OPERATING AND MAINTENANCE MANUAL FOR STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL “ ST and STH ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: htt p://www.hubbellhe ate rs.co m/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory.
3 TABLE OF C ONTENTS SECTION TITLE PAG E # I GENERAL DESCRI PTION AND CONSTRUCTI ON 9 I I INSTAL L ATION AND OPERATI ON 13 III S C H E D U LE D M A IN TE NANC E AND SERVICI NG 18 I V ADJUSTMENT OF TEM.
4.
5.
6 NOMENCLATURE FOR PARTS.
7 NOMENCLATURE FOR ACCE SSORY PARTS.
8.
9 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged steam powered water heater that is a stationary , self-contained unit.
10 3. Stainless Steel – Stainless steel (ty pe 304, 316, or 316L) is well suited for high purity applications requiring a corrosion resistant tank with minimal leaching of impurities into the water. Well suited for process, RO, and DI water sy stems in the pharmaceutical, food, and electronic industries.
11 STEAM OPERATING CONTROLS The steam operating controls are factory selected, sized, piped, and tested to ensure reliable operation. Steam controls can be shipped loose, upon request, for in the field installation by others. All steam components are factory plumbed with schedule 40 black iron pipe and ready for steam and condensate connections.
12 OPTIONS The following optional features may be included in your water heater. Reference the drawing specific to y our heater for further details. Single Solenoid Safet y System A single solenoid safety system closes the steam supply to the control valve should the temperature in the tank reach the high limit set point.
13 SECTION II – INSTALLATION AND OPERATION WARNING / CAUTION DO NOT TURN ON THE STEAM SUPPL Y to this unit until hea ter is completely filled with water and all air has been released. If the heater is NOT filled with water when the steam supply is turned on, damage to the heating coil may result.
14 3. I nstall the combination temperature and pressure safety relief valve in the tapping provided. Note that this is required by law for safety considerations. Outlet to floor drain I n s t a l l i n t o p r o v i d e d t a p p i n g Manual Release Lev e r T e m p e r a t u r e P r o b e 4.
15 Typical Piping Diagram ELECTRICAL IN STALLATION 1. If the unit is furnished with a pilot or self contained control valve, no external source of power is required for the valve. (See enclosed operation and maintenance manual for specific valves). 2.
16 FILLING THE HEATER 1. Begin with all steam, condensate, and water valves closed. 2. Open the isolation valves on the integral circulator line ,if supplied. 3. Open cold water valve, fill unit with cold wate r. L ift lever on relie f valve to relieve trapped air.
17 SHUTDOWN 1. Close valve to heating medium and air supply valve, if air operated controls are furnished 2. Disconnect all el ectrical power to uni t. 3. Close hot water outlet valve. 4. Close building recirculation inlet valve, and shut down building circulation pump.
18 SECTION III - SCHEDULED MAINTE NANCE AND SERVICING WARNING / CAUTION Before performing any maintenance procedure, make certain steam supply and electrical power supply is OFF and cannot accidentally be turned on. QUARTERLY INSPECTION 1. Monitor thermostat a.
19 11. Convection packages may be equipped with an integ ral circulator. This circulator should be serviced per the enclosed pump O&M manual. 12. The unit as well as all strainers should be blown down regularly to remove any trash, and sediment that may have accumulated.
20 occur at this point, but a s the gasket se ats, leaking will g radually stop). After leak ing has stopped, turn the nut approximately 1 revolution. At this point there may be some miner seepage, wait a few minutes to see if this seepage stops.
21.
22.
23 SINGLE SAF ETY SOLENOID SYSTEM (if inst alled).
24 DOUBLE SAF ETY SOLENOID SYSTEM (if installe d).
25 SECTION IV – ADJUSTMENT OF TEMPERATURE RE GULATORS 1. The spring tension on temperature regulators is adjusted at the factory to meet design conditions. However, design conditions may vary from actual operating conditions and re- adjustment might be required on this job.
26 f. Apply air pressure to valve diaphragm so that stem halves are aligned and re-connect stem halves. g. If valve will not open with air on the diaphrag m, spring tension should be decreased. h. Adjustment is essentially the same as if spring tension wer e increase d except the adjustment screw is turned in the opposite direction.
27 c. Spence Valv es : There is no main spring adjustment on Spence Valves. To set temper ature on the water heater: (1) Turn pilot spring a djustment “A” cloc kwise until all tension is off the spring. (2) Refer to unit sta rt-up section a nd start unit except for the rmostat setting .
28 SECTION V – TROUBLESHOOTING (See separate component O &M for add itional d etails.) Symptom Probable Cause Corrective Action / Remedy T u b es a r e f o u l e d . C l e a n t u b e s p er S e c t i o n III, a nnual scheduled maintenance. Excess silt in bottom of tank.
29 High rate of flow bey ond design conditions. Consult factory . Excessive vibration. Under sized piping to the unit. Re-pipe lines to unit using proper sized lines. Defective steam t rap. Repair or replace per separate O&M. Undersized condensate lines.
30 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI L I CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.
31 METRIC CONVERSIONS.
デバイスHubbell STの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Hubbell STをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHubbell STの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Hubbell STの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Hubbell STで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Hubbell STを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHubbell STの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Hubbell STに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHubbell STデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。