Made in USA Made in USA Slim Line Rack UPS User’ s Manual Models 3 & 4 www .mgeups.com.
For service call: 1-800-438-7373 MGE UPS SYSTEMS 1660 Scenic A ven ue Costa Mesa, CA 92626 (714) 557-1636 www .mgeups .com Revision History Esprit Rack UPS User's Manual 86-153301-03 Copyright © 2000 MGE UPS Systems All rights reser ved.
Important Safety Instructions. Save These Instructions. This manual contains impor tant saf ety instructions for the Esprit Models 3 and 4 that should be f ollowed during installation and maintenance of the UPS and Batteries. Caution: Risk of electric shock, even with the unit disconnected fr om the A C po wer source.
ii Caution: Do not dispose of batteries in a fire. The batteries may e xplode. Do not open or mutilate the batteries. Released electrol yte is harmful to the skin and ey es. It may be to xic. A battery can present a risk of electric shock and high short circuit current.
iii Contents Quick Start ..........................................................inser t Important Safety Instructions ....................................i 1. Introduction ........................................................1—1 MGE UPS Systems .
iv 6. Ad vanced Configuration ..................................6—1 6A. Entering/Exiting Configuration Mode ....................................................6—1 6B Using Configuration Mode .......................................................
1—1 Thank you f or your purchase of the Esprit rack "UPS" from MGE. The Espr it "UPS" will provide many y ears of, trouble-free po wer protection for critical high av ailability ser vers and other de vices. Please read this manual fully , to familiarize yourself with the saf ety instructions and Espr it features .
1—2.
2. Getting to Know Your Esprit Rack UPS 2A. Pr oduct Featur es & Benefits Features Benefits Comments ◗ Plug in operation Low installation cost ◗ Modular concept Greater fle xibility Add batter.
2—2 2C. Esprit Rack UPS Pr oduct V iews With Rack Kit Figure 2a. Rear View of Models 3 and 4 With Rack Kit and Extended Batteries Model 3 Model 4 Figure 2b.
3A. Storing the UPS and Rechar ging the Battery Alwa ys store the equipment in its or iginal packaging. The batter y is of the sealed lead-acid type. Batter y recharge requires that the batter y module be plugged into an energized NEMA 5-15 receptacle f or 6-8 hours.
3E. Connecting the Optional Extended Battery Plug the DC batter y cable into the UPS module as sho wn in Figure 2a . The cable plug is keyed , so make sure to align the plug properly to the receptacle. Do not force the cab le on, nor attempt to re verse the connection.
The transistor resistance is 27 ohms and the maximum current allo wed is 140mA AC or DC with ambient temperature of up to 40°C . In order to get a "logic low" y ou have to limit the current to: logic low voltage required divided by 27, logic lo w voltage = 0.
3—4 Caution: Connect only computer -type loads to the Esprit UPS. W arranty is void if non- computer-type loads are connected to the UPS. 3J. Solution-Pac Softwar e Solution P ac software allows y ou to interf ace your computer with the UPS .
4. Startup and Shutdown 4A. UPS Startup Y ou are ready to star t the equipment after installing the UPS module , optional batter y module(s), any options , and the communication cab le (if used). F ollow these simple steps: 1. Connect your computer equipment.
4—2 If desired, the UPS can be set up to operate at a known, fix ed frequency regardless of the detected utility frequency . Fixed-frequency operation is often desir able in installations that make use of cold-start capability . Discussion on this is in the Advanced Configuration Section (section 6) of this manual.
4—3 Off Flashing On 1. F ault The UPS is operating The UPS has detected a The UPS has detected an Detected normally . No faults ne w operating fault. The operating fault that has been (yello w) hav e been detected. F A UL T indicator will continue ackno wledged by the user .
4—4 The "F ault Detected" LED tur ns on and acts as described above f or ANY system alar m, including those that hav e their own status indicators (e.
