Precision Cooling For Business -Critic al C ontinuity™ Li eber t X DV ™ User Ma nual –50 & 6 0 Hz.
G ENERAL S AFETY G UIDELINES SAVE THESE INSTRUCTIONS Fluorinated Greenhouse Gas Requireme nt s—European Union Stationary air conditioning, refrigerat ion, heat pu mp equipments and stationa ry fire .
i T ABLE OF CONTENTS G ENERAL S AFETY G UIDEL INES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER 1.0 L IEBERT XDV C OMPONENT L OCATIONS AND M ODEL N UMBER N OMENCL ATURE . . . . . . . . . 1 2.0 I NST ALLATION .
ii 6.8 Connecting Liebert XD Fle x Pipe to Liebert X DV Modu les . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.9 Connecting a Liebert XDV with Li ebert Flex Pipe to an Operatio nal Liebert XD System . . . . . . . . . . . . . . . . . . . . .
iii FIGURES Figure 1 Liebert XD V component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Liebert XDV mo del number nomenclature . . . . . . . . . . . . . . . . . . . . . . .
iv.
Liebert XDV Component L ocations and Model Number Nomenclature 1 1.0 L IEBERT XDV C OMPONENT L OCATIONS AN D M ODEL N UMBER N OMENCLATURE Figure 1 Liebert XDV component locations Figure 2 Liebert XDV .
Installation 2 2.0 I NST ALLATION 2.1 References This document must be used together with site specific documenta tion and documentation fo r other parts of the system. 2.2 Pre-Inst allation Checks • Verify that the Liebert XDV vo ltage matches the av ailable utility power.
General produ ct information 3 3.0 G ENERAL PRODUCT INFORMATION 3.1 Product / System Description The Liebert XDV cooling system is designed to be a ttached to the top of a co mputer cabinet or rack containing heat dissipating equipment.
General produ ct information 4 3.3 Equipment Inspection Upon arrival of the unit, and before unpacking, veri fy that the labeled equi pment matches the bill of lading.
General produ ct information 5 3.3.2 Unit Handling If possible, tran sport the unit using a forklift or pallet jack. • If using a forklift or pallet ja ck, ensure that the fork tine length is suitable to safely move the packaged unit.
General produ ct information 6 Export Packaging 1. Unbend all metal tabs as indicated in Step 1 in Figure 6 . 2. Remove outer packaging when re ady to install the Liebert XDV. 3. Ke ep the Liebert XDV covered by th e unit bag until removal from pallet.
General produ ct information 7 Removing the Liebert XDV from the Pallet 1. Unfold the unit bag to expose the Liebert XDV. 2. Verify the nameplate information found on the Liebert XDV against the bi ll of lading. If the information does not matc h the product specifi ed, contact your local Liebert sales representative.
Mechanical Considerations 8 4.0 M ECHANICAL C ONSIDERATIONS 4.1 Determining Placement in the Conditioned Sp ace Liebert XDVs should be placed above or on top of the cabinets that generate the greatest amount of heat. If heat loads are dispersed ev enly throug hout the room, the Lieb ert XDV modules may be spread out accordingly.
Mechanical Considerations 9 4.2 Changing the Air Intake Location The Liebert XDV comes from the fact ory with the air intake on the re ar of the unit. If required for your application, this can be changed so th at th e Liebert XDV takes in heated air from the bottom.
Mounting the Liebert XDV 10 5.0 M OUNTING THE L IEBERT XDV The Liebert XDV module must be securely attached to the top of the computer cabinet or, alterna- tively, suspended above the cabinet.
Mounting the Liebert XDV 11 Figure 1 1 Mounting hole locat ions—st andard mounting me thod Figure 12 Mounting hole locations—alte rnate mounting point s Fan tray removed to show mounting location(s) of 1/4" - 20 bolts Bolt 1/4" - 20 (2 places, typ.
Mounting the Liebert XDV 12 5.1.2 Using Supplied Clip s for Mounting 1. Attach the mounting clips to the back of the Liebert X DV by fitting them into the machined slots.
Mounting the Liebert XDV 13 5.2 Suspended Mounting Method The Liebert XDV also may be mounted abo ve the cabi net by suspending it either from overhead com- ponents or from Unistruts above the cabinets (see Figures 15 and 16 ). An optional kit availa ble from Liebert will simplify mounting the Li ebert XDV above the computer cabinet.
