PV500 - 22A 08 - 98 1 Section 22A INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER B40 OIL BURNER 1.0 thru 10.0 gph CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a seasonal or annual combustion check - out be performed by a qu alified service agency to ensure safe and efficient operation.
PV500 - 22A 08 - 98 2 Section 22A PVI FIREPOWER B40 OIL BURNER ELECTRICAL 1. Wiring to the unit should conform to the National Electrical Code or the code legally authorized to your locality. A fused disconnect switch should be used for water heater control.
PV500 - 22A 08 - 98 3 Section 22A PVI FIREPOWER B40 OIL BURNER START - UP (Refer to Figure 22 - 1 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. The wiring diagram, located on the backside of the cover, will show the controls used in our circuitry.
PV500 - 22A 08 - 98 4 Section 22A PVI FIREPOWER B40 OIL BURNER START - UP (con't) After purging is complete, terminal 3 energizes the oil valve and terminal 4 energizes the ignition transformer. The flame is then established and the VDC reading on the meter should read a steady 14 - 18 VDC for photocell or 4 - 6 VDC for UV amplifiers.
PV500 - 22A 08 - 98 5 Section 22A PVI FIREPOWER B SERIES OIL BURNER START - UP (con't) 20. Record the following information for future use: a) Air shutter position ________________ b) Oil supply pressure ____________PSIG c) Stack draft _________________" W.
PV500 - 22A 08 - 98 6 Section 22A PVI FIREPOWER SINGLE STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT Loosen the locking screw and move the knob (A) along the scale (B) to the position wanted and tighten the screw. Check the air adjustment by making a flue gas analysis.
PV500 - 22A 08 - 98 7 Section 22A PVI FIREPOWER TWO STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT First stage : Set the operating switch on low capacity. Loosen the screw (A) and move the damper ar m (C) along the scale (E) to a position where the flame does not soot nor blow out.
PV500 - 22A 08 - 98 8 Section 22A PVI FIREPOWER NOZZLE POSITION INPUT - GPH NOZZLE POSITION 1.4 1 2.8 3 4.3 4 5.7 2 7.2 2 8.6 4 TABLE 22 - 2 Figure 22A - 8.
PV500 - 22A 08 - 98 9 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER 1. BURNER FAILS TO START: A. Defective on/off or fuel transfer switch. Replace switch. B. Control circuit has an open control contact. Che ck limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 22A 08 - 98 10 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 4. OIL FLAME IGNITES, BUT THEN FLAME SAFEGUARD CONTROL LOCKS OUT ON SAFETY: A. Flame scanner lens dirty. Remove and clean. B. Scanner si ght tube blocked or dirty.
PV500 - 22A 08 - 98 11 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 6. OIL HIGH FIRE INPUT RATE CANNOT BE ACHIEVED: A. Oil nozzle size too small. Remove nozzle and check marking. Replace with correct size nozzle. B.
デバイスPVI Industries B40の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
PVI Industries B40をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはPVI Industries B40の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。PVI Industries B40の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。PVI Industries B40で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
PVI Industries B40を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はPVI Industries B40の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、PVI Industries B40に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちPVI Industries B40デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。