Aprilaireメーカー1770Aの使用説明書/サービス説明書
ページ先へ移動 of 20
Model 175 0A / 1 7 7 0A Dehumidifier Installation Instructions READ AND SA VE THESE INSTRUCTIONS CAUTION 1. Read all instructions before beginning installation. 2. Do not use in pool applications. Pool chemicals can damage the dehumidifier . 3. Do not use solvents or cleaners on or near the circuit board.
OVERVIEW The Aprilaire ® Dehumidifier is designed to control humidity inside the whole home. The dehumidifier uses a dew point calculation to control the humid ity based on the drynes s set point on the dehumidi fier contr ol. An opti onal Model 70 Living Space Contro l or third- party control can be used in place of the onboar d control.
SPECIFICA TIONS Dimensions: 20-3/4”W x 24”L x 20-5/8”H Adjustable feet allow for 22-5/8” total height W eight: 1750A – 93 lbs. 1770A – 100 lbs.
FIGURE 2 – Dimensions and Location Considerations 20-3/4 (527) 24.00 (610) 9-1/2 (241) 10-3/8 (264) 1-1/4 (32) 6-1/2 (165) OFF ON Air Outlet 8 in. Round Collar OFF/ON Switch Drain 2-1/2 (64) 3-7/8 (98) Damper Fully Open Filter Access (Front and Back) Power Cord Air Flow 2-1/2 (64) 20-3/4 (527) 11 (279) 9 (229) 19-5/8 (498) 3 (76) Max.
FIGURE 3 – Install Damper in Collar 90-1503 FIGURE 4 – Install Collar with Damper on Outlet 90-1503 FIGURE 5 – Minimum Ductwork Bend Distance 90-1503 DUCT COLLARS & BACKFLOW DAMPER The backfl ow damper installs on the outlet side of the dehumidifi er , using featur es molded into the duct collar .
FIGURE 6 – Drain Trap 90-961 MECHANICAL INST ALLA TION (CONTINUED) DRAIN 1. Adjust feet of dehumi difie r to allow a 2-1/2” minimum clearance for drain trap. See Figure 6 . Use the 90° elbow if necessa ry for clearance restrictions. See Figure 7 .
WHOLE-HOME INST ALLA TION (CONTINUED) FIGURE 9 – Whole-Home Basement Installation CONDENSA TE HOSE (TO COMMON DRAIN OR OUTSIDE) AIR IS PULLED FROM RETURN DUCT DEHUMIDIFIED AIR IS SUPPLIED DOWNSTREAM.
WHOLE-HOME INST ALLA TION (CONTINUED) • HV ACFAN ON:Activatin gtheHV AC fan during dehumidi ficat ionis recomm ended because it offers bett er circul ation and balancing of indoor air conditions. Running the HV AC fan during dehumidification does not affect moisture removal efficiency .
SPOT INST ALLA TION (CONTINUED) FIGURE 14 – Spot Ducted Installation OUTSIDE AIR TO HOUSE LIVING SP ACE SUPPL Y DUCT RETURN DUCT FLOOR DRAIN DEHUMIDIFIER 115 VA C CIRCUIT EQUIPMENT ROOM CONDENS AT E.
CONVERTIBLE INST ALLA TION In this installation the dehumidifier controls humidity in both the whole- home and a spot locatio n. The dehu midif ier will dehumidify the whole home as the first priority , switching to the spot location after the whole-home dehumidification need has been met.
CONVERTIBLE INST ALLA TION (CONTINUED) • HV ACFAN ON:Activatin gtheHV AC fan during Whole-Ho medehumid ifica tion is recomme nded beca use it offers bette r circu latio n and balancin g of indoor air condit ions.
VENTILA TION OR AIR CYCLING The dehumi difie r has outputs avai lable to open a norm ally clos ed damper and introd uce out door air thoug h an outdoo r air intake duct. V entilat ion is cont rolle d by the Cycle Period switches, Cycle T ime potentiometer , and V ent-Auto/Vent-T imed switches.
VENTILA TION OR AIR CYCLING (CONTINUED) DETERMINE FRESH AIR DELIVERY RATE 1. Measure the negative static pressure of the return system at the location where the outdoor air duct enters the return duct. 2. See T able 4 for estimated inlet airflow in CFM, based on duct type, length, and available negative pressure.
VENTILA TION OR AIR CYCLING (CONTINUED) Switch Notes: • Setting theCycle T ime ≥ Cycle Period will result in constant ventilation. • Setting theCycle T imeto OFF willdisable ventilation. 1. Set VENT -AUTO and VENT -TI MED switch .
VENTILA TION OR AIR CYCLING (CONTINUED) SEQUENCE OF OPERATION VENT-TIMED, HVAC INITIATES VENTILATION • V entilat ionwilloccur whenev erthereisanHV ACfan (Gs )or.
MODEL 70 LIVING SP ACE CONTROL WIRING & DIP SWITCH CONFIGURATION TheModel 70 LivingSpace Controlcontains itsown sensorsthat override themain controlsensors onthe dehumidifier .
THIRD-P ARTY CONTROL WIRING & DIP SWITCH CONFIGURATION An externa l thermos tat with dehum idifi er connect ions can be used as an ON/ OFF dehumi difier control. In this configura tion, the third-par ty control initiates dehumidification and overrides the on-board dehumidifier control logic.
SYSTEM CHECKOUT DEHUMIDIFICATION 1. Check the wiring to the HVAC equipment and any accessories if applicable. 2. Plug unit in and turn on/off switch to ON. 3. Rotate the main control knob clockwise to the TEST position. 4. If set up cor rectl y , the dehumidi fier blow er will turn on and the dehumidi fier damp er output will turn on.
TROUBLESHOOTING T ABLE 7 – Green LED Codes Activity Status Solid ON Compressor ON Blinking 1 sec. ON & 1 sec. OFF Sampling Blinking 1/2 sec. ON & 1/2 sec. OFF Defrosting Alternating Green & Red T est Mode T echnical Support is available Monday through Friday , 7:00 a.
T ABLE 9 – T roubleshooting Guide Symptom Possible Reason T roubleshooting Procedure Dehumi difier does not turn on/run. No power to unit. • Check thatthe dehumidifieris pluggedin. • Check thatthe powerswitch onthe dehumidifieris ON.
デバイスAprilaire 1770Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Aprilaire 1770Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAprilaire 1770Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Aprilaire 1770Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Aprilaire 1770Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Aprilaire 1770Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAprilaire 1770Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Aprilaire 1770Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAprilaire 1770Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。