7/2012 506945-01 *2P72012* *P506945-01* Page 1 E 2013 Lennox Industries Inc. Dallas, T exas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE W ARNING The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death.
Page 2 A B SIDE VIEW UNIT DIMENSIONS - INCHES (MM) FIGURE 2 T ABLE 1 UNIT DIMENSIONS Model Numbers A B 13ACX-018-230 24-1/4 (616) 25-1/4 (641) 13ACX-024-230 24-1/4 (616) 25-1/4 (641) 13ACX-030-230 24-.
Page 3 13ACX SERIES ANCHORED HEA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER‐TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON-CORROSIVE MET AL SLEEVE V APOR LINE - WRAPPED IN ARM.
Page 4 STEP 2 -- REFRIGERANT PIPING -- Flushing Existing Line Set and Indoor Coil Flush the existing line set per the following instructions. For more information, refer to the Installation and Service Procedures manual available on DaveNet.
Page 5 13ACX SERIES STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device SENSING LINE TEFLON ® RING FIXED ORIFICE BRASS NUT LIQUID LINE ASSEMBL Y (INCLUDES STRAINER) LIQUID LINE O.
Page 6 STEP 2 -- REFRIGERANT PIPING -- Brazing Procedures A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SERVICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE.
Page 7 13ACX SERIES WHEN BRAZING LINE SET TO SER VICE V AL VES, POINT FLAME A WA Y FROM SER VICE V AL V E. LIQUID LINE SERVICE V AL VE LIQUID LINE BRAZE LINE SET Wra p both service valves with water -saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.
Page 8 STEP 2 -- REFRIGERANT PIPING -- Installing Indoor Expansion V alve This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or expansion valve metering device (purchased separately) at the indoor coil.
Page 9 13ACX SERIES STEP 3 -- LEAK TEST AND EV ACUA TION A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only). B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit.
Page 10 STEP 3 -- LEAK TEST AND EV ACUA TION (CONTINUED) A Open both manifold valves and start the vacuum pum p. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once.
Page 1 1 13ACX SERIES STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing In t he U .S .A., w iring must conform with current local codes a nd the current National Electric Code (NEC). In Canada, wiring must conform with cur rent local codes and the current Canadian Elec trical Code (CEC ).
Page 12 STEP 4 -- ELECTRICAL (CONTINUED) -- High V oltage and Field Control Wiring The following illustration provide an example of control wiring connections when using standard thermostat. Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring.
Page 13 13ACX SERIES T ABL E 3 . T O RQUE REQUIREM ENTS Parts Recommended Torque Service valve cap 8 ft.- lb. 1 1 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb.
Page 14 CHECKING AND ADDING SYSTEM REFRIGERANT The 13ACX unit is factory-charged with enough HFC-410A refrigerant to accommodate a 15-foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker located o n th e unit access panel.
Page 15 13ACX SERIES 13ACX Start-Up and Performance Checklist Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Notes: ST ART UP CHECKS Refrigerant T ype: Rated Load Amps: Actual Amp.
デバイスLennox International Inc. 506945-01の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lennox International Inc. 506945-01をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLennox International Inc. 506945-01の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lennox International Inc. 506945-01の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lennox International Inc. 506945-01で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lennox International Inc. 506945-01を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLennox International Inc. 506945-01の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lennox International Inc. 506945-01に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLennox International Inc. 506945-01デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。