PioneerメーカーMUH-GA20VBの使用説明書/サービス説明書
ページ先へ移動 of 36
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ····································2 2. P ART NAMES AND FUNCTIONS ······················6 3. SPECIFICA TION·················································6 4.
TECHNICAL CHANGES 2 1 MUH-A07YV - ➔ MUH-GA20VB- 1. Indication of capacity has been changed. (BTU base ➔ kw) 2. Dimension of outdoor unit has been changed. ( 780W o 540H o 255D ➔ 800W o 550H o 285D) 3. Stop valve cover has been added. 4. Outdoor fan motor has been changed.
3 Refrigeration oil Refrigerant New refrigerant R410A HFC-32: HFC-125 (50%:50%) Pseudo-azeotropic refrigerant Not included A1/A1 72.6 -51.4 1.557 64 Non combustible 0 1730 From liquid phase in cylinder Possible Incompatible oil Non Non Previous refrigerant R22 R22 (100%) Single refrigerant Included A1 86.
4 2.Refrigerant piping 1 Specifications Use the refrigerant pipes that meet the following specifications. • Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
5 R410A Pipe diameter mm 6.35 9.52 17 22 Dimension of flare nut R22 17 22 2 Flaring work and flare nut Flaring work for R410A pipe dif fers from that for R22 pipe.
6 P ART NAMES AND FUNCTIONS 2 ( ) Air inlet Air outlet Drain outlet Piping Drain hose back : MUH-GA20VB back and side : MUH-GA25VB MUH-GA35VB OUTDOOR UNIT MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - E1 E1 .
7 NOISE CRITERIA CUR VES 4 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMA TE TERESHOLD OF HEARING FOR CONTINUOUS NOISE NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT AVE BAND SOUND PRESSURE LEVEL, dB re 0.
8 OUTLINES AND DIMENSIONS 5 10 69 800 302.5 500 Bolt pitch for installation 150 22.3 Handle 550 280 164.5 99.5 170.5 23 Service panel Service port 285 344.5 44 400 Air in Air out Air in 17.5 Bolt pitch for installation 304~325 40 Liquid refrigerant pipe joint Refrigerant pipe (flared) [ 6.
9 WIRING DIAGRAM 6 MODELS WIRING DIAGRAM SYMBOL T61 TB1,TB2 21S4 52C SYMBOL MF NR61 RT61 SR61,SR62 SYMBOL C1 C65 DSAR F61 MC NAME NAME NAME COMPRESSOR CAP ACIT OR OUTDOOR F AN CAP ACIT OR SURGE ABSORBER FUSE(2A) COMPRESSOR(INNER PROTECTOR) V ARIST OR DEFROST THERMISTOR SOLID ST A TE RELA Y TRANS FORMER TERMINAL BLOCK R.
10 REFRIGERANT SYSTEM DIAGRAM 7 OUTDOOR UNIT (with heat insulator) Refrigerant pipe [ 9.52 4-way valve Defrost thermistor RT61 Muffler Outdoor heat exchanger Capillary tube [ 3.0x [ 1.4x700 (MUH-GA20VB) [ 3.0x [ 1.4x1000(MUH-GA25VB) [ 3.0x [ 1.4x500 (MUH-GA35VB) Capillary tube [ 3.
11 Piping size O.D : mm Length of connecting pipe : m Model Refrigerant piping Max. length : m A 20 25 Indoor unit Gas 0.43 Liquid 0.5 Liquid 6.35 Gas 9.
12 MSC-GA20VB - E1 MUH-GA20VB - E1 MUH-GA35VB - E1 MSC-GA35VB - E1 MUH-GA25VB - E1 MSC-GA25VB - E1 8.5 7.8 7.1 6.4 5.8 5.1 10.0 9.2 8.3 7.5 6.8 6.0 1 1.0 10.0 9.1 8.2 7.4 6.5 20.0 18.5 16.9 15.4 13.9 12.3 10.8 9.2 19.2 17.8 16.3 14.8 13.3 1 1.8 10.4 8.
13 8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation ① Both indoor and outdoor unit are under the same temperature/humidity condition. ➁ Air flow should be set at MAX. Dry-bulb temperature Relative humidity(%) 20 50 25 60 30 70 ③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
14 HEA T operation Condition indoor:Dry bulb temperature 20.0°C Wet bulb temperature 14.5°C Outdoor:Dry bulb temperature 7,15,20°C Wet bulb temperature 6,12,14.
15 MSC-GA20VB - : MUH-GA20VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 2.70 1.51 0.56 572 2.59 1.45 0.56 601 2.48 1.39 0.56 629 2.39 1.34 0.56 658 21 20 2.82 1.24 0.44 601 2.70 1.19 0.44 636 2.62 1.15 0.44 651 2.53 1.11 0.44 679 22 18 2.70 1.
16 MSC-GA20VB - : MUH-GA20VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 2.25 1.26 0.56 701 2.07 1.16 0.56 744 1.99 1.11 0.56 758 21 20 2.37 1.04 0.44 729 2.21 0.97 0.44 765 2.13 0.94 0.44 787 22 18 2.25 1.35 0.60 701 2.07 1.24 0.60 744 1.99 1.
17 MSC-GA25VB - : MUH-GA25VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 3.11 1.62 0.52 656 2.98 1.55 0.52 689 2.86 1.49 0.52 722 2.76 1.43 0.52 754 21 20 3.25 1.30 0.40 689 3.11 1.25 0.40 730 3.02 1.21 0.40 746 2.92 1.17 0.40 779 22 18 3.11 1.
