Thank Y ou! Thank y ou for selectin g the American Power Conversion SmartSlot Series Measure-UPS II . It has been desi g ned for man y y ears of reliable, mainte- nance-free service. Please read this manual! It provides installation and operatin g instructions that will help y ou g et the most from y our accessor y .
Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Operation Check . . . . . . . . . . . . .
1. Introduction The SmartSlot Measure-UPS II performs temperature and humidit y sensin g , as well as contact monitorin g . Measure-UPS II supports up to four zones of contact monitorin g , each of which supports both normall y open and normall y closed contacts.
Safety Notice The SmartSlot Measure-UPS II UPS accessor y is intended solel y for use in supplementar y surveillance of equipment. APC does not recom- mend this product for life or propert y protection. APC will not know- in g l y sell Measure-UPS II for use in such applications.
2. Installation Use the followin g procedure to install SmartSlot Measure-UPS II : 1. Install and configure an y software or hardware that will be used with Measure-UPS II for data reporting (see software and hard- ware compatibility abov e). 2. Using figure 2 as a guide, install Measure-UPS II in the host SmartSlot.
Do not: • Cov er any of the ventilation holes on the probe • Immerse the probe or place it where de w can be expected to form • Use the probe in an en vironment with chlorine gas or insecti- cides. 5. The contact monitoring connection is a two piece design.
3. Operation Check 1. Confirm the basic operation of Measure-UPS II . Use the data reporting system (see hardware and software compatibility in sec- tion 1) to confirm that Measure-UPS II is w orking.
4. Sensor Zone Connections Connection Information Measure-UPS II supports normall y open and normall y closed loop s y stems, and allows mixin g of normall y open and normall y closed sensors on an y zone. See the fi g ures below for more information on usin g multiple sensors in one zone and for s y stem hookup.
In order to avoid receivin g alarm indications on unused zones, install a j umper wire between the COM and NC connectors for each unused zone. T o use more than one sensor on a zone, follow the dia g ram below . Connect normall y open sensors in parallel and normall y open sensors in series.
See below for a t y pical hookup. Note that in this example s y stem zone 1 is a normall y closed motion zone with power for the passive infrared detector supplied b y Measure-UPS II . Zone 2 is a normall y open zone. Zone 3 is a combination normall y open and normall y closed zone.
5. Sensor Selection Measure-UPS II ma y be used with an y dr y contact closure t y pe sen- sors. The Measure-UPS II sensor inputs are desi g ned to monitor cir- cuits that have no volta g e potential of their own.
6. Maintenance Measure-UPS II requires periodic maintenance. Confirm contact sens- in g usin g the sensor manufacturers recommended intervals and meth- ods. Use the data reportin g s y stem to verif y that each sensor operates as planned. Clean the temperature (or temperature and humidit y ) probe whenever there is a visible buildup of dust.
7. T roubleshooting Problem Possible Cause Solution Constant Alarm on one or more unused zones. Unused zones not jumpered. Connect a wire between the COM and NC terminals of all unused zones (see section 4). Constant low tem- perature and humid- ity readings.
8. Service If the SmartSlot Measure-UPS II requires service: 1. Check Measure-UPS II using the troubleshooting chart in section 7 before calling for service. 2. Note the model number of the Measure-UPS II , the serial number , and the date purchased. See the back cov er of this manual for the correct telephone number and call customer service.
9. Specifications Electrical SmartSlot specification compatible Operatin g volta g e: 16 - 27 Vdc Operatin g current draw: 30 mAdc (exclusive of an y attached sensors) T emperature accurac y : ±2° C (± 3.
10. Declaration of Conformity Application of Council Directives: 89/336/EEC Standards to Which Conformit y is Declared: EN55022, EN50082-1 Manufacturers Name: American Power Conversion 132 Fair g roun.
Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obli- gation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products.
デバイスAPC SmartSlot Seriesの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
APC SmartSlot Seriesをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAPC SmartSlot Seriesの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。APC SmartSlot Seriesの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。APC SmartSlot Seriesで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
APC SmartSlot Seriesを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAPC SmartSlot Seriesの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、APC SmartSlot Seriesに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAPC SmartSlot Seriesデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。