B AC-10000 Series 1 Operation Guide, Rev . J Oper ation Guide B A C-10000 Series FlexStat ™ B A Cnet Progr ammable T hermostats Contents Over vie w ................................................................ 2 Applications and Installation ....
B AC-10000 Series 2 Operation Guide, Rev . J Ov er vie w The KMC FlexStat series of intelligent temperature/ humidity/occupancy-sensing, w all-mounted, ther- mostat/controllers are native BACnet Advanced Application Controllers (B-AAC) for use in a BAC- net system.
B AC-10000 Series 3 Operation Guide, Rev . J WED 11/19 3:20 PM COOL: OCC: FAN: HUM: 36% RH Oper ation (Basic) Enter Button Right /Menu Button Left /Ov erride Button Down /Setpoint Button Up /Setpoint .
B AC-10000 Series 4 Operation Guide, Rev . J Configur ation (Initial Setup) NOTE: Menus shown in this document reect rmware version R1.3.0.4 or later . Actual context-sensitive screens are dependent on rmware version, FlexStat model, and options selected.
B AC-10000 Series 5 Operation Guide, Rev . J Adv anced Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS The Adv anced Menu displays v arious submenus. Not all submenus can be seen on the screen at one time. Scroll up or down to see additional submenus.
B AC-10000 Series 6 Operation Guide, Rev . J Sensor Setup SENSOR SETUP IN 2: DISCH AIR TEMP The Input 2 sensor (AI2) can be congured for discharge air temperature (T ype III thermistor is the default), fan status (dry contact), or unused.
B AC-10000 Series 7 Operation Guide, Rev . J (Adv anced) B A Cnet Communications COMMUNICATIONS MAC ADDRESS: BAUD RATE: 38400 MAX MAS TER: 127 1 T o set parameters for BACnet MS/TP EIA-485 communications, press: 1. Up / Down to move among entries. 2.
B AC-10000 Series 8 Operation Guide, Rev . J (Adv anced) T emp. Setpoint Limits LIMITS OCC MIN CL G: OCC MAX HTG: 76° F UNOCC MIN CL G: 77° F UNOCC MAX HTG: 65° F 71° F T o set the minimum and maximum allowed user/ operator setpoint v alues, press: 1.
B AC-10000 Series 9 Operation Guide, Rev . J (Adv anced) Security Lev els and P asswor ds SECURITY ACCESS LEVEL S PASSWORDS ACCESS LEVEL S SETPOINT ADJ: MAIN MENU: ADMIN S YS TEM MODE: OPER OCC OVERRI.
B AC-10000 Series 10 Operation Guide, Rev . J (Adv anced) T est TES T L CD/KEY TEST The test menu merely tests the display’ s pixels and key functions.
B AC-10000 Series 11 Operation Guide, Rev . J Date/T ime DATE/TIME DATE: TIME: 1:43:59 PM APR 11 2009 T o enter date and time information (only), press: 1. Up / Down to move among entries. 2. Enter to select. 3. Right / Le to move among v alue elds.
B AC-10000 Series 12 Operation Guide, Rev . J HOLIDAY S HOL1: HOL2: MAR 21 2009 HOL3: MAY 26 2009 HOL4: JUL Y 4 2009 HOL5: SEPT 1 2009 HOL6: NOV 2 7 2009 HOL7 : NOV 28 2009 JAN 1 2009 The Holiday entries will override the normal occupied weekly schedule entries and keep those days’ seings at their setback values.
B AC-10000 Series 13 Operation Guide, Rev . J System Setup SYS TEM S YS TEM ENABLE: OCC OVRIDE (HRS): 1.0 INACTIVITY (SECS): 60 DISPL AY BLANKIN G: NO AUTO T o adjust the system conguration values, such as system enable (auto, o, heat, or cool), occupancy override time, and display inactivity time-out: 1.
B AC-10000 Series 14 Operation Guide, Rev . J Resetting the FlexStat T ypes of Reset If the FlexStat is not operating correctly or if a low limit alarm has occurred , the FlexStat should be reset (reinitialized).
