High Efficiency Commercial Gas W ater Heater USE & CARE MANUAL WITH INST ALLA TION INSTRUCTIONS FOR THE CONTRACTOR ON OFF This Use & Care Manual covers the following model numbers: HE45-100N H.
2 SPECIFICA TIONS DIMENSIONAL INFORMA TION All dimensions shown in English and Metric MODEL W A TER CONNECTIONS APPROX NUMBER UNITS HEIGHT WIDTH DEPTH VENT INLET OUTLET SHIPPING WT . inches 42 23 1/2 32 2 1 1 175 lbs. mm 1067 597 813 51 25 25 79 kgs inches 42 23 1/2 32 3 1 1 175 lbs.
Gasoline, as well as other flammable materials and liq- uids (adhesives, solvents, etc.), and the vapors they pro- duce, are extremely dangerous. DO NOT handle, use or store gasoline or other flammable or combustible materi- als anywhere near or in the vicinity of a water heater .
age, personal injury or fire: DO NOT connect this water heater to a fuel type not in accordance with unit rating plate. Propane gas for prop ane units.
Read and review this entire manual with special emphasis on the V enting Sections and Operation Sections prior to any inst allation work. LOCAL INST ALLA TION REGULA TIONS This water heater must be in.
devices may shorten the life of the water heater and may endanger life and property . The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices.
T ank MUST be full of water before power is turned on. Heat exchanger coil WILL BE DAMAGED if ener- gized even for a short time while the t ank is dry . The water heater ’ s warranty does not cover damage or failure resulting from operation with an empty or p ar- tially empty t ank.
VENTING WHEN USING 3" VENT PIPE (ONL Y MODELS WITH INPUTS OF 100,000 BTU AND 130,000 BTU ARE CERTIFIED TO USE 2" VENT PIPE, SEE SPECIAL VENTING INSTRUCTIONS SECTION) For inlet air supply , top pipe on the right of the shroud, use 3" PVC schedule 40.
9 or two 45 degree elbows . Then use a 4" x 3" PVC or 4" x 3" ABS reducing coupling. Then proceed with PVC 4" NON FOAM CORE pipe and fittings for both the intake and exhaust piping. On 4" piping you may go an addi- tional 125 equivalent feet of pipe and fittings, combined total length.
10 3' 0' 1' = 1' 4" 45˚ FRICTION LOSS EQUIVALENCE TABLES EQUIVALENT FEET OF PIPE 3" VENTED MODELS 2" VENTED MODELS AFTER THE FIRST 10' OF 3" ONLY 4" .
CONTROL DESCRIPTION The fully integrated water heater control is an all elec- tronic, fully automatic controller which will provide many years of trouble free service. The control requires no periodic maintenance and includes a built-in micro- processor which performs a number of diagnostic tests to verify proper appliance and control operation.
There is a hot water SCALD POTENTIAL if the thermost at is set too high. THERMOST A T DIFFERENTIAL ADJUSTMENT PROCEDURE T o allow proper water heater operation, the control has an 8°F "window" around the set point.
F AILURE TO OPERA TE Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout state (flash- ing “LOC”).
14 Component s of the AdvantagePlus 1. 1/2” NPT x 6” Gas Inlet Nipple 2. Gas V alve 3. Gas V alve Elbow 4. Gas Orifice Union 5. Gas Orifice 6. Union Connector Nipple 7. Main Control PC Board 8. Display PC Board 9. Pressure Switch 10. T ransformer 1 1.
15 NOTES ________________________________________________________________________________ ________________________________________________________________________________ _____________________________.
16 LINE K1 COMB BLOWER K5 IGNITER ELEMENT 24 VAC ECO/VENT SWITCH SWITCH PRESSURE GAS VA LV E RL Y 1 GAS VA LV E RL Y 2 GAS VA LV E CONTROL HEAL TH WA TER TEMPERA TURE K1 K5 K3 K4 K4 K3 CONTROL ELECTRO.
