T A C Xenta ® 400 I/O modules 0-004-7771-2 (GB), 2003-07-01 ~ 0 24 V AC (19-40 V DC) } 1 2 3 4 5 6 7 8 9 10 G G0 C1C2 Comm } T AC Xenta RS232 I/O MAN 1 AUTO MAN 2 AUTO 1 2 3 4 AO 0 - 10V T AC Xenta 4.
.
T AC AB , 200 3-07-01 0-004-7771-2 (GB), 3 (36) T AC Xenta 400 I/O modules F oreword Forew or d This handbook describes the I/O modules of the T AC Xenta 400 family .
T AC Xenta 400 I/O modules F oreword 4 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 List of revisions P ar t no. Comment A uthor Date 0-004-7771-0 Original edition. KW 1999-11-20 0-004-7771-1 T AC Xenta 471 and 491/492 added. KW 2000-09-01 0-004-7771-2 Operation temp.
T AC AB , 200 3-07-01 0-004-7771-2 (GB), 5 (36) T AC Xenta 400 I/O modules Contents T A C Xenta ® 400 I/O modules This document contains proprietary information of TAC AB and is made available solely to those who operate and maintain TAC AB equipment.
T AC Xenta 400 I/O modules Contents 6 (36), 0-004-7771-2 (GB) T A C AB, 2003-07-01.
T AC AB , 200 3-07-01 0-004-7771-2 (GB), 7 (36) T AC Xenta 400 I/O modules 1 Introduction 1 Intr oduction 1. 1 T A C Xenta 400 I/O modules The T AC Xenta 400 is a series of input/output modules designed to be connected to the TAC Xenta 300 or 401 type controllers.
8 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 1 Introduction 1.3 More inf ormation The T AC Xenta 400 I/O modules and the other T AC Xenta units are also described in the following documents: • the “T AC Xenta 300 and 401 Handbook”, part no.
T AC AB , 200 3-07-01 0-004-7771-2 (GB), 9 (36) T AC Xenta 400 I/O modules 2 I/O modules in the T AC Xenta 400 series 2 I/O modules in the T A C Xenta 400 series 2. 1 Hardware units The TAC Xenta freely-programmable controllers consist of the follow- ing units.
10 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 2 I/O modules in the T AC Xenta 400 series The I/O modules are used as expansion modules for the TAC Xenta controllers, connected to these via the common TP/FT-10 network. The modules have different I/O configurations to suit different applications.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 11 (36) T AC Xenta 400 I/O modules 2 I/O modules in the T AC Xenta 400 series 2.2 Configurations The I/O modules of the TAC Xenta 400 series can be used in different configurations, for example: • Together with a stand-alone controller.
12 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 2 I/O modules in the T AC Xenta 400 series.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 13 (36) T AC Xenta 400 I/O modules 3 T echnical description 3 T echnical description 3.1 Common features 3.1.1 T erminals In all the modules, the first four screw terminals are used in the same way , i.e. two for the power supply and two for network communication.
14 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 3 T echnical description 3.1.3 T e c hnical data, common to all Supply voltage (G, G0) ................................. 24 V AC ±20%, 50/60 Hz ................................
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 15 (36) T AC Xenta 400 I/O modules 3 T echnical description 3. 2 The T A C Xenta 411/412 Digital Input module The modules have ten digital inputs and these inputs can also be used as pulse counters. In addition, the T AC Xenta 412 is equipped with LED status indicators, one for each digital input.
16 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 3 T echnical description 3 . 3 The T A C Xenta 421/422 Digital Input and Output module The modules have four digital inputs and five digital outputs. The inputs can also be used as pulse counters.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 17 (36) T AC Xenta 400 I/O modules 3 T echnical description T echnical data T A C Xenta 421 and 422 Digital inputs (X1–X4): Quantity ...........................................................................
