INSTALLATION INSTRUCTIONS AND USERS MANUAL HOT WATER STORAGE TANKS MODEL: ST 1500-3000 FOREWORD Before attempting to install th is water heater please read the insta llation instructions. An authorized installer must install the heat er an d commission it according to the local valid requirements.
CONTENTS 1. GENERAL 1.1 Description of the heater 3 1.2 Controls 3 1.3 Dimensions 3 1.4 Technical data 5 2. FOR THE INSTALLER 2.1 Installation 5 2.2 Water connections 6 2.3 Commissioning 7 2.3.1 Filling the heater 7 2.3.2 Heater start-up 7 2.4 Shutting down 7 2.
1. GENERAL 1.1 Description of the heater Construction of the heater is in accordance wi th the European standard f or water heaters or sanitary use. The heaters are suitable for use with a working pressure of up to 7 bar. The cylindrical tank is made from sheet steel .
1.4 Technical specifications ST 1500/2000 ST 2500/3000 1 Storage capacity ltr 1500/2000 2500/3000 2 Tank heat loss kWh/24h 8.5 10.1 3 Maximum working pressure bar 7 7 4 Test pressure tank bar 12 12 5 Maximum allowed tank temperature °C 95 95 6 Weight empty kg 374/506 637/739 2.
Back-up element 6 1 = drain (on small tanks only) 2 = valve 3 = check valve 4 = pressure relive valve 5 = circulation pump sanitary water 6 = temperature sensor for boiler three way valve A = circulat.
2.3 Commissioning 2.3.1 Filling the tank 1. Check if any installed drain valve is closed. 2. Open the cold-water supply valve to the heater 3. Open all hot-water outlets in order to bleed all air from the system . The heater is filled when cold water runs out of all outlets.
2.5.2 Descaling Calcium precipitation depends on the water properties and the hot water demand. In addition, calcium precipitation in the tanks in creases at high water tem peratures. A clean out opening is located at the front for inspecting and des caling the tank.
4. WARRANTY 4.1 Warranty in general If within one year of the origin al installa tion date of the tank s upplied by A.O. Sm ith any part or component other than the tank sh all prove upon examination by A.O. Smith, and in the exclusive opinion of the latter, to be defective in material and/or workmanship, A.
4.4 Exclusions The warranty ensuing from sections 4.1 and 4.2 will be null and void: a. If the tank has been damaged by external causes. b. In case of misuse, neglect (including fros t damage), incorrect or improper use of the tank, or if attempts have been made to repair leaks; c.
ST 1500-3000 series Kit installation instructions 1 – Contents of flange kit Bag A Flange plate Designation Quantity Bolts 6 Gasket 1 Flange plate 1 Bag D 1 Bag D Flange collar and cover fixation sc.
2 – Mounting instructions for flange cov ers, anodes, T&P and insulation package IMPORTANT: Start with mounting two plug anodes in the lo wer and center anode opening on the side of the tank. In the top anode opening you need to mount the o utlet anode with T-piece for T&P relieve valve (included) and ther mometer (not included).
3 – Mounting instruction for rigid jacket Center each jacket segment on one of the feet .. Nota : top panels, once placed, fixate the jacket. 4 – Mounting of the flexible jacket Install the flexible jacket before mounting the cl ean out colla r and cover.
デバイスA.O. Smith ST 3000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
A.O. Smith ST 3000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはA.O. Smith ST 3000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。A.O. Smith ST 3000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。A.O. Smith ST 3000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
A.O. Smith ST 3000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はA.O. Smith ST 3000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、A.O. Smith ST 3000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちA.O. Smith ST 3000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。