4—5 Although six button states are detectab le, not ev er y button combination has an assigned task. button states/combinations that hav e no assigned task will simply be ignored. The “Utility P ower Present” does NOT reflect the state of the UPS output.
4—6.
5. Performance & Product Specifications 5—1 T able 5a. Esprit Models 3 and 4 Rack UPS Specifications Item Specification Comment Output V A 2880/4000 Output W 2016/3150 Surge protection, joule ra.
T able 5a. Esprit Models 3 and 4 Rack UPS Specifications (Continued) Item Specification Comment Design standards Safety; UL, cUL 1778, Emissions; FCC A, Surge protection; ANSI C62.41, T ranspor tation; (drop test), IEC 68 le vel 1, (vibr ation), IEC 68.
6. Advanced Configuration 890-=qwertyuio Esprit Front Panel Configuration Mode Usage and Instructions For advanced users only! The Esprit UPS is shipped from the factory with a configuration that is suitable f or most applications . Howe ver , there are some circumstances where modification of the UPS operating parameters is required.
6—2 It is possible to cycle bac kward through the configuration options by pressing and holding the top button. A given option setting can be f orced to its f actor y def ault state by pressing and holding the bottom button. The middle (P ower ON) b utton is not used in configuration mode.
6—3 Options 0, 1, 2 – Extended Batter y Configuration These three option s witches should be changed as shown in the tab le below when new battery cabinet(s) are added to the UPS. The standard setting for these options are all OFF , selecting the single/internal batter y module option.
6—4 Options 5, 6 – Input V oltage T olerance Use these two option s witches to select the Esprit’ s sensitivity to low/high input v oltage conditions. The Esprit will switch to battery power when the utility v oltage falls outside the range selected.
6—5 Option 10 – A utomatic UPS restar t after Low Battery shutdown The f actor y setting f or this option is ON, which allows the UPS to automatically turn its output back on f ollowing a Low Battery shutdown once input A C is present.
6—6 Option 15 – P ower -On In ver ter T est (POIT) When this option is set to the f actor y def ault ON setting, the Esprit will perform a shor t batter y/in verter test shor tly after it is tur ned on. This test is only perf ormed only if the UPS is able to po wer up the load from utility power first.
7—1 7. Service & Maintenance 7A. Maintenance Clean the UPS with a dr y cloth after turning off all power to the UPS and s witching off the power s witch. The UPS perf orms monthly automatic batter y tests. Howe ver , it is recommended that a 6 month test be perf ormed on the UPS for battery condition.
7—2 7B. Recycling Y our UPS In USA or Canada, call 1-714-557-1636, M - F , 6:00 A.M. to 5:00 P .M. PST . Ask for a return goods authorization for free UPS or battery recycling. MGE does not cov er return freight charges f or recycling and will not accept items without a return goods authorization number .
8—1 8. T roubleshooting Pr oblem Possible cause Requir ed User Action ◗ UPS does not turn on. ◗ UPS is not plugged in. ◗ Plug UPS into a working outlet. ◗ W all socket is dead. ◗ T est wall sock et, repair as required. ◗ UPS has not been activated.
Notes 8—2.
Other Fine MGE Pr oducts Eclipse Surge Suppr essors Ellipse 300-1200 V A ESV+ UPS ESV+ Rack UPS 780-2200 V A 780-2200 V A EX UPS EX Rack UPS 700-3000 V A 700-3000 V A Call MGE for man y more power sol.
MGE UPS SYSTEMS USA (headquarters) 1660 Scenic Avenue Costa Mesa, CA 92626 tel: (800) 523-0142 (714) 557-1636 fax: (714) 557-9788 www .mgeups.com.
デバイスMGE UPS Systems 4の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
MGE UPS Systems 4をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMGE UPS Systems 4の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。MGE UPS Systems 4の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。MGE UPS Systems 4で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
MGE UPS Systems 4を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMGE UPS Systems 4の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、MGE UPS Systems 4に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMGE UPS Systems 4デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。