HEAT PUMP KITS AND ACCESSORIES ©1993 Lennox Industries Inc. 502,673M Dallas, Texas 9/93 Supersedes 3/92 Litho U,S,A. SOLID STATE DEFROST REPLACEMENT BOARD INSTALLATION INSTRUCTIONS FOR SOLID STATE DE.
TOP VIEW FRONT VIEW REPLACEMENT BOARD _J f REMOVE EXISTING BOARD Use existing hole to install replacement board I ®1 DEFROST TIME INTERVAL JUMPER 9O 6O 0 _o RST HLD 24V OUT COM _ INTERNAL JUMPER Drill new hole into control box panel FIGURE 1 _] HIGH PRESSURE SWITCH LOSS OF , CHARGE .
The defrost control is a solid state control manufactured by Hamilton Standard.The control provides automaticswitching from normal heating operation to defrost mode and back. The defrost controlcontains a solid state timer which switches an externa] defrost relay through 1/4" male spades mounted on the control'scircuit board.
DEFROST CONTROL TROUBLESHOOTING FLOWCHART START HERE I Check control transformer primary and secondary voltages. Repair or replace as necessary. I Turn off power to unit.
デバイスLennox International Inc. LB-83114Cの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lennox International Inc. LB-83114Cをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLennox International Inc. LB-83114Cの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lennox International Inc. LB-83114Cの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lennox International Inc. LB-83114Cで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lennox International Inc. LB-83114Cを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLennox International Inc. LB-83114Cの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lennox International Inc. LB-83114Cに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLennox International Inc. LB-83114Cデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。