Lennox International Inc.メーカーMerit Series 14ACX Unitsの使用説明書/サービス説明書
ページ先へ移動 of 30
07/1 1 506645−01 *2P0711* *P506645-01* Page 1 201 1 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These instructions are intended as a general guide and do not supersede local codes in any way . Consult authorities who have jurisdiction before inst allation.
Page 2 506645−01 Unit Dimensions − Inches (mm) SUCTION AND LIQUID LINE CONNECTION DISCHARGE AIR SIDE VIEW OUTDOOR COIL F AN COMPRESSOR A B A OPTIONAL UNIT ST ANDOFF KIT (4) (FIELD INST ALLED) SIDE.
Page 3 14ACX SERIES T ypical Unit Parts Arrangement COMPRESSOR HARNESS CONNECTION LIQUID LINE SERVICE V AL V E SUCTION LINE SERVICE V AL VE OUTDOOR COIL DISCHARGE LINE HIGH PRESSURE SWITCH (S4) COMPRE.
Page 4 506645−01 CAUTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury . Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Page 5 14ACX SERIES (V AL VE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE SERVICE PORT CORE SER VICE PORT CAP ANGLE−TYPE SERVICE V AL VE (FRONT−SEA TED CLOSED) SER VICE PORT CORE TO OUTDOOR UNIT STEM.
Page 6 506645−01 Recovering Refrigerant from Existing System Use the following procedure to recover refrigerant from an existing system (indoor coil, line set and outdoor unit). SER VICE DISCONNECT SWITCH MAIN FUSE BOX/BREAKER P ANEL Disconnect all power to the existing outdoor unit at the service disconnect switch or main fuse box/breaker panel.
Page 7 14ACX SERIES 6 (152) 36 (914) 12 (305) 30 (762) LINE SET CONNECTIONS 24 (610) LINE SET CONNECTIONS ACCESS P ANEL 48 (1219) MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES (MILLIMETERS) ACCESS P ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES: Clearance to on e of the o ther three sides must be 36 inches (914mm).
Page 8 506645−01 PLACING UNIT ON SLAB When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.
Page 9 14ACX SERIES New or Replacement Line Set This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on p age 1 1.
Page 10 506645−01 ANCHORED H EA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER-TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON−CORROSIVE MET AL SLEEVE V APOR LINE − WRAPPED IN .
Page 1 1 14ACX SERIES Brazing Connections Use the procedures outline in figures 9 and 1 0 for brazing line set connections to service valves. IMPORT ANT Polyol ester (POE) oils used wit h HFC−410A refr igerant absorb moisture very quickly . It is very important that the refrigerant sys tem be kept closed as much as possible.
Page 12 506645−01 A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SER VICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE SERVICE VA LV E SUCTION / V APOR LIN.
Page 13 14ACX SERIES WHEN BRAZING LINE SET TO SER VICE V AL VES, POINT FLAME A W A Y FROM SER VICE V A L VE. LIQUID LINE SERVICE V AL VE LIQUID LINE BRAZE LINE SET W rap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set .
Page 14 506645−01 Flushing Line Set and Indoor Coil Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering Device on page 15 .
Page 15 14ACX SERIES Installing Indoor Metering Device This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or exp ansion valve metering device (purchased sep arately) at the indoor coil.
Page 16 506645−01 IMPORT ANT The Environmental Protection Agency (EP A) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery , recycling or reclaiming must be followed.
Page 17 14ACX SERIES Evacuating Line Set and Indoor Coil A Open both manifold valves and start the vacuum pump. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once.
Page 18 506645−01 W ARNING Danger of Equipm ent Damage. A void deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compress or failure. Damage caused by deep vacuum operat ion will void warranty .
Page 19 14ACX SERIES Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. T o facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
Page 20 506645−01 HIGH PRESSURE SWITCH (S4) LIQUID LINE CRANKCASE THERMOST A T (S40) CRANKCASE HEA TER (HR1) Figure 16. T ypical Factory Wiring Diagram (Copeland Compressor).
Page 21 14ACX SERIES CRANKCASE HEA TER (HR1) HIGH PRESSURE SWITCH (S4) LIQUID LINE CRANKCASE THERMOST A T (S40) THERMAL PROTECTION SWITCH (S5 OR S173) Figure 17.
Page 22 506645−01 Servicing Units Delivered V oid of Charge If the out door unit is void of refrigerant, clean the system using the procedure described below . 1. Leak check system using procedure outlined in this instruction. 2. Evacuate the system using procedure outlined in this instruction.
Page 23 14ACX SERIES CHECKING AIR FLOW A T INDOOR COIL Check airflow using the Delta−T ( D T) process using the illustration in figure 19. 1. Determine the desired D T Measure entering air temper- ature using dry bulb ( A ) and wet bulb ( B ). D T is the intersect- ing value of A and B in the t able (see triangle).
Page 24 506645−01 Liquid Line Set Diameter Ounces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m) line set* 3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m) *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft.
Page 25 14ACX SERIES 1. Confirm proper airflow across coil using figure 19. 2. Compare unit pressures with table 4, Normal Operating Pressures . USE WEIGH-IN METHOD Weigh-in or remove refrigerant based upon line length SCº (Subcooling) V alues (F:+/−1.
Page 26 506645−01 ST ART : Measure outdoor ambient temperature NOTE − Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5ºF at the suction line service port.
Page 27 14ACX SERIES T able 4. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig) IMPORT ANT Use this t able to perform maintenance checks; it is not a procedur e for charging the system. Minor variations in these pressures may be due to differences in instal lations.
Page 28 506645−01 System Operation UNIT COMPONENTS IMPORT ANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded.
Page 29 14ACX SERIES Indoor Unit 1. Clean or change filters. 2 . Lennox blower mot ors are prelubricat ed and permanent ly sealed. No more lubr ication is needed. 3 . Adjust blower speed for cooling. Meas ure the pressure drop over the coil to determ ine the corr ect blower CFM.
Page 30 506645−01 S tart−Up and Performance Checklist Job Name Job no. Date Job Location City S tate Installer City S tate Unit Model No. Serial No.
デバイスLennox International Inc. Merit Series 14ACX Unitsの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lennox International Inc. Merit Series 14ACX Unitsをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLennox International Inc. Merit Series 14ACX Unitsの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lennox International Inc. Merit Series 14ACX Unitsの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lennox International Inc. Merit Series 14ACX Unitsで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lennox International Inc. Merit Series 14ACX Unitsを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLennox International Inc. Merit Series 14ACX Unitsの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lennox International Inc. Merit Series 14ACX Unitsに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLennox International Inc. Merit Series 14ACX Unitsデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。