AmtrolメーカーWH-7 Classic Seriesの使用説明書/サービス説明書
ページ先へ移動 of 32
INSTALLER: LEAVE THIS MANUAL WITH THE OWNER IMPORTANT GENERAL SAFETY INFORMATION - ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
-2- 1. TABLE OF CONTENTS 2. Pre-Installation Checklist ................................................. 2 3. Required Components and Accessories Checklist ......... 3 4. WH-7 & 9 Classic Series Piping Installation .................... 4 5. Top Down™ TD-Series Piping Installation .
-3- 3. REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST SHUTOFF VACUUM RELIEF THERMAL EXPANSION MODEL CIRCULATOR ZONE VALVE* VALVE BREAKER VALVE TANK DRAIN Residential = 5GPM *If Circulator not used Requ.
-4- 4. WH-7 & 9 CLASSIC SERIES PIPING INSTALLATION DOMESTIC WATER PIPING 1. Thread the included 3 / 4 ” brass tee onto the pipe marked COLD WATER. 2. Screw the 3 / 4 ” dra in va lve in to th e opp osi te en d of th e bra ss tee. 3. Connect th e col d wat er supply to the r emaini ng po rt on the brass tee.
-5- PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR.
-6- 5. TOP DOWN™ TD-SERIES PIPING INSTALLATION DOMESTIC WATER PIPING 1. Connect the cold water supply to the pipe labeled COLD WATER 2. Connect the HOT WATER piping to the domestic hot water system. 3. Make an 8-inch “heat trap” on the HOT WATER outlet as shown in the diagram.
-7- PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR.
-8- 6. READY-TO-RUN RTR-SERIES PIPING INSTALLATION DOMESTIC WATER PIPING 1. Connect the cold water supply to the pipe labeled COLD WATER. 2. Connect the HOT WATER piping to the domestic hot water system. 3. Make an 8-inch “heat trap” on the HOT WATER outlet as shown in the diagram.
-9- PIPING MODELS WITH PRE-INSTALLED CIRCULATOR W/INTEGRAL FLOW CHECK.
-10- 7. WHS PREMIER SERIES PIPING INSTALLATION DOMESTIC WATER PIPING 1. Thread the includ ed brass tee onto the pipe mar ked COLD WATER. 2. Screw the drain valve into the opposite end of the brass tee 3. Connect th e col d wat er supply to the r emaini ng po rt on the brass tee 4.
-11- PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR.
-12- 8. WIRING ALL SMART CONTROL ™ MODELS The Smart Control™ incorporates all the switching and temperature control functions necessary to control the BoilerMate™.
-13- 1 2 T T L1 L2 L8124 A & C ZC ZR B2 C1 B1 C2 BOILERMA TE ® CIRCULA TOR BOILERMA TE ® JUNCTION BOX (PLACE A WIRE NUT OVER EACH WIRE NOT USED) HONEYWELL L8124 A & C ORANGE ORANGE BLUE BLUE.
-14- HONEYWELL L8148 J WITH MILLIVOL T GAS V A L VE BOILERMA TE ® JUNCTION BOX (PLACE A WIRE NUT OVER EACH WIRE NOT USED) ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK BOILERMA TE ® CIRCULA TOR .
-15- WHITE - RODGERS 8J48A WITH SELF-GENERA TING GAS VA L VE 8J48A BOILERMA TE ® JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK (PLACE A WIRE NUT OVER EACH WIRE NOT USED) B1 B2 TV W T.
-16- BOILERMA TE ® CIRCULA TOR BOILERMA TE ® JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK L8148A L2 L1 C1 C2 B1 B2 3 T B R T L1 L2 PRIORITY WIRING HONEYWELL L8148A HIGH LIMIT PRIOR.
-17- PRIORITY WIRING HONEYWELL L8148 J WITH MILLIVOL T GAS V A L VE L8148J BOILERMA TE ® CIRCULA TOR BOILERMA TE ® JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK HI LIMIT T TV W TP Z.
-18- T T X X Boiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs T ypical Multi-Zone Relay Utilizing Post-Purge Feature Smart Control™ ORANGE ORANGE BLUE BLUE VIOLET VIOLET BLACK WHI.
