L N + - U SA MADE IN U ser ’ s Guide www.omega.com e-mail: info@omega.com ® ® Shop on line at iDRN-PS-1000 UNIVERSAL SWIT CHING PO WER SUPPL Y Compact DIN-Rail 24 V olt.
Servicing North America: USA: One Omega Drive, P.O. Box 4047 ISO 9001 Certified Stamford, CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.
1. General Information and Features 2 2. Safety Considerations 3 3. Installation and Removal 4 3.1 Installation Clearance 5 3.2 Mounting on DIN Rail 6 3.3 Removal of Unit 7 4. Input and Output Connections 8 4.1 Block Diagram 8 4.2 Wiring for 115 Vac - Single Phase 9 4.
The compact iDRN power supplies are designed to supply well-regulated 24 volt DC power to sensors, signal conditioners, data acquisition systems and high level logic equipment.
S AFETY C ONSIDERA TIONS 2 3 This device is marked with the international Caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).
If a rail assembly is to be transported, then disconnection, dismounting and separate packing of the power supply is recommended. For units that must be shipped installed on the rail, additional bracing to resist transportation shocks is recommended. Do not attempt to install or connect to the power supply when the mains are energized.
3.1 Installation Clearance Ensure that there is enough room for mounting the power supply unit. There should be a minimum of 1" [25mm] spacing to allow sufficient air circulation for proper cooling.
3.2 Mounting on DIN Rail To install unit onto DIN Rail 1. Tilt unit, position mounting slot onto DIN Rail, as shown. 2. Push unit towards DIN Rail and it will snap into place.
3 7 3.3 Removal of Unit 1. Insert flat screw-driver into tab and push downwards. 2. Unit will detach from DIN Rail. Figure 3.3 — Removal of Unit I NST ALLA TION AND R EMOV AL.
4 8 4.1 Block Diagram of Power Supply Figure 4.1 — Block Diagram 4.2 Wiring Warning: Do not turn on the ac power to the power supply unit until you have completed all output connections. Failure to do so may result in injury! This device must only be installed electrically by a specially trained electrician with corresponding qualifications.
4 9 I NPUT AND O UTPUT C ONNECTIONS 4.2 Wiring (Continued) 115Vac - Single phase power wiring Figure 4.2— Wiring for 115Vac - Single Phase L N + - Output V oltage (for shielded wire connections, if .
4.3 Wiring (Continued) 230Vac - Two phase power wiring Figure 4.3— Wiring for 230Vac - Two Phase I NPUT AND O UTPUT C ONNECTIONS 4 10 L N + - Output V oltage (for shielded wire connections, if neces.
S PECIFICA TIONS 5 11 INPUT POWER Input Voltage: 115 - 240Vac ±10% Frequency: 50/60 Hz Current: 0.400A @ 103Vac 0.190A @ 265Vac Overvoltage Protection: 275 Volt Varistor Overcurrent Protection: Fuse .
S PECIFICA TIONS 5 12 GENERAL Operating Temperature: 23° to 122°F(-5° to 50°C) Storage Temperature: -40° to 176°F(-40° to 80°C) Mounting: 35mm DIN Rail Size: Height: 3.55" (90mm) Width: 0.99" (25mm) Depth: 4.38" (111mm) Weight: 0.
D IMENSIONS 6 13.
I NPUT AC VOL T AGE / POWER OUTPUT 7 14 Example: If ambient is 50ºC, maximum wattage is 21W max. for 120-265Vac. If unit is operated at 21W at an input voltage of 100V, the maximum ambient temperature allowed is 40ºC.
NOTES 15.
NOTES 16.
WARRANTY / DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OME GA W arranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.
M2540/0202 W her e Do I Find Ev er ything I Need for Pr ocess Measur ement and Contr ol? OM EGA…Of Cour se! Shop on line at www.omega.com TEMPERATURE Thermocouple, RTD & Thermistor Probe.
デバイスOmega Engineering iDRN-PS-1000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Omega Engineering iDRN-PS-1000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはOmega Engineering iDRN-PS-1000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Omega Engineering iDRN-PS-1000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Omega Engineering iDRN-PS-1000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Omega Engineering iDRN-PS-1000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はOmega Engineering iDRN-PS-1000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Omega Engineering iDRN-PS-1000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちOmega Engineering iDRN-PS-1000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。