1 Smart-UPS ® RT Uninterrupti ble Power Su pply SURTD 300 0/5000 VA 2 00-240 VAC Tower/Ra ck-Mount 3U Engli sh 2010 APC by Sch neider E lectri c . APC, the APC logo, Smart - UPS a nd PowerChu te are owned b y Schneid er Electr i c Indus tries S.A.
2 Introduction The A PC ® by Schneider Electric Sm art-UPS ® RT is a high-performance, uninterruptible po wer supply (UPS) that provides protecti on for elect ron ic equipment from utility power blackouts , brownouts, sags a nd sur ges.
3 Wiring and Connecting the UPS 5000 VA XLI MO D E LS O NLY : H ARDWIRING I NSTRUCTIONS • Wiring must be perform ed by a qualif ied electrician. • Install a high magnetic 30/32 A utility circuit breaker. • Adhere to all national and local electrical codes.
4 C ONNECTING THE B ATTERY MODULE S AND A TTACHING THE F RONT B EZEL .
5 B ASIC C ONNE CTORS serial com The serial connector is to be u sed for interf acing with APC Po werChute software and terminal emulation software. Use only cables appro v ed by APC. Any other interface cable will be incompatible with the UPS connector.
6 C ONNECTING E QUIPMENT AND P OWER TO THE UPS 1. Connect equ ipment to the UPS (cables not included for XLJ/XLT/XLTW models). 2. Avoid using exte nsion cords. • 3000 VA XLJ/ XLT/XLI/XL TW and 5000 VA XL J/XLT/XLTW models : Using a po wer cord, plug the UPS into a two- pole, thr ee-wire, grounded receptacle only .
7 O PERA TION Load S MART -U PS RT F RONT D ISPLAY Battery Charge Indicator Description Online The Online LED il luminates when th e UPS is drawing utility powe r and performing double con version to supply power to con nected equipment. On Battery The UPS is supplying battery po wer to the conn ected equipment.
8 Feature Function Cold Start When there is no utility po w er and the UP S is o f f, press and hold the button to power up th e UPS and connected equipment.
9 U SER C ONFIGU RA BLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW E R C HUTE SOFTW ARE , OPTIONAL S MA RT S LO T ACCESSO RY CARDS , OR T ERMINAL M ODE .
10 N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW E R C HUTE SOFTW ARE , OPTIONAL S MA RT S LO T ACCESSO RY CARDS , OR T ERMINAL M ODE . F UNCTION F ACTORY D EFAULT U SER S EL ECTABLE C HOICES D ESC.
11 C ONNECTING THE EPO (E MERGENCY P OWER O FF ) O PTI ON The output pow er can be disabled in an emergen cy b y closing a switch connected to the EPO. Adhere to National and local electrical codes wh en wiring the EPO. The EPO switch is intern ally po w ered by the UPS for use with n on-po wered switch circuit breakers.
12 T ERMI NAL M OD E TO C ONFIGURE UPS P ARAM ETERS 3000 VA m odels: Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wi shing to use P o werChute ® soft ware o r an op tiona l Net wor k M ana geme nt Card .
13 5000 VA m odels: Terminal Mode is a menu driven interface that enables configuration of the UPS by users not us ing PowerChute software or the installed Net work Management Card interfaces. Connect the serial cable to the serial port on the back of th e UP S.
14 • Press 2 and ENTE R to change the Battery Settings. • Type in the number of external battery packs (four batt ery modules per pack), and press E NTE R. (Num ber of packs: 1 = 1 S URT192XLBP, 2 = 2 SURT192XL BP etc.) • Press 3 and ENTER to accept the changes.
15 M AIN T E N AN C E AN D T RA NSPOR T Replacing the Battery Module This UPS has an easy to replace, h ot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipm ent on during the procedure.
16 R EPLACIN G B ATTERY MODULES X Y Z [ ] ^ _ Disconnecting the Battery for Transport Alway s DISCONNEC T THE BATT ERY(s) befo re shipping in co mpliance with U.S. Departm ent of Transportation (DOT) and I ATA regulations. The battery(s) m ay remain in the UPS.
17 T ROUBLESHOOTING , S ER VICE , AN D W A RRA NTY I NFORMA T ION Use the table below to solve minor installation and op e ratio n problems. Refer to the APC We b site, www.apc.com for assistan ce with complex UPS problems. P ROBLEM AND P OSSI BLE C AUSE S OLUTION UPS WILL NOT TURN ON Batt ery not conn ected p roper ly.
18 P ROBLEM AND P OSSI BLE C AUSE S OLUTION BYPASS LED ILLUM INATE S The bypass swi tch h as been turne d on m anually or throu gh an acce ssory . If bypa ss is t he c hosen mode of opera tion, i gnor e the illumin ated LED.
19 Service If the UPS requires service do not return it to the dealer. Follow these s teps: 1. Revi e w the problem s discussed in t he Troubles hooting section of this manual to eliminate common problem s. 2. If th e problem persi sts, contact APC Customer Support t hrough the APC Web site, www.
20 R A DIO F REQUENCY W ARNINGS This e quipm ent ha s bee n teste d and found to com ply with the limits for a Clas s A dig ital device , purs uant to part 15 of the FCC Ru les. Th es e limi ts ar e desi gn ed t o provid e reason able p rotect ion ag ain st har m ful in t erferenc e when t he eq ui pment is oper ated in a comme rcial enviro nmen t.
デバイスSchneider Electric SURTD 3000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Schneider Electric SURTD 3000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSchneider Electric SURTD 3000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Schneider Electric SURTD 3000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Schneider Electric SURTD 3000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Schneider Electric SURTD 3000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSchneider Electric SURTD 3000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Schneider Electric SURTD 3000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSchneider Electric SURTD 3000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。