RaypakメーカーHot Water Energy Management Controlの使用説明書/サービス説明書
ページ先へ移動 of 30
INST ALLA TION AND OPERA TING INSTRUCTIONS RayT emp™ Hot W ater Energy Management Contr ol Catalog No: 5000.61B Effective: 04-15-05 Replaces: 09-01-02 P/N 241098.
2 Section 1. GETTING ST ARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 THE BIG PICTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 WHA T COMES WITH THE CONTROLL .
3 THE BIG PICTURE This RayT emp control is designed to make recirculating domestic hot water heating systems ener gy efficient. In a r ecirculating sys- tem, hot water is continuously pumped throughout the building. This lar ge loop has many branch- es which extend to fixtures in the rooms.
4 WHA T COMES WITH THE CONTROL Before arriving at the job site to begin the installation, it’ s important to first inspect the system and determine what materials you will need. Some parts are included with the control while the oth- ers you will need to provide.
5 On the sensor end, roll the shielding and tape so it will not contact a conductor . On the control end, the shield should be grounded. Do not ground both ends of the shielding. A void routing wiring on or near other electrical wires, conduit, motors, spark igniters or other sources of high, intermittent voltage or current.
6 Fig # 8285.2 INST ALLA TION LA YOUT.
7 ”DIP” SWITCH SETTINGS ON CIRCUIT BOARD CAUTION: Incorrect DIP switch settings may damage the RayT emp!!! Make all adjustments with ALL power off. The four relay outputs are factory set for normally closed dry contacts. These DIP switches ar e located behind the terminal block, on the right side.
CONNECTING THE OPTIONAL “ELSA” BRAND MODEM Raypak recommends the ELSA Microlink 56k modem for data communication. This modem will work with RayT emp and technical support will be provided if this modem is installed with the cor- rect cables. Raypak will not be able to provide support if you use other modem brands or build your own cables.
9 USING THE FRONT P ANEL TO CHECK SENSORS AND RELA YS The RayT emp front panel features an alphanumeric LCD display of four r ows by 20 lines. Six keys are provided to select scr eens, fields, and make pr ogram changes. The up-arrow and down-arr ow "WINDOW" keys are used to step thru each of the screens.
10 Section 3. CONNECTING A COMPUTER This section explains how to connect your personal computer to the RayT emp. Once connected, you can view all of the front panel screens cover ed in the previous section. Y ou can also retrieve the recorded data and view color graphs of temperatur e and demand profiles.
11 INST ALLING PTT SOFTW ARE ON YOUR PC This section provides instructions for installing PTT communication software. First insert the PTT CD into your CD drive. Double click on the folder Ptt258 then double click on Install. The PTT communication software will then be installed on your C:GBX subdirectory .
12 READING LOGGED DA T A Under the "History Report" menu item, logged data can be retrieved from a RayT emp control, saved to a disk file, viewed graphically on screen, or output to a printer . T o retrieve history , con- nect the RayT emp serial cable between the RayT emp and your laptop PC.
13 T o end the modem session, select the following screen in the LapT op window . This screen is used to terminate the call. The RayT emp will actually terminate the phone connection and prevent the modem from answering the phone for about five minutes.
14 Section 4. PROGRAMMING QUICK REFERENCE This section describes all the programmable features of the contr ol. Y ou make program changes from the front panel or by using a laptop. For information on connection with a LapT op using PTT software, refer to the pr evious section.
15 Screen code and description, in sequence of appearance See page FM PRODUCT IDENTIFICA TION - Model, type, and version 17 SE SENSORS - Displays temperature of each standard sensor 17 OS OPTIONAL SEN.
16 Screen Code and Description - continued See page HL SELECT - Supply High Limit 20 LL SELECT - Supply Low Limit 20 DW SELECT - Demand window in minutes 20 DM SELECT - Demand % for maximum temperatur.
