USER'S GUIDE JY992D53201C This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX and FX 0N , 485 communication adapters. It should be read and understood before attempt- ing to install or use these units.
1 INTRODUCTION ①⑥ LINK SG SDB SDA RDB RDA FG 24+ 24G 〈 FX-485ADP 〉 MITSUBISHI FX-485ADP ① Direct mounting hole ② Power LED · · · ③ R D L E D ······· ④ S D L E D ······· ⑤ Terminal screws (M3 (0.12)) ⑥ Extension cable ⑦ Terminal cover ⑧ Groove for mounting DIN rail (DIN rail width : 35 (1.
Station No.15 ↑ FX series PC Max. 16 stations including A series PCs (total extension distance 500m) (2) Computer and PC by 1 : n configuration In this case, the number of link stations is 16 PCs at maximum for one computer, including the FX series PCs and A series PCs.
For setting up the system, the 485ADP can be connected to the following PCs. PC series FX 0N FX , FX 2C PC version Ver. 1.20 or later Ver. 3.30 or later Remarks Exclusive protocol format 1 and format 4 are supported. Exclusive protocol format 1 and format 4 are supported.
*1 R is the terminating resistance. Connect the terminating resistance (330 Ω ) between terminals SDA and SDB , and terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less.
*1 R is the terminating resistance. Connect the terminating resistance (110 Ω ) between terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less. However, as for the computer link unit of the A series PC, see the manual of the computer link unit.
Classification of terminating resistances In this product, two sets of terminal end resistances (330 Ω ✕ 2, 110 Ω ✕ 1) are packaged, and the terminating resistances to be connected differ as shown below depending on the circuit being used.
FX 0N FX, FX 2C The communication format of the PC is set using special D8120. Operating ambient temperature Humidity no condensation Shock resistance Noise immunity Dielectric withstand voltage Insul.
X0000 ~ X0177 Y0000 ~ Y0177 M0000 ~ M0511 S0000 ~ S0127 M0000 ~ M8254 TS000 ~ TS063 CS000 ~ CS031 CS235 ~ CS254 TN000 ~ TN063 CN000 ~ CN031 CN235 ~ CN254 D0000 ~ D0255 D1000 ~ D2499 D8000 ~ D8255 ( ) .
In case of trouble, check the following points, and remedy according to the troubleshooting guide in the 485PC- IF manual. (1) Power LED Lit Otherwise (2) As for SD LED, RD LED, check and remedy according to the troubleshooting guide in the 485PC-IF manual.
Prior to start of operation, follow the procedure below. As for detail of procedure, see the 485PC-IF manual. 6 Determine system configuration Setting of transfer specification (D8120) Setting of stat.
Guidelines for the safety of the user and protection of the FX-485ADP, FX 0N -485ADP communication adapter JY992D53201C Effective AUG. 1997 Specifications are subject to change without notice.
デバイスMitsubishi Electronics FX-485ADPの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics FX-485ADPをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics FX-485ADPの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics FX-485ADPの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics FX-485ADPで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics FX-485ADPを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics FX-485ADPの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics FX-485ADPに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics FX-485ADPデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。