnet Assembly and Retainers Coil Replacement* Contact Replacement* 1. Isolate all power sources. Complete steps 1 through 5 in left column.
Limited Service Fire Pump Controller Page 11 of 12 VIII Limited Service Fire Pump Controller Parts Spares Symbol Description Function Part No. 1 1 CR, LRSR LK, PFR, PRR High Voltage Relay 2-Pole Relay Starting Relay Control Relay 31658141 31658123 2 FU1, FU2 Fuse, 1 A, MDL-1 Control Power 57361726 1 TR1 Timing Relay, octal Min.
Limited Service Fire Pump Controller Page 12 of 12 Spares Symbol Description Function Part No. CB ( Note 3 ) Breaker, 15 A Breaker, 20 A Breaker, 25 A Breaker, 30 A Breaker, 40 A Breaker, 50 A Breaker.
デバイスHubbell LX-1500の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Hubbell LX-1500をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHubbell LX-1500の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Hubbell LX-1500の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Hubbell LX-1500で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Hubbell LX-1500を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHubbell LX-1500の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Hubbell LX-1500に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHubbell LX-1500デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。