Mounting the Liebert XDV 14 5.2.1 Suspending the Liebert XDV from Unistrut s The Liebert XDV may be bolted to customer-supplie d Unistruts. The hei ght of the Unistruts above the computer cabinet must be adeq uate to accommodate the combined height of the Liebert XDV and the baffle.
Mounting the Liebert XDV 15 Figure 16 Suspending Liebert XDV f rom the overhead structure 3/8 " -16 all-thread bolts, field-supplied, typical To prevent bypass air from recirculating through the Liebert XDV without it passing through the cabinet, this space between the hanging XDV and the cabinet must be blocked.
Mounting the Liebert XDV 16 5.3 Mounting Liebert XDVs in St acked Setup Liebert designe d the Liebert X DV to permit mounti ng t he units in a stacked ar rangement to increase the system’s heat-removal. Stackin g may be done eith er during the original system or added later to an existing configuration.
Mounting the Liebert XDV 17 5.3.1 Hanging S t acked Liebert XDVs from Unistrut s Because the upper Liebert XDV in a stacked arrang ement must be positioned farther forward than the lower Liebert XDV, two sets of Unistruts are required. The second set of Unis truts must be installed 9-7/8 in ches (251mm) forward of the first set.
Mounting the Liebert XDV 18 5.3.2 Hanging S t acked Liebert XDVs from the Overhead Structure Because the upper Liebert XDV in a stacked arrang ement must be positioned farther forward than the lower Liebert XDV, the place wh ere the hangers attach to the ov erhead structure must be offset accordingly.
Piping 19 6.0 P IPING 6.1 European Union Fluorinated Greenhouse Gas Requirement s Stationary air conditioning, refrigerat ion, heat pu mp equipments and stationa ry fire protection sys- tems in the Eu.
Piping 20 Figure 22 T ypical Liebert XDV pi ping—non- interlaced connection 6.2.1 Piping Connections to Liebert XDP or Lie bert XDC Refer to site specific drawings for general locati ons of the piping connect ions. For Liebert XDV con- nection locations, refer to Figures 1 and 24 .
Piping 21 Figure 23 Hard-piped connection diagram C opper Tubi ng To tal l en gth of each li ne f rom Liebe rt X D V to M ai n ; no t to exceed 72" ( 1829 m m ) Top of Lieber t XD V Re t u r n Ma in (seen fro m en d ) 2- 1/ 8" O . D . or 2- 5/ 8" O .
Piping 22 6.4 Hard Piped Connection Sizes Supply piping connection is 1/2" OD copper pipe and return pipi ng connection is 5/8" OD copper. 6.4.1 Holding Charge—Hard-Piped Unit s The Liebert XDV in hard-piped configuration is shipped with a low-pressure holding charge (about 30 psi) of nitrogen to prevent oxidation and moisture.
Piping 23 Figure 25 Schrader valve location for venting holding cha rge 6.4.2 Brazing Prep arations—Hard-Piped Unit s After the holding charge for a hard-piped Liebert XDV has been vented, a torch ca n be used to remove the caps over the ends of the supply and return li nes.
Piping 24 6.6 Connection Methods—O ne-Shot Connections The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigera tion systems. Observe all standard practices during installa tion and startup to prevent damage and contamination.
Piping 25 6.6.1 Refrigerant Charge—Pre-Charged Option Liebert XDVs with the pre-charged option are equipped with one-shot connections on the supply and return fittings. These contain a ch arge of R-134a refrigerant un der pressure within the unit. This charge must not be vented.
Piping 26 6.9 Connecting a Liebert XDV wi th Liebert Flex Pipe to an Operational Liebert XD System NOTICE Before connecting the Liebert XDV with Liebert Fl ex Pipe to the prefabri cated piping mains, check the whole sy stem for leaks. Check the Liebert XDV to ensure that the unit has no refrigerant leaks.
Piping 27 Figure 29 Deta il view of Liebert XD Fl ex Pipe and prefabricated pipin g port 8. Repeat Steps 6 and 7 for the smaller coupler (supply line). 9. Once the supply and return co nnections are completed, check to make sure the Lieb ert XDV fan power switches are Off, then connect the power cords to their power sources.
