RuggedComメーカーRSG2288の使用説明書/サービス説明書
ページ先へ移動 of 43
RuggedSwitch ® RSG2288 9-Port Modular Managed Gigabit Ethernet Switch Installation Guide February 15, 2011 www.ruggedcom.com RuggedCom Inc. I 300 Applewood Crescent, Concor d, Ontario, Canada L4K 5C7.
Cop yright COPYRIGHT © 2010 RuggedCom Inc. ALL RIGHTS RESERVED Dissemination or reproduction of this document, or evaluation and communication of its contents, is not authorized except where expr essly permitted. Violations are liable for damages. All rights reserved, particularly for the purposes of patent application or trademark registration.
Federal Communications Commission Radio Frequency Interference Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules.
Table of Contents T able of Content s Table of Contents .............................................................................................................. 4 Table of Figures .................................................................
Table of Contents 4.3 IEC Environmental Type Tests ........................................................................ 42 5 Agency Approvals ................................................................................................... 43 6 Warranty .
Table of Figures T able of Figures Figure 1: RSG2288 Rack mount chassis orientation options – Front and rear mount. ... 11 Figure 2: RSG2288 Ethernet Port Layout ....................................................................... 12 Figure 3: Ethernet panel LEDs .
Table of Tables 7 RuggedCom ® RuggedSwitch ® RSG2288 Installation Guide rev103 T able of T ables Table 1: Pluggable Fiber Transceiver Modules............................................................... 13 Table 2: Fixed Fiber Transceivers........
Product Overview 1 Product Overview 1.1 Functional Overview The RuggedSwitch ® RSG2288 is an industrially hardened, fully managed, modular, Ethernet switch specifically designed to operate reliably in electrically harsh and climatically demanding utility s ubstation and industrial environments.
Product Overview Cy ber Security Features Multi-level user passwords SSH/SSL encryption MAC-based port security Selective port enable/disable Port-based network access control using IEEE 802.
Product Overview Port configuration, status, statistics, mirroring, security Loss of link management on fiber ports SNTP time synchronization (both client and server) Industrial automation features (e.
Product Overview 1.3 Mounting Flexibility The RS2000 series of products have been designed with maximum mounting and display flexibility. Customers can order an RS2000 series switch th at can be mounted in a standard 19” rack, 1” DIN Rail, or directly onto a panel.
Product Overview 1.4 Ethernet Panel Description The Ethernet connector panel of the RSG2288 is organized into six slots, five of which are modular and may be selected at the time the unit is ordered. Figure 2 shows the p hysical layout of these ports.
Product Overview 1.4.1 Fiber Optic Transceiver Orientation and Connection Depending on the order code of the product, the RSG2200 series products can be equipped with several different t ypes of fiber optic ports. The Transmit (TX) and Receive (RX) connections of each port must be properly connected and matched for proper link and operation.
Product Overview Figure 6 through Figure 9 show front and top views of the fixed fiber transceiver modules supported by RuggedSwitch ® . Note that when the daughter card containing transceiver modules is installed in the unit, most of the body of the module as shown in top views below will not be visible.
Product Overview 1.5 Display Panel Description RuggedCom RS2000 series products are equipped with a versatile d isplay panel, shown in Figure 10 , which is designed to provide quick status information for each port, as well as the entire device to allow for simple diagnostics and troubleshooting.
Product Overview The port-ba sed LEDs can be cycled between three display modes: Status, Duplex, and Speed. Pushing the mode button causes the display mode to be cycled.
Installation 2 Inst allation 2.1 Rack Mounting The RS2000 family of products can be ra ck mounted using the included rack mount adapter assemblies shown in Figure 11 . Secure the rack mount adapter to the front sid e of the chassis using the included black PAN head Philips screws in the positions shown in Figure 13 .
Installation 2.2 Panel and DIN Rail Mounting RS2000 series products can be ordered as a Panel/DIN mount chassis. Both options involve the use of the panel/DIN adapters to be mounted on each side of the chassis enclosure.
Installation 2.3 Power Supply Wiring and Grounding RS2000 series products support dual redundant power supplies – “Power Supply 1 (PS1)” and “Power Supply 2 (PS2)”. The connections for PS1, PS2 and the fail- safe relay are located on the terminal block as shown in Figure 14 and Figure 15 .
Installation The RS200 0 Family chassis ground connection, shown in Figure 16 , uses a #6- 32 screw. It is recommended to terminate the ground connection in a #6 ring lug, and to use a torque setting not exceeding 15 in.lbs (1.7 Nm). Figure 16: Chassis Ground Connecti on #6 rin g lu g stainless steel standoff #6-32 screw with ext.
Installation 2.3.1 AC Power Supply Wiring Examples (RSG2288) Figure 17: AC Single Power Supply Wiring Example Figure 18: AC Dual Redundant Po wer Supply Wiring Example Notes: 100-240VAC rated equipment: A 250VAC appropriately rated circuit breaker must be installed.
Installation 2.3.2 DC Power Supply Wiring Examples Figure 19: DC Power Supply Wiring Examples Notes: 125/250VDC rated equipment: A 300VDC appropriately rated circuit breaker must be installed. A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
Installation 2.3.3 Dual Power Supplies – DC and AC Inputs Figure 20: DC and AC Power Supply Wiring Examples Notes: 125/250VDC rated equipment: A 300VDC appropriately rated circuit breaker must be installed. 100-240VAC rated equipment: A 250VAC appropriately rated circuit breaker must be installed.
Installation 2.4 Dielectric Strength (HIPOT) Testing For dielectric strength (HIPOT) testing in the field, users must remove the metal jumper located on terminal 2, 4, and 6 of the power supply terminal block.
