DIGIT AL NON-PROGRAMMABLE THERMOST A T 9420 HEA T PUMP H NeW 2 Heat / 2 Cool User's Manual Quick Start Installation Application The Robertshaw 9420 is a multi-stage thermostat designed to control 24 V AC heat pump systems. Features • Summer and winter setpoints •L arge back lit display • Adjustable 1 st stage temperature differential: 0.
IMPORT ANT SAFETY INFORMA TION W ARNING: • Always turn off power at main fuse or circuit breaker panel before installing, removing, cleaning, or servicing thermostat. • Read all the information in this manual before installing this thermostat. • This is a 24 V AC low-voltage thermostat.
Recycling Thermostat If this thermostat is replacing a thermostat that contains mercury in a sealed tube, do not place your old thermostat in the garbage. Contact your local waste management authority for instructions regarding proper disposal of the thermostat.
5. Place thermostat against the wall at desired location. Make sure wires will feed through opening (Figure 4) on base of thermostat. 6. Mark placement of mounting holes (Figure 4). Set base aside. 7. If mounting on drywall, tap plastic anchors into wall.
5 T yp ical heat p um p with cool active reversin g valve and auxiliar y /emer g enc y heat. T yp ical heat p um p with heat active reversin g valve and auxiliar y /emer g enc y heat. T yp ical heat p um p with cool active reversin g valve and auxiliar y /emer g enc y heat.
15. Replace thermostat cover by snapping into place. 16. T urn on power to system. T est thermostat as described in the following section. Step 3: T esting the Thermostat W ARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS V AL VE OR SYSTEM CONTROL TO TEST OPERA TION.
7 NOTE: ONCE THE THERMOST A T TURNS OFF , A BUIL T IN 5-MINUTE DELA Y PREVENTS THE SYSTEM FROM TURNING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO ADDITIONAL TIME DELA Y RELA Y IS REQUIRED. TO OVERRIDE THE 5-MINUTE DELA Y FOR INST ALLA TION, PRESS THE RESET BUTTON.
Step 4: Customizing the Thermostat ◆ Settings System Cool: The thermostat controls the cooling. Off: The heating and cooling systems are off. Heat: The thermostat controls the heat. Emer: The thermostat controls the second stage emergency heat. Used only when the primary stage of heat is not functioning or requires service.
9 ◆ T emperature Differential 2 nd Stage Delay The temperature differential is factory set at 1.0°F (.5°C) for the 1st stage differential and 2°F (1°C) for the 2nd stage. This means that whenever the room temperature changes by one degree Fahrenheit from the tempera- ture setting, the system will turn on.
10 WIRING OPENING Reset Switch ◆ Reset To reset the thermostat press the RESET button located just below the lower left corner of the display . Step 5: T r oubleshooting Symptom Remedy Display shows CHECK Monitors system status. Call your local HV AC service provider .
T wo Y ear Limited Warranty Climate Controls Americas warrants to the original contractor installer , or to the original consumer user , each new Robertshaw thermo- stat to be free from defects in materials and workmanship under normal use and service for a period of two (2) years from date of purchase.
NOTES 12.
デバイスRobertshaw 9420の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Robertshaw 9420をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRobertshaw 9420の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Robertshaw 9420の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Robertshaw 9420で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Robertshaw 9420を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRobertshaw 9420の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Robertshaw 9420に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRobertshaw 9420デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。