ERV -1 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard LGH-F-RX 3 -E 1. COMP ARISON OF PRIMARY BUILDING VENTILA TION METHODS .................................................................... ERV -2 2 . LOSSNA Y ® PRINCIPLES.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -2 There are two main ventilation methods: Centralized V entilation Method This is mainly used in large buildings, with the outside air intake being installed in one machine room.
ERV -3 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 2.3. Calculation of T otal Energy Recovery Efficiency The Lossnay ® Core’s energy recovery efciency can be considered using the following three transfer rates: 1.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -4 2.5. Lossnay ® Operation / V entilation Modes Supply side Exhaust side T emperature t SA = t OA - (t OA - t RA ).
ERV -5 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 2.6. Automatic Ventilation Switching - Bypass Damper Operation Effect of Automatic Ventilation Mode The automatic damper mode automatically provides the correct ventilation for the conditions in the room.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -6 2.72. Calculation T able for Dust Collection Efficiency of each Lossnay ® Filter 2.7.3. Pr essure Loss MERV Rating Dust Size (µm)* 6.6-8.6 6; 3.0-10.0 µm less than 49.
ERV -7 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Outdoor Air (OA) Air drawn from outdoors - ventilation air . Pulse Input When the control signal from an external device outputs a pulse such as the one shown at right, the pulse input control is performed by the Lossnay ® unit.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -8 3. LOSSNA Y ® MODELS AND SPECIFICA TIONS Model specifications and materials list for Lossnay ® units Model LGH.
ERV -9 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F300RX3-E Characteristic Curve * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -10 Model LGH-F470RX3-E Dimensions Ceiling suspension Nominal Duct connecting Duct pitch Unit fixture pitch diameter.
ERV -1 1 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F4 70RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -12 Model LGH-F600RX 3 -E Model LGH-F600RX3-E Model LGH-F600RX3-E Specifications Ta ble Dimensions Ceiling suspensio.
ERV -13 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F600RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -14 Model LGH-F1200RX 3 -E Model LGH-F1200RX3-E Model LGH-F1200RX3-E Specifications Ta ble --T wo addresses re quir ed .
ERV -15 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F1200RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -16 E P L N A m 0 0 1 V 5 C D A 2 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 2 V 0 4 2 C A N. I M X. A M t u p t u o r o t i n o m n o i t a r e p O A m 0 0 1 V 5 C D A 1 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 1 V 0 4 2 C A N.
ERV -17 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard LGH-F1200RX3-E • Dotted lines represent eld-supplied wire. • Be sure to connect the ground wire. • Breaker should be provided by the customer .
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -18 The human ear senses differently according to frequency . However , sound generated from a vibration is not limited to one frequency but in - stead various frequencies are generated at different levels.
ERV -19 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 5.2. LGH-F-RX3-E NC Curves LGH-F300RX 3 LGH-F470RX 3 LGH-F600RX 3 : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation 5 ft .
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -20 7. INST ALLA TION 7.1. Installation Diagrams LGH-F300 · F470 · F600RX types LGH-F1200RX type Note: The double control board for the LGH-F1200RX has two M-NE T addresses.
ERV -21 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 7.2. Alternate Installation for Lossnay T op/bottom reverse installation V ertical installation patterns Precautions Slanted installation Special Note ® ® All LGH-RX models can be installed in top/bottom reverse.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -22 7.3. Selecting Duct Attachment Direction Installation and maintenance Installation applications ® ®® ® ® ® Ø condensation. Choose between two directions for the outside duct (OA, EA) piping direction for optimum installation.
ERV -23 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 8. ELECTRICAL INST ALLA TION Names of components in control box Ground Bushing Ground Bushing Bushing With this product, the wiring installation method will vary according to the design of the system.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -24 Use Lossnay ® M-NET remote controller PZ-52SF-E. (Do not use PZ-41SLB-E).
ERV -25 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Use Lossnay ® M-NET remote controller PZ-52SF-E. (Do not use PZ-41SLB-E).
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -26 System Selection ERV -22 LGH-F-RX3-E Lossnay operation when indoor unit is stopped Available Not available Lossn.
ERV -27 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Centralized Control System with CITY MUL TI ® Indoor unit Lossnay Indoor unit Outdoor unit A-control Mr. Slim P-Series outdoor unit Mr. Slim A-control PAR- 21 MAA remote controller A-control Mr.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -28 Remote controllers for CITY MULTI ® indoor unit Remote controllers for . Slim ® indoor unit Remote controllers for Lossnay ® unit ® ® ® ® ® ® PA R-21MAA ON/OFF FILTER CHECK OPERA TION CLEAR TEST TEMP .
ERV -29 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Combination with CITY MULTI ® --Independent Lossnay ® System with Lossnay ® AG-150A Centralized c.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -30 Item Details Centralized contr oller MA r emote contr oller ME remote contr oller Lossnay ® M- NET r emote cont.
ERV -31 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard CITY MULTI ® and Lossnay ® Interlocked System ® ® ® ®® ® ® ® ® ® ® ® ® ® ® Lossnay® remote controller PZ-41SLB-E cannot be used with any group on the M-NET .
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -32 Item Details MA re mote controller ME re mote controller Lossnay M-NET re mote controller O Local Remote Model O 8 8 x 7 min.
ERV -33 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard MA Remote Contr oller/ME Remote Contr oller in Combination with Lossnay M-NET Remote Contr oller Ind.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -34 A mixed system including the CITY MUL TI can also be configured.
ERV -35 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard O Contents Individual Lossnay (Lossnay not set for interlocked operation) Interlocked Lossnay (Lossn.
LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -36.
デバイスMitsubishi Electronics LGH-F-RX3-Eの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics LGH-F-RX3-Eをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics LGH-F-RX3-Eの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics LGH-F-RX3-Eの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics LGH-F-RX3-Eで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics LGH-F-RX3-Eを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics LGH-F-RX3-Eの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics LGH-F-RX3-Eに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics LGH-F-RX3-Eデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。