The Smart Control™ features an error code designed to alert the user to the presence of water on the oor . This is useful to warn of a leaking boiler , water heater , etc., or to alert the owner to a leak in the basement. If equipped with the optional water sensor , follow the installation instructions below: W ater Sensor Plug 1.
-20- 9. WIRING ALL DIAL CONTROL MODELS (EXCEPT RTR MODELS) Dial Control models utilize a standard dry-cont act aquastat with capillary temperat ure sensor. The dial control contains a make-and-break switch and is suitable for 24V or 120V, 25A Max. To wire Dial Control models, select the appropriate diagram from the following pages.
-21- T T X X Boiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs T ypical Multi-Zone Relay BoilerMate ® Circulator BoilerMate ® Thermostat PRIORITY W/CIRCULATORS - SCHEMATIC 4 ZONE V.
-22- BOILER CONTROL - SCHEMATIC 5 HONEYWELL L8148E ORANGE ORANGE BLUE BLUE VIOLET VIOLET BLACK WHITE SMART CONTROL™ JUNCTION BOX (PLACE A WIRE NUT OVER EACH WIRE NOT USED IN THE AMTROL BOILER MA TE ® JUNCTION BOX.
-23- Ready- To-Run models include a circula tor with built-in priority zoning relay. The aquastat is pre-w ired and controls the circulator. Line voltage must be supplied and a signal wire must be run to fire the boiler. To wire RTR models, select the appropriate diagram from the following pages.
-24- CIRCULA TOR RELA Y BOX 1 234 C1 C2 Indirect A quastat LIVE NEUT PR OUT PR IN L1 L2 L1 L2 T T HEA TING CIRCULA TOR REMOVE JUMPER BETWEEN 1 & 3 3 HONEYWELL L8148A OR SIMILAR W/PRIORITY CIRCULA .
-25- 11. STARTUP PROCEDURE FOR ALL MODELS 1. PURGE HEAT EXCHANGER: The heat exchanger should be free of large air pockets to allow the circul ator to operate properly . Using the diagram below as a g uide, iso late the boile r return line and flu sh the loop until large air pock ets are purged.
-26- GREEN LIGHT - CIRCULATOR INDICATOR MODE SWITCH READOUT DISPLAY The Smart Control™ incorporates multiple features that increase hot water performance and efficiency. All settings are accessed via the MODE button. To change any setting, simply hold the MODE button then tap to cycle through the settings as outlined below.
-27- 1. No power to unit 2. Air in heat exchanger loop 3. Faulty circulator or zone valve 4. Faulty BoilerMate™ thermostat 5. Faulty Smart Control™ 6. Boiler inoperable 1. Demand exceeds capacity 2. Temperature too low 3. Boiler lacks sufficient output 4.
-28- WH-7, 41 WHS 60 & 80 WHS 120 WHS 60 & 80 WHS 120 and 9 Series TD-7 Series TD-7 RTR TD-80 Series Residential Residential Commercial Commercial Single Wall Heat Exchanger w/Gasket and Nuts .
A diminished temperature difference between the boiler water entering and leaving the heat exchanger coil may indicate heat exchanger scale buildup. Water treatment equipment and proper maintenance will help to avoid this problem. To clean a scaled heat exchanger coil proceed as follows: 1.
-30- 15. GENERAL SAFETY INFORMATION SCALDING HAZARD . If the water temperature is over 120°F, household mem ber s ca n su ffe r ser ious or fata l sc al din g and pa inful and permanent injury.
-31-.
West Warwick, Rhode Island 02893 Part #: 9040-586 (07/08) Boiler Mate, AMTROL, AMTROL logo, Therm-X-T rol, Radiant EXTROL and EXTROL are r egistered trademarks of AMTROL Inc.
デバイスAmtrol WH-7 Classic Seriesの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Amtrol WH-7 Classic Seriesをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAmtrol WH-7 Classic Seriesの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Amtrol WH-7 Classic Seriesの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Amtrol WH-7 Classic Seriesで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Amtrol WH-7 Classic Seriesを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAmtrol WH-7 Classic Seriesの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Amtrol WH-7 Classic Seriesに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAmtrol WH-7 Classic Seriesデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。