NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS .....................................................1 Clearances From Combustible Materials .
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE CAUTION: Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure.
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch- ing control or wires. 5. Use this procedure for installed and uninstalled (un- grounded) furnaces.
CAUTION: Air for combustion must not be contami- nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
c. When ducts are used, they must be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in. (See Fig. 3.) WARNING: Do not install the furnace on its back; safety control operation will be adversely affected.
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement. V. GAS PIPING Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.
WARNING: Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death. CAUTION: Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the control board. The gas service pressure must not exceed 0.
1. Heating mode When the wall thermostat "calls for heat," the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor. a. Prepurge period—As the inducer motor comes up to speed, the pressure switch contacts close to begin a 15-sec prepurge period.
→ Fig. 11—Unit Wiring Diagram A95335 PCB BLOWER OFF DE LAY SELECTION CHAR T 90 SEC 135 SEC 180 SEC 225 SEC GVR HI/LO RELAY SEC-1 SEC- 2 PL1 3 2 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DELAY G R Y W C HUM HSIR IDR BLWR BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC-3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1.
unit and the combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 termi- nal is energized with 115v when the blower is operating on cooling speed. When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower and EAC continue operating on cooling speed for an additional 90 sec.
b. Check gas input rate by clocking gas meter. (1.) Obtain average yearly heat value for local gas supply. (2.) Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY. CAUTION: DO NOT redrill burner orifices. Improper drilling (burrs, out of round, etc.
(3.) When correct input is obtained, replace regulator seal cap. Main burner flame should be clear blue, almost transparent. (See Fig. 13.) d. High altitude—In the United States gas input on rating plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent less for each 1000 ft above sea level.
3. Set thermostat heat anticipator. The thermostat heat anticipator must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 14 illustrates an easy method of obtaining the actual amp draw.
A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization.
© 1996 BDP Co. • P.O. Box 70 • Indianapolis, IN 46206 Printed in U.S.A. —16— 395c4010 Catalog No. BDP-3339-518.
デバイスLG Electronics 395CAVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
LG Electronics 395CAVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLG Electronics 395CAVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。LG Electronics 395CAVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。LG Electronics 395CAVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
LG Electronics 395CAVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLG Electronics 395CAVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、LG Electronics 395CAVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLG Electronics 395CAVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。