990-1216B 02/2004 User Manual English APC Smart APC Smart APC Smart APC Smart- - - -UP S UPS UPS UPS ® ® ® ® RT RT RT RT 7500/10000 VA 200 7500/10000 VA 200 7500/10000 VA 200 7500/10000 VA 200- - .
.
1 Introduction The APC Smart-UPS RT is a high-performance, uninterruptible power system (UPS), designed to prevent blackouts, brownouts, sags and surges from reaching your com puters, servers, and other sensitive electronic equip ment. 1: I NST ALLA TION Attention: Re ad the safety i nformation sheet be fore installation.
2 Hardwiring Attention: Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring only. 2. Switch the UPS input ci rcuit breaker (see A ) and utility circuit breakers OFF.
3 7. XLI model only: For three-phase input, set the Input Phase Selector switch (see C ) to ‘3’. For single-phase input, leave switch in default position of ‘1’. 8. Switch the circuit breakers ON. 9. Check line voltages. 10. Replace the access panel.
4 Installing and Connecting the Batteries and Attaching the Front Bezel .
5 C ONNECTING P OWER AND E QUIP MENT TO THE UPS 1. Hardwire the UPS (see Hardwiring ). 2. Connect equi pment to the UPS (cables not included for X LT/XLJ/XLTW m odels). 3. Turn on all connected equipm ent. To use the UPS as a m aster on/off switch, be sure that all connected equipm ent is switched ON.
6 B ASIC C ONNECTORS Serial Port Power management software and interface kits can be used with the UPS. Use only inter face kits suppli ed or approved b y APC.
7 2: O PERA TION F RONT D ISPLAY P ANEL Indicator Description Online The UPS is drawing utility power and performin g double conversion to sup ply power to connected equipm ent (see Troubl eshootin g ). On Battery The UPS is supplying battery powe r to the connected equipment.
8 Feature Function Normal /Bypass Manually switch connected eq uipment to bypass mode, so that utility power is sent directly to connected equipment. Battery op eration is not available while the UPS is in bypass mode. (See Troubleshooting. ) Cold Start This is not a normal condition.
9 3: U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , W EB /SNMP CA RD , OPTIONAL S MA R T S LOT ACCESSORY CARDS OR T ER MINAL M ODE .
10 N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , W EB /SNMP CA RD , OPTIONAL S MA R T S LOT ACCESSORY CARDS OR T ER MINAL M ODE .
11 EPO (Emergency Power Off) Option The output power can be disabled i n an emergency by closing a s witch connected to the EPO. Adhere to national and loca l electrical codes when wiring. The switch should be connected in a normally open switch contact.
12 Terminal Mode to Configure UPS Parameters Terminal Mode is a menu driven interface that enables en hanced configuration of the UPS. Connect the serial cable to the serial port on the back of t he UPS. When using Po werChute ® Network Shut down software: 1.
13 4: S TOR AG E , M AINTE NANCE , AND T RANSPORTING Storage Store the UP S covered a nd positi oned as for pro per functioni ng, in a cool , dry locatio n, with the batteries fully charged.
14 5: T ROUBLESHOOTING Use the table below to solve minor installation and operation prob lems. Refer to the APC web site, www.apc.com , for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON Batteries are not connected properly.
15 P ROBLEM AND P OSSIBLE C AUS E S OLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of ope ration, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position.
16 Service If the UPS requires service do not return it to the dealer. Instead, follow these steps: 1. Review t he problem s discussed in the Troubl eshooting section of t his manual to eliminate common pr oblems. 2. If the pr oblem persists, contact APC C ustomer Se rvice through t he APC we b site, www.
17 6: R EGULA T OR Y AND W ARRANTY I NFORMA TION Regulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V MODELS This is a Class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take corrective actions.
18 Declaration of Conformity.
デバイスAPC SURT10000RMXLT-2TF5の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
APC SURT10000RMXLT-2TF5をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAPC SURT10000RMXLT-2TF5の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。APC SURT10000RMXLT-2TF5の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。APC SURT10000RMXLT-2TF5で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
APC SURT10000RMXLT-2TF5を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAPC SURT10000RMXLT-2TF5の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、APC SURT10000RMXLT-2TF5に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAPC SURT10000RMXLT-2TF5デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。