Piping 28 6.10 Disconnecting a Liebert XD V With Liebert Flex Pipe From a Liebert XD System NOTICE Before uninstalling a Liebert XDV with Liebert Flex Pipe fr om the pre fabricated piping mains: With the fans running, close the supply serv ice valve, wait approximately two minutes, then clos e the return service valve.
Piping 29 Figure 32 Piping mains without Li ebert XDV and Lie bert Flex Pipe 11. Repeat Steps 8 through 10 for the return coup ler (larger coupler). 12. Carefully l ay the Liebert Flex Pi pe o n the top of the Liebert XDV. NOTICE Risk of permanent damage to the flex pipes.
Electrical 30 7.0 E LECTRICAL The unit must be installed in accord ance with national wiri ng regulations. Refer to the unit’s serial tag for electrical requirements.
Electrical 31 Figure 34 Liebert XDV electrical connections for CE-approved unit s PRI MARY PO WER SO URCE SE CONDA RY 82 83 60 Hz MODE LS O NLY. FIE LD WIRING CO NNE CTIONS AT T E RM INAL S TRIP TO BE N.E .C. CLAS S 2 U SE SWI TC H CONT ACTS WITH 75 V.
Electrical 32 7.2 Connecting Low V oltage W iring—Optional Low voltage connections to the Liebert XD V are avail able only on units with the optional condensate detection feature. The low voltag e connections are on the right side o f the electrical connections box, just above the power connections (see Figure 35 ).
Installation Checklist and System F ill for S tartu p 33 8.0 I NST ALLATION C HECK LIST AND S YSTEM F ILL FOR S T ARTUP 8.1 Checklist for Proper Inst allatio n ___ 1. Li ebert XDV modu le is properly mounted , secu red either to the cabinet, overhead structure or to the Unistruts.
Operation 34 9.0 O PERATION The Liebert XDV’s fan controls are on the front of the unit, near the fa ns, for easy acce ss. Each switch controls the operation of one fan (see Figure 36 ). The separate sw itches permit the use of only one fan at a time, reducing the airflow if the Lieb ert XDV’s full cooling capacity is not needed.
Maintenance 35 10.0 M AINTENANCE Minimal maintenance is required to keep the Liebert XDV operatin g a t optimal levels. The unit should be cleaned and checked for damage an d worn parts.
Maintenance 36 10.2.1 Accessing Internal Electrical Component s 1. Disconnect all power inputs. 2. Remove five screws to remove th e front electrical panel cover.
Maintenance 37 To remove the fan tray: 1. Remove the fro nt electrical pane l cover as described in 10.2.1 - Accessing Internal Electrical Components . 2. Disconnect the 12-pin connector. Ta ke care not to stretch or stress the electrical wires to the fans.
Specifications 38 11 . 0 S PECIFICATIONS T able 5 Liebert XDV10 spec ifications Models XDV10BK--*; XDV10DK--* XDV10BKP-*; XDV10DKP-* XDV10BK-E*; XDV10DK-E* XDV10BKPE*; XDV10DKPE* XDV10BKR-*; XDV10BKR .
Specifications 39 T able 6 Liebert XDV8 specifications Models XDV8BK--*; XDV8DK--* XDV8BKP-*; XDV8DKP-* XDV8BK-E*; XDV8DK-E* XDV8BKPE*; XDV8DKPE* XDV8BKR-*; XDV8BKRE* XDV8DKR-*; XDV8DKRE* XDV8BT--*; X.
Specifications 40 T able 7 Liebert XD Liebe rt Flex Pipe assemblie s, supply and ret urn Description Liebert P/N Straight Connection Assembly Liebert P/N 90-Degree Connection Assembly Length ft (m) Minimum Bend Radius inches (mm) Supply Return Liebert XD Flex Pipe Kit 186568G1 186567G1 6 (1.
.
Ensuring The Hi gh A vai labilit y Of Mission-Critic al Data And Ap plic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures network resiliency and a.
デバイスLiebert XDVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Liebert XDVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLiebert XDVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Liebert XDVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Liebert XDVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Liebert XDVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLiebert XDVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Liebert XDVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLiebert XDVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。