MGE TM Gala xy TM 6000: Specification guide ______ _________ _________ _________ _ Parallel UPS, 250 to 3000 kVA* * Power rating for an N+1 configuration.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 2 Contents 1 - UPS definition ............... ... ... .... .
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 4 2 - Operating principle The double-co nversion UPS ( also called on-l ine) shall ope rate as defined below.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 5 2.6 - UPS maintenance For main tenance purpo ses, all elect r onic components shall be accessib le from the front of the UPS.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 7 specified by the battery supplier (0.1 x C10 for a sealed l ead-acid battery).
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 10 7 - Environm ent conditions 7.1 - UPS (not including battery ) 7.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 11 9 - Battery management As the life of the batteries is very sensit ive to operat ing conditi ons, the bat tery shall be managed in an optimum manner.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 13 10.1.3 - Status indications wi th mimic panel Indication o f status conditio ns shall be dis tinct of the grap hic display.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 15 14 - Services 14.1 - Maintenance The suppli er shall propose cont racts covering four levels o f maintenance.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 16 17 - Electrical diagram Batter y Normal A C input UPS 1 B ypass AC i npu t Load Battery Normal A C input UPS 2 P < P 1 P1 (k V A ) P1 (k V A ) Fig.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 17 Load Bypass AC input Normal AC input Normal AC input Normal AC input Centralized bypass Fig.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 18 Appendix. Comparison table Type of UPS Total rate d pow er (kVA) at PF 0.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec.
デバイスMGE UPS Systems 6000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
MGE UPS Systems 6000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMGE UPS Systems 6000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。MGE UPS Systems 6000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。MGE UPS Systems 6000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
MGE UPS Systems 6000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMGE UPS Systems 6000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、MGE UPS Systems 6000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMGE UPS Systems 6000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。