Installation 2.5 Failsafe Alarm Relay Wiring and Specifications The “Failsafe” output relay is provided to signal critical error conditions that may occur on RS2000 series products. The contact s are energized upon power-up of the unit and remain energized unless a critical error occurs.
Installation 2.6 Console Port Wiring A RS232 console port for configuration and management of the device is located on the LED display module shown in Figure 23 . This port is intended to be a temporary c onnection during initial configuration or troubleshooting and a llows for direct serial access to the management console.
Installation 2.7 Ethernet Ports 2.7.1 RJ45 Twisted-Pair Data Ports RSG2288 Ethernet switches are equipped with up to nine 10/100/1000BaseTX ports that allow connection to st andard CAT-5 UTP cable with RJ45 male connectors. All RS2000 series RJ45 RuggedSwitch products feature auto- negotiation, auto-polarity, and auto-crossover functions.
Installation Cabling Category 1000BaseTx Compliant Required action < 5 No New wire infrastructure required 5 Yes Verify TIA/EIA-568-A compliance 5e Yes No action required. New installations should b e designed with Category 5e components or higher 6 Yes No action required > 6 Yes Connector and cabling standards to be determined.
Installation prevent the accumulation of residue or particles that may inhibit proper operation. Ensuring that the user has properly discharged any possible electrostatic build-up in order to prevent electrostatic discharges (ESD).
Installation 2.8.2 GBIC Module Removal GBIC Modules have two locking latches, one on either side of the module, as shown in Figure 27 . To remove a GBIC modu le, disconnect any cables and replace the dust cover to protect the optics. Depress both latches simultaneously and gently pull the module from the chassis.
Installation 2.9 Precision Time Protocol (PTP) Card and IEEE1588 v2 The Precision Time Protocol (PTP) card option for the RSG2288 adds the ability to provide time synchronization via IRIG-B , and to synchronize to an external IRIG-B source or to the GPS network.
Installation 2.9.1 PTP Card Panel Description Figure 30: PTP Card Panel Description The four BNC connectors on front panel of the PTP card are defined in Table 11 , below: Connector Function AM OUT IR.
Installation Lightning arrestor (optional) Line Amplifier or Filter (optional) To ensure correct GPS signal reception, the overall system of antenna, cabling, lightning arrestor, line amplifier and filters requires a relativ e gain which should be greater than 5 dBi but less than 18 dBi (to avoid signal saturation at the receiver input).
Installation which degrades the accuracy of the calculated t ime and position. The time delay is dependent on the type of dielectric material in t he cable and ranges from 1 to 2 ns/ft.
Installation The number of IRIG-B d evices that can be connected to the AM or PWM sources is dependent on the cabling type and length as well as the input impedances of the devices. Figure 31 shows a simplified circuit diagram of the interface between an IRIG-B s ource and connected devices.
Technical Specifications 3 T echnical Specifications 3.1 Power Supply Specifications Input Range Power Supply Type Min Max Internal Fuse Rating Max . Po we r Consumption 3 12 – 24 VDC 10 VDC 36 VDC 6.3A(F) 2 48 VDC 36 VDC 59 VDC 3.15A(T) 2 HI (125/250 VDC) 1 HI (110/230 VAC) 1 88 VDC 85 VAC 300 VDC 264 VAC 2A(T) 1,2 28W Notes: 1.
Technical Specifications 3.4 Copper Ethernet Port Specifications The RSG2288 can be ordered with two-port 10/100/1000Tx modules in slots 1, 2, 3, and 4, and a one-port 10/100/1000Tx module in 5.
Technical Specifications FXA09 SM SC 9/125 1310 0 5 -37 0 90 37 FXA10 SM LC 9/125 1310 0 5 -37 0 90 37 3.5.2 Gigabit Ethernet (1000Mbps) Optical Specifications Fixed Gigabit Transceivers Order Code Mode Connector Type Cable Type (um) Tx λ (typ.) (nm) Tx min (dBm) Tx max (dBm) Rx Sensitivity (dBm) Rx Saturation (dBm) Distance (typ.
Technical Specifications 3.6 PTP Card Specifications IRIG-B PWM Input Parameter Typical Value Input Voltage TTL-Compa tible Input Impedance > 200 k Ω 3.
Technical Specifications 3.8 Mechanical Specifications Parameter Value Comments Dimensions 18.29 x 12.14 x 1.75 inches (464,57) x (308,356) x (44, 45) mm (Length x Width x Height) with mounting brackets installed Weight 10 lb (4.
Type Tests 4 T ype T est s 4.1 IEC 61850-3 Type Tests Test Description Test Levels Severity Levels Enclosure Contact +/- 8kV 4 IEC 61000-4-2 ESD Enclosure Air +/- 15kV 4 IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x Signal ports +/- 4kV @ 2.5kHz x D.
Type Tests 4.2 IEEE 1613 Type Tests IEEE Test IEEE 1613 Clause Description Test Levels Enclosure Contact +/- 8kV C37.90.3 9 ESD Enc losure Air +/- 15kV C37.90.2 8 Radiated RFI Enclosure ports 35 V/m Signal ports +/- 4kV @ 2.5kHz D.C. Power ports +/- 4kV A.
Agency Approvals 43 RuggedCom ® RuggedSwitch ® RSG2288 Installation Guide rev103 5 Agency Approvals Agency Standards Comments CSA CSA C22.2 No. 60950, UL 60950 Passed CE EN 60950, EN 61000-6-2 CE Co.
デバイスRuggedCom RSG2288の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
RuggedCom RSG2288をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRuggedCom RSG2288の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。RuggedCom RSG2288の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。RuggedCom RSG2288で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
RuggedCom RSG2288を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRuggedCom RSG2288の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、RuggedCom RSG2288に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRuggedCom RSG2288デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。