TS2000 Installation & User Guide Compatible Equipment CPA6 OM - Output Module 9040 - Loudspeaker DC54/58 - Digital Communicators 496529 Issue A 1 of 20 TS2000.
OVERVIEW Introduction The Intruder Alarm Control System TS2000 is provided for large domestic and general commercial intruder systems conforming to BS 4737 part 1 1986. It is an extremely versatile system with the following facilities: 1. Will monitor up to 128 zones using various types of detector device; 2.
Additional Equipments Ward Control Unit (WCU) : When fitted the WCU will allow a group of circuits, which are designated a Ward, to be Set and Unset using Exit and Entry routes separate from the system. The WCU is connected to the outputs and circuits of a REM or a NU and will require a separate 12V supply.
Schematic Block Diagram TS2000 4 of 20 496529 Issue A TS2000 WARD CONTROL UNIT* REMO TE POWER SUPPL Y UNIT* NODE OR REMO TE KEYP AD No 32 (MAX) NODE OR REMO TE KEYP AD No X NODE OR REMO TE KEYP AD No .
TS2000 System Options - Schematic 496529 Issue A 5 of 20 TS2000 TS2000 SIB* PIB* PSU DC3(M)* OR D 3* CPM A I NB O A R D 8 Programmable output s DC 28 Digi com PSTN Line Centr al Stati on Mai ns I np ut To P S T N To P S T N Approved Mode m P. C . To S e r i a l Pr i n t e r * 8O u t p u t s * 8O u t p u t s * CP A6.
Equipment System Specification Supply Voltage: 240V + or - 10% 30W 50 Hz Battery: 12V 6Ah Zones: 128 maximum Outputs: 128 remote 8 local maximum Unit Dimensions: CP L 395 x W 280 x D 100mm (boxed) NU/WCU L 145 x W 85 x D 50mm REM L 220 x W 145 x D 40mm Unit Weights: CP 4 kg NU/WCU 220 g REM 430 g Environment: 0 - 40 ° C 95% RH n.
Node Unit (NU) The NU comprises a small two part polycarbonate case containing a single pcb on which are terminal blocks. The unit is connected to the control network and is a control and connecting device for four circuits and four programmable outputs.
TS2000 TS2000 8 of 20 496529 Issue A Connect to Control Networ k See Fig 6 . For Mimic . Connect to CP A6. OM module. For S A B Tamp er . Link t o 0V if not us ed Relay contacts are shown in the de-energis ed state. Alarm rela y is norm ally energised and i s de-energi sed at alar m.
TS2000 496529 Issue A 9 of 20 TS2000 Use for Networ k power to NU and REM only Cable 6 or 8 core 7/ 0.2mm Maximum length 100m between each unit. Using 8 co re cable will allo w the Netw ork power suppli es to be kept s eparate. NO TE It is essenti al that the connector s shown are correct and that no cross- overs occur.
TS2000 TS2000 10 of 20 496529 Issue A OUT D OUT C OUT B OUT A I/P C + I/P A + I/P B + I/P D + 0V +12V DIRECT ION - DIRECT ION + DA TA UP - DA TA UP + DA TA DOWN - DA TA DOWN + Connect t o CP (Fi g 4) .
TS2000 496529 Issue A 11 of 20 TS2000 Settle RV SPKR ACCESS OUT LX OUT WARD CONTROL 0V +12V WARD SET WARD EXI T SET F AIL WARD ALA RM To nc contacts of Access device* To nc contacts of Las t E xi t d .
TS2000 TS2000 12 of 20 496529 Issue A 4k7 Tam p e r S w Detector Sw Next PIR or Det EOL Res 2k2 Exit T erm inator n.c . (Or n.o.) C ontacts For n . o co n ta ct s s e t Inverted Attribute 4k7 2k2 E.
TS2000 Key Functions Engineer Reset 1. Enter your engineer’s code default 1234, you are now in Engineer’s Mode 2. Press 0 in quit to unset. Loading Defaults 1. Power down panel battery and mains, close LK2 2. Power up panel battery and mains 3. Enter 1234 and open LK2 4.
Define Circuit Text TS2000 TS2000 14 of 20 496529 Issue A STEP ACTION DISPLAY REMARKS 1 NO* Press < YES > to DEFINE CIRCUIT TEXT Press YES to Define Circuit Text from the dictionary. Press NO to go to to Install DC3 menu. Press 0 to quit 2 YES CCT > 001 000 000 000 Press YES to accept displayed data.
TS2000 Dictionary TS2000 496529 Issue A 15 of 20 TS2000 001 A 056 CEILING 111 ENTRANCE 002 ABOVE 057 CELL 112 ENTRY 003 ACCESS 058 CELLAR 113 EQUIPMENT 004 ACCOUNTS 059 CENTRAL 114 ESCAPE 005 ADMIN 06.
TS2000 Dictionary Cont’d TS2000 TS2000 16 of 20 496529 Issue A 164 INFRA-RED 217 METER 271 PORCH 165 INSIDE 218 MEZZANINE 272 POST 166 INSTRUCTORS 219 MICROWAVE 273 POWER 167 INTERIOR 220 MIDDLE 274.
TS2000 Dictionary Cont’d TS2000 496529 Issue A 17 of 20 TS2000 325 SITE 381 TRAP 431 11 326 SITTING 382 T.V. 432 12 327 SLIDING 383 TWIN 433 13 328 SMOKE 384 TYPE 434 14 329 SOFTWARE 385 TYPING 435 .
TS2000 Programmable Ouputs The programmable outputs from the NU and the REM, are referred to as the Node Outputs and are activated in response to various conditions or events. They are programmed to respond to System, Ward or Circuit activation. Panel outputs are from the CP and are programmed in the same way as the Node outputs.
TS2000 496529 Issue A 19 of 20 TS2000 Menu No Menu Passcode Level 1 Start Set Sequence 1, 2, 3, 4, 5, 6 User 2 Unset Wards 1, 2, 3, 4, 5, 6 3 View Circuits 1, 2, 3, 4, 5, 6 4 View Event Log 1, 2, 3 5 .
TS2000 20 of 20 496529 Issue A TS2000 This page intentionally left blank.
デバイスSecurity Centres TS2000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Security Centres TS2000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSecurity Centres TS2000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Security Centres TS2000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Security Centres TS2000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Security Centres TS2000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSecurity Centres TS2000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Security Centres TS2000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSecurity Centres TS2000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。