B AC-10000 Series 15 Operation Guide, Rev . J Restore F actor y Restore Factory (restoring the FlexStat to the factory seings) does the following: • Clears present v alues. • Restores the object database/conguration to the defaults. • Restarts the controller ’ s (factory installed) Con- trol Basic programs.
B AC-10000 Series 16 Operation Guide, Rev . J BA Cnet MS/TP Network Communication Connect the network wiring and set the EOL switch- es accordingly . (See the Installation Guide for wiring and end-of-line switch information.) From the FlexStat menus, adjust the device instance number , the MAC address, and baud rate from the defaults as necessary .
B AC-10000 Series 17 Operation Guide, Rev . J T roubleshooting Alarm Issues Alarm, (F alse) F an F ail • Check conguration. Be sure the Fan Status option is not selected when there is no sensor/ switch for it. • Check that the IN2 (fan status) input pull-up resistor switches are fully latched in the correct positions.
B AC-10000 Series 18 Operation Guide, Rev . J Co v er and Displa y Issues Cov er Binds on Bac kplate • Carefully remove the FlexStat cov er from the backplate and inspect for bent pins and/or termi- nal socket connectors. If cover pins are bent, use a needle-nose pliers to straighten them.
B AC-10000 Series 19 Operation Guide, Rev . J Input, Sensor , and V alue Issues Input V alues Are Outside the Expected Range • Check that ALL the input pull-up resistor switches are fully latched in the correct positions. See the Connections and W iring section of the relev ant BAC-10000 Series Installation Guide.
B AC-10000 Series 20 Operation Guide, Rev . J F an Does Not Run NOTE: The animated fan icon is coupled with BV18 in the packaged programming (not the actual fan output terminal). • Select Occupied mode from the Home Menu— see H/C, Fan, Occupancy, and Override on page 3 .
B AC-10000 Series 21 Operation Guide, Rev . J +B –A IN4 IN3 GND IN2 Common / – / C Phase / / R Analog 9 GND 7–9 Analog 8 Analog 7 Rela y 6 SC 4–6 Rela y 5 Rela y 4 Rela y 3 SC 1–3 Rela y 2 R.
B AC-10000 Series 22 Operation Guide, Rev . J Firmw are Upgr ade The existing version of rmw are can be viewed from the About the FlexStat screen. (See About the Flex- Stat on page 4 ). Firmw are in the FlexStat can be upgraded using a PC and a KMD-5699 rmw are ash upgrade kit av ailable from KMC Controls.
B AC-10000 Series 23 Operation Guide, Rev . J Important Notices The KMC logo and T otalControl are registered trademarks and BACstage is a trademark of KMC Controls, Inc.
B AC-10000 Series 24 Operation Guide, Rev . J Reference Common acronyms and abbreviations in FlexStat and related documents include: amp = amperes A = amperes AAC = Adv anced Application Controller A/C = air conditioning AC = alternating current AHU = air handling unit avg.
B AC-10000 Series 25 Operation Guide, Rev . J For denitions of v arious terms in this document, refer to the aw ard-winning pocket-sized Green Building and Con- trols Glossary (SB-046) . A hyperlinked online version can be downloaded from the Brochures section of KMC Controls web site, www.
B AC-10000 Series 26 Operation Guide, Rev . J Index Symbols 4 x 4 Hand y Box Mounting Plate: 22 A Abbreviations: 24 About the FlexStat: 4 Access Levels, P assword: 9 Accessories: 22 Acronyms: 24 Adjustment.
B AC-10000 Series 27 Operation Guide, Rev . J G Glossary , Green Buildings Controls: 25 H Heat, Cool, A uto, Off (System Enable): 13 HMO-10000 Mounting Plate: 22 Home (T emperature Displa y) Screen: 3.
B AC-10000 Series 28 Operation Guide, Rev . J © 2010 KMC Controls, Inc. 913-019-02J KMC Controls, Inc. 19476 Industrial Drive, New P aris, IN 46553 574.
デバイスKMC BAC-10000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
KMC BAC-10000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはKMC BAC-10000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。KMC BAC-10000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。KMC BAC-10000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
KMC BAC-10000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はKMC BAC-10000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、KMC BAC-10000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちKMC BAC-10000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。