Model 8100 Energy Recovery V entilator Installation Instructions READ AND SA VE THESE INSTRUCTIONS CAUTION 1. Read all instructions before beginning installation.
SPECIFICA TIONS Dimensions Unit – 37-7/16” W x 12-3/4” D x 20-9/16” H EnergyMax T ransfer Core – 12-1/8” x 12-1/8” x 10-3/4” Weight 75 lbs. Performance 77% Apparent Sensible Effectiveness (ASE) At rated ventilation capacity with 72°F indoor temperature and 32°F outdoor temperature.
SERVICE CLEARANCE 12" 12" 36" 37-7/16" 20-9/16" CEILING MOUNTING HOLES CEILING MOUNTING HOLES ON / OFF SWITCH W ALL MOUNTING HOLES W ALL MOUNTING HOLES RETURN ST ALE AIR SUPP .
The unit can be mounted on a concrete wall or on a stud wall. The mounting bracket is pre-drilled for fastening to standard 16” O.C. or 24” O.C. stud spacing. Remove the access panel, EnergyMax T ransfer Core, and air filters for installation. 1. Remove the access panel, EnergyMax T ransfer Core and filters.
MECHANICAL INST ALLA TION (CONTINUED) CEILING MOUNT The unit can be mounted on ceiling joists. The mounting bracket is pre-drilled for fastening to standard 16” O.C. or 24” O.C. ceiling joists. Remove the access panel, EnergyMax T ransfer Core, and air filters for installation.
MECHANICAL INST ALLA TION (CONTINUED) DUCTING DUCT WORK SPECIFICATIONS • Plan ontemporarily installing two airflow measuring devices. The systemwill have to be balanced( BALANCING THE SYSTEM SECTION ), after all duct work has been installed.
MECHANICAL INST ALLA TION (CONTINUED) DUCTING (CONTINUED) RETURN: FROM LIVING SPACE TO ERV • Stale airfrom the house should beexhausted from one exhaustgrille centrally located, such asa hallway .
MECHANICAL INST ALLA TION (CONTINUED) BALANCING THE SYSTEM DUCTING (CONTINUED) EQUIPMENT REQUIRED • The intakeand exhaust hoods must belocated at least 10ft. apart to avoid cross contamination. (See Figure 18 .
5 FT . MIN. 5 FT . MIN. 2-1/2 FT 2-1/2 FT PRESSURE GAUGES ST ALE AIR FROM HOUSE FRESH AIR FROM OUTSIDE FRESH AIR TO HOUSE ST ALE AIR TO OUTSIDE AIR FLOW MEASURING DEVICE #5158 AIR FLOW MEASURING DEVICE #5158 DAMPER DAMPER FIGURE 19 – Set-up for Balancing Airflow 90-1746 BALANCING THE SYSTEM (CONTINUED) BALANCING AIRFLOW 1.
SYSTEM ST ART -UP CONSTANT ON OPERATION OPERATION WITH HOME COMFORT CONTROL ™ (FIGURE 20) OPERATION WITH 8120 VENTILATION CONTROLLER OR THIRD-PARTY CONTROL (FIGURE 20) The Energy Recovery V entilator has an on/off switch which enables the unit to be constantly on.
SYSTEM ST ART -UP (CONTINUED) T able 2 – V entilation Air Requirements, CFM Home Size (ft 2 ) Number of Bedrooms < 2 2 - 3 4 - 5 6 - 7 > 7 ≤ 1500 30 45 60 75 90 1501 – 3000 45 60 75 90 105.
P.O.Box1467•Madison,WI53701-1467•Phone:800/334-6011 •Fax:608/257-4357• www.aprilairepartners.com 10009736 1.12 B2701202A Printed in U.S.A. © 2012 Aprilaire – A division of Research Products Corporation TROUBLESHOOTING T echnical Support is available Monday through Friday , 7:00 a.
デバイスAprilaire 8100の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Aprilaire 8100をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAprilaire 8100の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Aprilaire 8100の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Aprilaire 8100で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Aprilaire 8100を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAprilaire 8100の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Aprilaire 8100に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAprilaire 8100デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。