1 DURA-POWER MODELS NW 37- 670 COMMERCIAL ELECTRIC W A TER BOILERS • Inst allation • Operation • Service • Maintenance • Limited Warranty PLACE THESE INSTRUCTIONS ADJACENT T O THE BOILER AND NOTIFY OWNER T O KEEP FOR FUTURE REFERENCE.BE SURE THA T THE W ARRANTY INFORMA TION HAS BEEN FILLED IN ON COMPLETION OF INST ALLA TION.
2 DIMENSIONAL DA T A SIZES AND DA T A 45KW THRU 720KW Model Number Inlet* & Boiler Prefix Gal.Cap. Std.KWInput D E F G** H J K S T U Outlet* Drain N W 37 45K 32 30 12 42 12 1 /2 - - 20 4 42 3 1 N .
3 SIZES AND DA T A 780KW THRU 3300KW Model Number Inlet* & Boiler Prefix Gal.Cap. Std.KWInput D E F G** H J K S T Outlet* Drain N W 220 780K 60 50 25 71 21 2 25 1/2 30 5 1/ 2 5 1 1/ 2 N W 220 840K.
4 ELECTRICAL/RECOVER Y DA T A MODEL AND RA TING PLA TE W A TER BOILER SPECIFICA TIONS Model Number Gal. Std. KW BTU Output Gal./Hr . Number of Number of Standard Number Amperage 3 Phase Prefix Cap.
5 APPROV ALS These designs comply with requirements of Underwriters Laboratories and bear the U.L. label on the cabinet. All models are built to the standards of Section lV of the American Society of Mechanical Engineers. Boiler and Pressure Code, inspected and identified by this symbol.
6 IMPORT ANT IT IS RECOMMENDED THA T A QUALIFIED SER VICE TECHNICIAN PERFORM THE INITIAL FIRING OF THE BOILER. A T THIS TIME THE USER SHOULD NOT HESIT A TE TO ASK THE TECHNICIAN ANY QUESTIONS WHICH THEY MA Y HA VE IN REGARD TO THE OPERA TION AND MAINTENANCE OF THE BOILER.
7 Calculating Amperage/Overcurrent Protection The boiler is factory wired for connection to three wire single-phase or three and four wire three-phase branch circuits. In addition, a ground conductor may be required. A diagram of the wiring is furnished with the boiler for the electrician’s use.
8 ELECTRICAL CONFIGURA TION T ABLE Boiler T ype V olt age Between Control Elements Nameplate o f Boiler T erminal Circuit Quantity Element Markings Service Lugs V ol t age Per Operating V oltage Phase.
9 WIRING DIAGRAM 480V THREE-PHASE (WYE) SYSTEM CLEANING The hot water system should be internally cleaned and flushed to remove contaminants which may have accumulated during installation. System cleaning provides chemical stability necessary for component life and system performance.
10 4. Close the vent as water starts to flow from the opening. Place the make-up water valve in the desired position. The boiler is now ready for ST ART UP and TEMPERA TURE REGULA TION if being placed in operation for the first time.
11 • Use a twisting, pulling action to remove elements scaled beyond the size of the tank opening. • Brush loose scale from elements. • Silicates, sulfates and aluminates must be removed by scraping or other mechanical means. Lime scale dissolvents will not remove these types of scale which are occasionally encountered.
12 NW -37 THRU NW-670 ELECTRIC HOT W A TER BOILER LIMITED W ARRANTY A.O. Smith Corporation, the warrantor , extends the following LIMITED WARRANTY to the owner of this boiler .
デバイスA.O. Smith NW 37-670の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
A.O. Smith NW 37-670をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはA.O. Smith NW 37-670の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。A.O. Smith NW 37-670の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。A.O. Smith NW 37-670で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
A.O. Smith NW 37-670を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はA.O. Smith NW 37-670の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、A.O. Smith NW 37-670に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちA.O. Smith NW 37-670デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。