18 MSC-GA25VB - : MUH-GA25VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 2.60 1.35 0.52 804 2.39 1.24 0.52 853 2.29 1.19 0.52 869 21 20 2.73 1.09 0.40 836 2.54 1.02 0.40 877 2.45 0.98 0.40 902 22 18 2.60 1.45 0.56 804 2.39 1.34 0.56 853 2.29 1.
19 MSC-GA35VB - : MUH-GA35VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 4.11 1.97 0.48 872 3.94 1.89 0.48 916 3.78 1.81 0.48 959 3.64 1.75 0.48 1003 21 20 4.29 1.54 0.36 916 4.11 1.48 0.36 970 3.99 1.44 0.36 992 3.85 1.39 0.36 1036 22 18 4.
20 MSC-GA35VB - : MUH-GA35VB - E1 E1 PERFORMANCE DA T A COOL operation (230V) 21 18 3.43 1.65 0.48 1068 3.15 1.51 0.48 1134 3.03 1.45 0.48 1155 21 20 3.61 1.30 0.36 1112 3.36 1.21 0.36 1166 3.24 1.17 0.36 1199 22 18 3.43 1.78 0.52 1068 3.15 1.64 0.52 1134 3.
21 MSC-GA20VB - : MUH-GA20VB - E1 E1 PERFORMANCE DA T A HEA T operation (230V) MSC-GA25VB - : MUH-GA25VB - E1 E1 OUTDOOR WB( : ) INDOOR -10 -5 0 5 10 15 20 DB( : ) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT CAP ACITY : 2.5(kW) INPUT : 690(W) 15 21 26 1.
22 TROUBLESHOOTING 10 3. T roubleshooting procedure 1) First, check if the OPERA TION INDICA TOR lamp on the indoor unit is flashing on and off to indicate an abnormality . T o make sure, check how many times the abnormality indication is flashing on and of f before starting service work.
23 10-2. Instruction of troubleshooting Start Indoor unit operates. Outdoor unit doesn't operate. Indoor unit doesn't receive the signal from remote controller . Indoor unit operates. Outdoor unit doesn't operate normally . OPERA TION INDICA T OR lamp on the indoor unit is flashing on and off.
24 A A Check of outdoor unit Compressor and/or outdoor fan motor doesn’t operate. Y es Compressor doesn't operate. Y es Y es Is there 230V AC between 3 on the compressor contactor (52C) and N on the outdoor terminal block (TB1)? Operate the unit in COOL or HEA T mode by pressing the EMERGENCY OPERATION switch.
25 B B Check of outdoor unit Does compressor stop? No Y es Is there 230V AC between 3 on the compressor contactor (52C) and N on the outdoor terminal block (TB1)? Replace the deicer P .C. board. Y es OK No Does outdoor fan motor stop? Replace the deicer P .
26 D D How to check mis-wiring and serial signal error Serial signal error is indicated. (0.5-sec. ON, 0.5-sec. OFF) 1. T urn OFF the power supply (indoor/outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side. 2. Short-circuit between indoor terminal block N and 3 .
27 E E Check of outdoor thermistor Measure resistance between CN 661 1 and 2 . No Y es Replace the thermistor . Defrost thermistor (RT61) Reconnect CN661. T urn ON the power supply and press the EMERGENCY OPERA TION switch. Is the resistance of thermistor normal? No Y es Does the unit operate 10 minutes or more? Replace the deicer P .
28 MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - Outdoor deicer P .C. board E1 E1 E1 CN71 1 Outdoor fan motor 230V AC CN721 R.V . coil 230V AC F61 Fuse 2A/250V } } CN661 1 - 2 Defrost thermistor RT61 } 12V D.
29 DISASSEMBL Y INSTRUCTIONS 11 MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - OUTDOOR UNIT E1 E1 E1 OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the top panel. (2) Remove the screw of the service panel. (3) Remove the screws of the cabinet.
30 3. Removing the propeller and the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut. (3) Remove the propeller . NOTE : Loose the propeller in the rotating direction for removal. When attaching the propeller , align the mark on the propeller and the motor shaft cut section.
31 OPERA TING PROCEDURE PHOTOS 4. Removing the compressor (1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor . (5) Disconnect lead wires from the glass terminal of the com- pressor .
32 P ARTS LIST 12 22 3 5 2 21 1 ( W ) 15 12-1. OUTDOOR UNIT STRUCTURAL P ARTS MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - E1 E1 E1 4 17 14 19 20 18 13 6 7 8 9 10 1 1 12 16 23 ( W ) This figure shows MUH-GA20VB.
33 Part numbers that are circled are not shown in the illustration. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 E02 904 630 E02 905 630 E02 906 630 E02 90.
34 OB387-2.qxp 05.2.21 10:03 AM Page 34.
35 OB387-2.qxp 05.2.21 10:03 AM Page 35.
C C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Feb. 2005. No.OB387 6 Made in Japan New publication, effective Feb. 2005 Specifications subject to change without notice. HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, T OKYO100-8310, JAP AN OB387-2.
デバイスPioneer MUH-GA20VBの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Pioneer MUH-GA20VBをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはPioneer MUH-GA20VBの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Pioneer MUH-GA20VBの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Pioneer MUH-GA20VBで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Pioneer MUH-GA20VBを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はPioneer MUH-GA20VBの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Pioneer MUH-GA20VBに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちPioneer MUH-GA20VBデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。