17 LINE K1 COMB BLOWER K5 IGNITER ELEMENT 24 VAC ECO/VENT SWITCH SWITCH PRESSURE GAS VA LVE RL Y 1 GAS VA LVE RL Y 2 GAS VA LVE CONTROL HEAL TH WA TER TEMPERA TURE K1 K5 K3 K4 K4 K3 CONTROL ELECTRONIC.
18 POSSIBLE CAUSE 1. No Input power . 2. Wiring disconnected 3. One or more wiring recep- tacles disconnected from control. 4. LED burned out. 5. Defective transformer . 6. T ransformer wiring problem. REMEDY 1. Apply Power 2. Check all wiring 3. Reconnect plugs on control.
19 POSSIBLE CAUSE 1. Burner ground wire broken or corroded. 2. Connectors unplugged. 3. Flame probe faulty . 4. Gas shut off. 5. Clogged gas valve. 6. Faulty gas valve. 7. Defective control. 8. Burner improperly adjusted. 9. Dirty burner . 10. Improper line connection.
20 POSSIBLE CAUSE This indicates that the main control board has failed one or more of its internal diagnostic self-tests. REMEDY Press red reset button on the display board to reset the con- trol. If this error occurs repeat- edly , replace the main control board.
21.
22 Integrated W ater Heater Control Parts Identification Drawing.
23 INT AKE EXHA UST HO T COLD 24" MIN. 10' - 0" MIN. MAINT AIN 12" MIN. (18" MIN. FOR CANADA) CLEARANCE ABO VE HIGHEST ANTICIP A TED SNOW LEVEL.
24 V enting Samples INT AKE EXHA UST HO T COLD 24" MIN. 10' - 0" MIN. MAINT AIN 12" MIN. (18" MIN. FOR CANAD A) CLEARANCE ABO VE HIGHEST ANTICIP A TED SNOW LEVEL.
25 3" PVC 3" PVC GAS 3" ABS MIN 84" REQ'D CONDENSA TE DRAIN 3" ABS MIN 84" REQ'D 3" ABS MIN 84" REQ'D 3" PVC 3" PVC 3" PVC 3".
26 Sequence of Operations Fill tank Ensure gas connections are present and no leaks Ensure water heater is properly vented YES LINE See Flashing LED table 24 VAC ECO/VENT SWITCH CONTROL HEALTH YES LIN.
27 Sequence of Operations LINE See Flashing LED table 24 VAC Igniter remains on for an addition 4 seconds. ECO/VENT SWITCH CONTROL HEALTH Burner lights. WATER TEMPERATURE COMB BLOWER Presence of flame is rectified. PRESSURE SWITCH IGNITER ELEMENT GAS VALVE YES Water is heating.
28 LED Flashing Controlling F unction Possible C ause Ser vice Remedy LINE Check Break er T ur n breaker ON Wiring disconnected Check wiring Does not hav e 120 V AC Reseat plugs on control module 24 V.
HOW T T O O O BTAIN S S ERVICE A A SSISTANCE Should y ou ha ve an y questions about your ne w water heater , or if it requires adjustment, or routine maintenance, it is suggested that y ou first contact your installer , plumbing contractor or previously ag reed upon ser vice agency .
MOST COMMON ADV ANT AGEPLUS INST ALLA TION CONCERNS VENTING: VENT LENGTH TOO LONG - OVER 85’ VENTING NOT PITCHED PROPERL Y - CONDENSA TE BUILD UP IN VENT EXHAUST GAS RE-CIRCULA TION - VENT TERMINALS.
デバイスRheem HE45-199Nの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Rheem HE45-199Nをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRheem HE45-199Nの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Rheem HE45-199Nの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Rheem HE45-199Nで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Rheem HE45-199Nを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRheem HE45-199Nの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Rheem HE45-199Nに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRheem HE45-199Nデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。