18 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 3 T echnical description 3 . 4 The T A C Xenta 451/452 Analog Input and Output module The modules have four universal inputs, four thermistor inputs and two analog outputs. The universal inputs can also be used as digital inputs or pulse counters.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 19 (36) T AC Xenta 400 I/O modules 3 T echnical description T echnical data T A C Xenta 451 and 452 Universal inputs (U1–U4): Quantity .........................................................................
20 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 3 T echnical description 3 . 5 The T A C Xenta 471 Analog Input module The module has eight universal analog inputs (U). The analog inputs can independently be used for current input or as voltage inputs.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 21 (36) T AC Xenta 400 I/O modules 3 T echnical description • Network Management Authentication = Off • Pre-emption T imeout = Forever • The inputs will be configured as voltage inputs. Technical data TAC Xenta 471 Universal inputs (U1–U8): Quantity .
22 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 3 T echnical description Type No. TAC Menta Block type Terminal ref. Override (492) Analog outputs 8 AO - Analog outputs Y1 -Y.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 23 (36) T AC Xenta 400 I/O modules 4 Installation 4 Installation 4 . 1 Mounting The T AC Xenta controllers and I/O modules are designed for mounting on a DIN rail inside a cabinet. They can also be mounted directly on a wall.
24 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 4 Installation 4.2 Electrical installation 4.2.1 General considerations Installation is normally treated as category CA T III (IEC 664), which in principle means permanent connection to a 230 V AC mains supply .
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 25 (36) T AC Xenta 400 I/O modules 4 Installation Connections When cabinet mounting is used, jumpers may be used between M (measurement neutral) terminal pairs, as shown in the figure below and on the next page.
26 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 4 Installation When connecting G0 to ground, each T AC Xenta unit must have its own connection to the ground rail, i.e. jumpers cannot be used for the G0 terminals. Please refer to the figure on the next page.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 27 (36) T AC Xenta 400 I/O modules 4 Installation T AC Xenta 2 G0 PU G0 T AC Xenta 1 G0 PU G0 TR G0 min 1.5 mm 2 Connections between insulated signal ground ra.
28 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 4 Installation 4.2.3 Cables P ower and Communication G and G0 (Power supply): G, min. cross-sectional area ............................................... 0.75 mm² G0 to TAC Xenta, min.
T AC AB , 2003-07-01 0-004- 7771-2 (GB), 29 (36) T AC Xenta 400 I/O modules 4 Installation If a shielded communication cable is used, the shield must be grounded at one point only . Redundant wires (second pair of Siemens J-Y(st)Y) are cut at the end of the shield.
30 (36), 0-004-7771-2 (GB) T AC AB, 2003-07-01 T AC Xenta 400 I/O modules 4 Installation T A C Xenta 400 I/O modules Terminals type X: Min. cross-sectional area ................................................... 0 .25 mm² Max. cable length .........
TAC AB, 2003-07-01 0-004-7771-2 (GB), 31 (36) TAC Xenta 400 I/O modules Index Index A Analog Input and Output module 18 Analog Input module 20 Analog Output module 21 B B1–B4 19 C C1 and C2 28 cabin.
32 (36), 0-004-7771-2 (GB) TAC AB, 2003-07-01 TAC Xenta 400 I/O modules Index.
Y ou can help to make this manual even better! Please help us to make our documentation as good as possible. Use this form to let us know of any errors, unclear descriptions or to suggest improvements. Send the form to: Or e-mail it to: T AC AB helpdesk@tac.
T A C AB, 2003-07-01 T A C Xenta 400 I/O modules Reply form.
.
T AC AB, J ägershillgatan 18, SE-213 75 MALMÖ, SWEDEN, +46 40 38 68 50 (s witchboard), www .tac.com.
デバイスSchneider Electric 400の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Schneider Electric 400をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSchneider Electric 400の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Schneider Electric 400の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Schneider Electric 400で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Schneider Electric 400を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSchneider Electric 400の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Schneider Electric 400に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSchneider Electric 400デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。