APCメーカーSYAF16KXR9Iの使用説明書/サービス説明書
ページ先へ移動 of 25
Symmetra LX Rack-mount UPS Symmetra LX T ower UPS Symmetra LX Rack-mount Extended Run Symmetra LX T ower Extended Run Symmetra LX Operations Guide ® For use with Symmetra LX UPS Models: 200 V , 4–8.
.
T ABLE OF C ONTENTS Chapter 1: Overview ............................................................................................................ ....... 1 PowerView ..................................................................................
.
C HAPTER 1: O VERVIEW 1 Overview This manual provides an ov erview of operations for the Symmetra ® LX and Extended Run Cab inet, including detailed explanations of monitoring, co ntrol, and configuration through the PowerView user interfac e. Illustrations are representative.
C HAPTER 1: O VERVIEW 2 Navigation Keys Name Sound Function ? Help Short beep Opens context-sensitive help. Enter Short beep Opens the selected menu item or setting. Two short beeps When pressed simultaneously for about one second, resets the PowerView RM interface.
C HAPTER 2: B ASIC C OMMANDS 3 Basic Commands Supply Power to the UPS This procedure supplies po wer to the Symmetra LX and do es not supply power to the equipment connected to the UPS. 1. Turn ON the AC utility power to the UPS 2. Switch ON the circuit breake rs for all connected equipment.
C HAPTER 2: B ASIC C OMMANDS 4 Set the Correct Output Voltage 1. Press the ‘Esc’ button until the Ma in Menu appears. Use the up and do wn arrow keys to choose ‘Setup’, and ENTER to select. Control Logging Status Display >Setup Diags Accessories Help 2.
C HAPTER 2: B ASIC C OMMANDS 5 5. In approximately 90 seconds, the green Load On indicator will illuminate and this message will appear. UPS LOAD IS ON Press any key… Turn Off UPS Output Power and Load Equipment 1. Press ‘Esc’ until the Main Menu appears.
C HAPTER 2: B ASIC C OMMANDS 6 Command Bypass Command Bypass requires utilization of the c ommands on the PowerView display. This mode is used to bypass the UPS electronics and direct ly supply power to the load. Follow the steps below to directly connect the output powe r of the UPS to the branch circuit (mains) usin g the command bypass mode.
C HAPTER 2: B ASIC C OMMANDS 7 Language Setting The factory default language of the us er inte rface is English. You can change the langua ge by downloading new firmware into the PowerView. French, German, Italian, and Spanish are availa ble on the enclosed CD.
C HAPTER 2: B ASIC C OMMANDS 8 Language Setting (continued) 6. Locate the language program file to be downloaded into the UPS. See the APC website at http://www.
C HAPTER 3: M ENU C OMMANDS 9 Menu Commands The following sections describe the details of each co mman d. Commands are organized according to the menu hierarchy in the Po werView. Accessories Menu The Accessories Menu allows you to monitor APC accessories if they are installed.
C HAPTER 3: M ENU C OMMANDS 10 Display Menu The Display Menu allo ws the user to customize the PowerView display. Display Function Options Date/Time Sets the correct date and time. Date: dd-mmm-yyyy Ex:11-Aug-2003 Time: hh:mm:ss Ex: 21:36:10 Password Protects against unauthorized configuration changes.
C HAPTER 3: M ENU C OMMANDS 11 Diagnostics Menu The Diagnostics Menu prov ides useful information for troubleshooting. Menu Item Function Fault and Diagnostics Displays current sy stem f ault and diagnostic information of that fault. (Main) Intelligence Module Displays detailed in tellige nce module status and information.
C HAPTER 3: M ENU C OMMANDS 12 Logging Menu (continued) Menu Item Function List Event Groups Lists the specific events in each group. Power Events UPS Control Events User Activiti es UPS Fault Event s Measure UPS Events Clear Log Clears the view log. Does not clear the active event lists.
C HAPTER 3: M ENU C OMMANDS 13 Setup Menu The Setup Menu allo w s the user to customiz e the UPS functionality. Menu Item Function Options Shutdown Sets the shutdown parameters in the event of a utility pow er failure.
C HAPTER 3: M ENU C OMMANDS 14 Setup Menu (continued) Menu Item Function Options Alarms Sets the alarm thresholds. None Redundancy An audible alarm sounds if the redundancy falls below this level. 0 (default), 1, or 2 Load An audible alarm sounds w hen the load exceeds this limit.
C HAPTER 4: T ROUBLESHOOTIN G 15 T roubleshooting The PowerView reports various messages on the displa y, i ncluding alarm status and changes in system configuration. This section lists all the Po werView display messages, the reason for the message, and the appropriate corrective action.
C HAPTER 4: T ROUBLESHOOTIN G 16 Condition PowerView Message Reason Correcti ve A ction AC adequate for UPS but not for bypass. The UPS will funct ion on-line with the input voltage. But, in the event that bypass is required, the input voltage is not adequate to power the load equipment.
C HAPTER 4: T ROUBLESHOOTIN G 17 Condition PowerView Message Reason Correcti ve A ction Redundancy Restored. Power module redundancy loss occurred and was restored. Additional modules have be en installed or the load has been reduced. Load is No Longer above Alarm Threshold.
C HAPTER 4: T ROUBLESHOOTIN G 18 Condition PowerView Message Reason Correcti ve A ction Redundancy is below alarm threshold. Actual power module redundancy has fallen below the user-specified redundancy alarm threshold. The power module(s) failed or the load has increased.
C HAPTER 4: T ROUBLESHOOTIN G 19 Condition PowerView Message Reason Correcti ve A ction On Battery. The UPS is in the on-batter y mode. The battery modules are being discharged. No corrective action is necessary. Note: The runtime duration is limited.
C HAPTER 4: T ROUBLESHOOTIN G 20 Condition PowerView Message Reason Correcti ve A ction Input circuit breaker tripped open. The input circuit breaker on the UPS tripped open. Input voltage is disconnected from the UPS. Option 1: If this occurs in conjunction with an overload condition, decrease the load and reset the breaker.
C HAPTER 5: S ERVICE 21 Service If the UPS requires service, do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Tro ubleshooting chapter to eliminate common pr oblems. 2. Verify that the circuit breakers have not tripp ed.
デバイスAPC SYAF16KXR9Iの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
APC SYAF16KXR9Iをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAPC SYAF16KXR9Iの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。APC SYAF16KXR9Iの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。APC SYAF16KXR9Iで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
APC SYAF16KXR9Iを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAPC SYAF16KXR9Iの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、APC SYAF16KXR9Iに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAPC SYAF16KXR9Iデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。