17 FIRST SCREEN A T POWER-UP FM PRODUCT IDENTIFICA TION. This screen displays the model number , type of control, copyright notice, and software version number . Press F2 to select the next screen in or der , or press two keys for direct access to any one of the following screens.
18 ERASE MEMORY / RESET PROGRAM ER ERASE/RESET - Press F4 or F5 to select which item will be r eset or cleared, then press CTRL+E to confirm each action. Set BAUD Rate will reconfigure the serial port accor ding to the BA screen. If the speed is differ- ent, then reset the BAUD rate on your LapT op (garbage characters will appear).
19 TIME SCHEDULE TS TIME SCHEDULE This is a seven-day time clock. Each line is a program for starting a new period (such as Night) on a day (such as M-F) and at a time (such as 6:00 am). Up to 20 lines can be displayed or programmed using the SP ACE, F4 and F5 keys.
20 C6 SELECT - Maximum Extra T emperature C6 and C7 are an extra set of temperatures which can be scheduled for any purpose. They will become the maximum and minimum supply temperature if the Extra schedule is activated by the time clock. Default T emp 140°F .
21 RETURN TEMPERA TURE The return sensor is used to compensate for seasonal changes in loop heat loss. The strategy may raise the supply/branch temperature in cold weather to ensure that the last r ooms on the loop have hot enough water even during low demand periods.
22 BRANCH TEMPERA TURE - NOT USED B0 SELECT - # of Branch Sensors Installed Not used. RELA Y SEQUENCING HS SELECT - # of Heaters Enter 1 thru 4 for the number of heaters connected to relay out- puts 1 thru 4. This allows the RayT emp to correctly sequence heaters and recor d demand.
23 DD SELECT - Differential Increasing DD lengthens the heater burn cycle; decr easing DD improves temperature stability . For instance: desired=140, deadband=1, heater turns off at 141 and on at 139.
24 SA VINGS TEST SETUP S1 SELECT - Day of Month for Savings T est Selecting a value other than 0 (default) acti- vates the flip-flop savings test. This test will cause a simulation of conditions before the RayT emp was installed - for 24 hours on the day specified every month.
25 T otal days in service displays the total operating days in modes RUN, BYP ASS, and OFF . When 24 V AC power is absent this value will not increase however the clock will still operate. Number of power interruptions value is incremented each time 24 V AC power is removed or inter- rupted.
26 LOCA TION TEXT DN TEXT - Company Name Accepts entry of company name into RayT emp memory . This information will appear in installation reports. Edit with SP ACE, BACKSP , F4, and F5. PN TEXT - Property Name Accepts entry of site name into RayT emp memory .
27 F AX MODEM SETUP AND TEST FD TEXT - Fax Dial-Out Use this screen to enter the phone number of the fax machine which is to receive fax alarm messages, installation reports, and/or graphics. Example "A TDT5551212". Edit text with SP ACE, BACKSP , F4, and F5.
28 XH V ALUE - Fax on Hour of Day This option sets the time of day to transmit fax reports. It works in conjunction with XW and XM, above. The RayT emp will attempt to fax the specified data on the specified day (above) and at this specified time. Military time is used with values of 0 to 23, 12 is noon.
29 W ARRANTY The Raypak RayT emp Control is warranted to be free from defects in material and workmanship for a peri- od of one year from the date of installation or fourteen months from date of shipment, whichever occurs first.
Raypak Inc., 2151 Eastman A venue, Oxnard, CA 93030 • (805) 278-5300 • (800) 872-9725 www .raypak.com.
デバイスRaypak Hot Water Energy Management Controlの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Raypak Hot Water Energy Management Controlをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRaypak Hot Water Energy Management Controlの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Raypak Hot Water Energy Management Controlの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Raypak Hot Water Energy Management Controlで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Raypak Hot Water Energy Management Controlを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRaypak Hot Water Energy Management Controlの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Raypak Hot Water Energy Management Controlに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRaypak Hot Water Energy Management Controlデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。