S I T E M O N I T O R I N G ■ ■ ■ ■ ■ ■ ■ ■ MR1 Mi ni-Re m ote Env i ronmental Monitor U SER M ANUAL DISCONTINUED PR ODUCT.
DISCONTINUED P R O D U C T.
TA BLE OF CONTENTS Section 1: INTRODUCTION .......................................................................................... 1 Specific ations ...................................................................................................
Figure 1. Typical System Configuration DISCONTINUED P R O D U C T.
DISCONTINUED P R O D U C T.
Section 1: INTRODUCTION The Liebert MR1 Mini-Rem ote monitors the operating status and controls the operation of your Liebert Env ironmental unit. It serv es as a remote user interface, supplementing the unit-front controls.
NOTE This equipment has been tested and found to comp ly with the limits for a Class A dig ital device, pursuant to part 15 of the FCC rules. These limits are designed to prov ide reasonable protection against harm ful interference when the equipment is operated in a com mercial environm ent.
Lieber t MR 1 • 3 Section 2: INSTA LLA TION Mounting Th e MR1 Mini- R em ote is com p letely tested, then shipped from the factory disassem b led for your convenience during installation. T o beg i n flush- m ount installation, please refer to Fig u re 2A.
Figure 2a. Flush-Mount Installation 4 • User Manual DISCONTINUED P R O D U C T.
Electrical Connections Th e MR1 Mini- R em ote requires a two- wire connection (field- supplied) to com m unicate with the Env i ronm ental unit under its control. T h e stranded tw isted- pair connects to the MR1 interface board at T B 2- 11 (T+) and T B 2- 12 (T - ) .
Figure 2b. Display Panel Mounted Remotely from Electrical Box 6 • User Manual DISCONTINUED P R O D U C T.
Section 3: HA RDWA RE CONFIGURA TION DIP Switch Settings The following user selectable operations are set by DIP SW1 on the display panel circuit board: Refer to Table 2 and Figure 3. Position OFF ON 1 Audible beeper enabled Audible beeper disabled 2 Remote on/off disabled.
Figure 3. Electrical Connecti ons, Electric Box and Display 8 • User Manual DISCONTINUED P R O D U C T.
Lieber t MR 1 • 9 Section 4: OPERA TION LCD and Key pad When power is first applied, the MR1 perform s self- initializ ation and then enters the norm al display m ode. The display alternates between show ing the tem p erature and humidity readings, and cooling / heating , de/hum idification, and econocyc le operating status.
button will turn on/off the unit being m onitored and the MR1. With DIP switch # 2 in the OFF position, pressing the ON/OFF button will turn tog g l e the on/off operation of the MR1 only . Setpoint Control Th ere are two hidden buttons on the MR1 k eyp ad.
Setpoint AM/AG SM L10 L00 MM2 SSC On/Of f ✔ ** ✔ ** ✔ ✔ Temperature ✔ ✔ ✔ ✔ ✔ Temp Sensitiv ity ✔ ✔ ✔ ✔ ✔ Hum i dity ✔ ✔ ✔ ✔ ✔ Hum idity Sensitivity ✔ ✔ ✔ .
Alarm AM/AG SM L10 L00 MM2 SSC High Tem perature ✔ ✔ ✔ ✔ ✔ ✔ Low Temperature ✔ ✔ ✔ ✔ ✔ ✔ Hig h Hum idity ✔ ✔ ✔ ✔ ✔ ✔ Low Humidity ✔ ✔ ✔ ✔ ✔ ✔ High Head .
DISCONTINUED P R O D U C T.
Mini-Re m ote Envi ronmental Monitor ■ ■ ■ ■ ■ ■ ■ ■ MR1 T HE C OM PANY B EHI ND T HE P RODUCT S W i th more than 500,000 installations around the globe, Liebert is the w o rld leader in computer protection systems.
デバイスLiebert MR1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Liebert MR1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLiebert MR1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Liebert MR1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Liebert MR1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Liebert MR1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLiebert MR1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Liebert MR1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLiebert MR1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。