PV500 - 9 04 - 2000 ( 1 ) Section 9 PVI FIREPOWER GAS BURNER TYPICAL CONSTRUCTION Figure 9 - 1 1. Burner housing 15. Air switch 29. Orifice location * 2. Air intake 16. Door assembly * 30. Electrode retaining bracket 3. Oil pump opening plug 17. Flame sensing electrode 31.
PV500 - 9 04 - 2000 ( 2 ) Section 9 POWER GAS BURNER START - UP (Refer to Figure 9 - 1 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. Located on the back side of this cover is a wiring diagram of the unit.
PV500 - 9 04 - 2000 ( 3 ) Section 9 POWER GAS BURNER ST ART - UP (Con’t) clearance). Ensure plate is seated firmly against the gas spider and tighten the plate retaining screws.
PV500 - 9 04 - 2000 ( 4 ) Section 9 POWER GAS BURNER START - UP (Con’ t) 20. Direct Spark Ignition – (DSI) Burners – No pilot: 1. Connect a manometer to the manifold test port. Set the air shutter as shown on the tag attached to the gas train. This may not be the exact setting you end up with, but it is a good starting point.
PV500 - 9 04 - 2000 ( 5 ) Section 9 REMOVAL OF THE NOZZLE ASSEMBLY (EXCEPT “L” SERIES BURNERS) Figure 9 - 2 ELECTRODE POSITIONS “L,P,Q,R,S,T” SERIES BURNER Figure 9 - 3.
PV500 - 9 04 - 2000 ( 6 ) Section 9 AIR ADJUSTMENT FIXED AIR BURNERS Loosen the locking screw and move the arm (B) along the scale (C) to the position wanted and tighten the screw.
PV500 - 9 04 - 2000 ( 7 ) Section 9 Figure 9 - 6 NOTE: Nomograph is limited for use with Natural Gases with the following characteristics: Heating Value (gross) Btu/SCF - 970 - 1100; Specific G ravity - 0.
PV500 - 9 04 - 2000 ( 8 ) Section 9 NOMOGRAPH FOR DETERMINING FLUE LOSSES FROM CO 2 AND FLUE TEMPERATURE FOR L.P. GAS (STEADY STATE EFFICIENCY CAN BE DETERMINED FROM THE FLUE LOSS) Figure 9 - 7 NOTE: Nomograph is limited for use with L.P. Gas with the following characteristics: Heating Value (gross) Btu/SCF – 2466 - 2542; Specific Gravity – 1.
PV500 - 9 04 - 2000 ( 9 ) Section 9 TROUBLESHOOTING SUGGESTIONS GAS BURNER 1. BURNERS FAILS TO START A. Defective On/Off or fuel transfer switch. Replace swi tch. B. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 9 04 - 2000 ( 10 ) Section 9 TROUBLESHOOTING SUGGESTIONS GAS BURNER (Con't) 5. CARBON MONOXIDE READINGS ON GAS FIRING A. Flame impingement on "cold" heat transfer surfaces caused by excessive firing rate. Reduce firing rate to correct input volume.
デバイスPVI Industries FIREPOWER PV500-9の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
PVI Industries FIREPOWER PV500-9をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはPVI Industries FIREPOWER PV500-9の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。PVI Industries FIREPOWER PV500-9の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。PVI Industries FIREPOWER PV500-9で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
PVI Industries FIREPOWER PV500-9を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はPVI Industries FIREPOWER PV500-9の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、PVI Industries FIREPOWER PV500-9に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちPVI Industries FIREPOWER PV500-9デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。