Instruction Manual Athena 6050 Temperature Controllers -THENIL.
INSTRUCTION MANUAL SPECIFICATIONS: Inputs: Line Voltage Sensor Power Consumption Ranges Available Accuracy: Temperature Stability Cold end tracking Operating ambient for rated accuracy Maximum T/C lea.
Display update rate: 5 times per second Filtering: Analog and digital filtering techniques increase stability of process and display. °F/°C: output: -B Relay (time proportioning) -F Current proporti.
3.
FRONT PANEL AOJUSTMENTS Touch Key 1 Index: Allows the following adjustments to be selected. 1) Set point temperature O-14OO'F (760°C) O-2500°F (O-137O°C) 2) Heat cycle time 3) Prop.
3. 4. Loss of power or turn-off during warm-up requires a re-start from ambient. Change of state processes, i.e. solid to liquid or liquid to gas, may introduce erroneous tuning parameters during process warm-up. 1. Accurately measures, linearizes and displays temperature in °F and °C.
.
Output Modules The Athena 6050 offers users field interchangeable output modules. This unique feature makes it possible to fill output requirements for a variety of applications with a single controller model. Module Type B: This 7A/5A relay (at 120/240 Vac) is used for driving resistive heaters.
INTERNAL SWITCHES Damping Control -To allow the controller to provide automatic tuning for processes with varying heating characteristics and with varying heating capabilities, the 6050 offers three d.
THERMOCOUPLE PLACEMENT Proper thermocouple placement can eliminate many problems in the system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed close to the heater.
OPERATING INSTRUCTIONS How to Start the automatic tuning procedure STEP 1: Energize the unit and proceed immediately to step 2. STEP 2: Place the unit on standby by holding the "Index" button until the "Autotune" LED lights then press the Cancel button.
How to override automatic tuning parameters It is possible to set or fine tune three mode parameters manually on the 6050. To manually enter parameters: 1) Press "Index" button until the LED for the desired parameter lights. 2) Enter the new parameter using the up or down key.
TROUBLE SHOOTING Front dark - no instrument power. Process display shows CCCC - Open thermcouple. Short terminals 1 and 2. Process display should indicate temperature at back of case. Repair or replace thermocouple. About Half or Twice Expected Reading - Check position of °C/°F switch.
WARRANTY This equipment is warranted to be free from defects of material and workmanship. It is sold subject to our mutual agreement that the liability of Athena Controls, Inc. is to replace and/or repair at its factory, provided the equipment is returned, transportation prepaid within (2) years of its purchase.
dTHENd Controls, Inc., 5145 Campus Drive Plymouth Meeting, PA 19462 (215) 828-2490.
デバイスAthena Technologies 6050の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Athena Technologies 6050をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAthena Technologies 6050の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Athena Technologies 6050の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Athena Technologies 6050で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Athena Technologies 6050を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAthena Technologies 6050の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Athena Technologies 6050に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAthena Technologies 6050デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。