MODEL 3100-XX FLAME DETECTOR.
Sierra Monitor Corporation 1991 T arob Court, Milpitas, CA 95035 (408) 262-661 1, T oll Free: 800-727-4377 Fax: 408-262-9042 MODEL 3100-XX Flame Detector APPLICABILITY & EFFECTIVITY This manual pr.
Instruction Manual T able of Contents TABLE OF CONTENTS SECTION PAGE 1 . PRODUCT DESCRIPTION 1 2 . OPERA TION 2 2.1 General 2 2.2 Field-of-V iew 3 2.3 Range 3 2.4 Environment 3 2.5 Configuration 3 2.6 LED operation 4 2.7 Relay operation 5 3 . INST ALLA TION 7 3.
Model 3100 Series Flame Detector (1 1/04) Page: 1 Instruction Manual FIGURE 1-1: Model 3100 Series Flame Detector 1. PRODUCT DESCRIPTION 1.1 Introduction All versions of the Model 3100 Flame Detector Se- ries utilize Ultraviolet, Infrared and V isible spectrum to provide continuous and reliable flame detection.
Instruction Manual Page: 2 Model 3100 Series Flame Detector (1 1/04) 2 . OPERA TION 2. 1 General When the Model 3100 Flame Detector is powered up, the microprocessor checks the configuration switch settings and configures the detector . The mi- croprocessor then runs a full series of self tests.
Model 3100 Series Flame Detector (1 1/04) Page: 3 Instruction Manual 2.2 Field-of-V iew (See Figur e 2-1) Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de- tectors ability to cover the threat area.
Instruction Manual Page: 4 Model 3100 Series Flame Detector (1 1/04) LED 1 LED 2 Mounting Screw (2 locations) Configuration Switches 2.5.2 V erify Control The Enhanced Model 3100-02, -03, -04, - 05 and -06 have the V erified Fire function.
Model 3100 Series Flame Detector (1 1/04) Page: 5 Instruction Manual (“on” or “off”) of a switch (SW1-SW8). The first flash pattern indicates the position of the first switch (SW1), with each consecu- tive flash indicating the position of the next switch in order .
Instruction Manual Page: 6 Model 3100 Series Flame Detector (1 1/04) ing” - remain energized until power is re- moved, ”Fire Following” - de-energize a short time after the fire is no longer detected. The “J2” connector provides connections for both normally open contacts and normally closed contacts on the Fire Relay .
Model 3100 Series Flame Detector (1 1/04) Page: 7 Instruction Manual 3. 0 INST ALLA TION 3.1 General Precautions All wiring and installation must be done in accor- dance with the NFP A 70 and 72 standards and must comply with any codes specific to the application or location.
Instruction Manual Page: 8 Model 3100 Series Flame Detector (1 1/04) 3.3.5 Auxiliary Relay The Auxiliary Relay connector is located be- tween the Power and Fire Relay connectors. The connection points are labeled “Aux In” and “Aux Out”. The Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 9 Instruction Manual 5 . 0 TROUBLESHOOTING The flame detector has several built-in self test mechanisms which verify function and calibration. The following procedure covers most faults and problems which may occur during installation or during the course of normal operation.
Instruction Manual Page: 10 Model 3100 Series Flame Detector (1 1/04) 1. If the relay closes (0 ohms on the meter) and the LEDs come “on” the detector is operating normally .
Model 3100 Series Flame Detector (1 1/04) Page: 11 Instruction Manual 6 .0 SPECIFICA TIONS SIERRA MONITOR CORPORA TION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment.
Instruction Manual Page: 12 Model 3100 Series Flame Detector (1 1/04) Figure A-2: Model 3100 Series Dimensions Figure A-1: Model 3100 Series Exploded V iew APPENDIX A.
Model 3100 Series Flame Detector (1 1/04) Page: 13 Instruction Manual Figure A-3: Model 3100 Series Common W iring Connections.
Instruction Manual Page: 14 Model 3100 Series Flame Detector (1 1/04) Figure A-4: Model 3100 Series (Enhanced) W iring Connections Factory jumpers are used to set NC or NO connections.
Model 3100 Series Flame Detector (1 1/04) Page: 15 Instruction Manual APPENDIX B T ABLES B.1 Dip Switch Settings B.1.1 Sensitivity Sensitivity SW1 SW2 Level 20 Foot O N O N 4 40 Foot OF F O N 3 60 Foot O N OF F 2 80 Foot OF F OF F 1 B.
Instruction Manual Page: 16 Model 3100 Series Flame Detector (1 1/04) B.2 Connectors B.2.1 Fire Relay Connector (J2) Fire Relay Description Pin 1 (Left Most) & Pin 2 Normally Open Side of Relay Pin 3 & Pin 4 (Middle) Common or Center Side of Relay Pin 5 & Pin 6 (Right Most) Normally Closed Side of Relay B.
Model 3100 Series Flame Detector (1 1/04) Page: 17 Instruction Manual B.3 V erify/Aux. Relay Configurations Model # V erify Relay Aux. Relay 3100-02 Open Contacts Closed Contacts 3100-03 Closed Contac ts Open Contacts 3100-04 Open Contacts Open Contacts 3100-05 Closed Contact Closed Contacts B.
Instruction Manual Page: 18 Model 3100 Series Flame Detector (1 1/04) B.7 Detector Response to Fuels T able Fuel Distance Fire Size Response T ime Heptane 80 Feet 1 Square Foot Less than 3 sec. Silane 5 0 Feet 18 inch jet Less than 3 sec. Hydrogen 15 Feet 18 inch jet Less than 5 sec.
Model 3100 Series Flame Detector (1 1/04) Page: 19 Instruction Manual APPENDIX C -- WIRING CONNECTIONS.
Instruction Manual Page: 20 Model 3100 Series Flame Detector (1 1/04) Index A Alarm Mode 2, 4 V erified 2 Auxiliary Relay 1, 2, 5, 6, 7 C Cleaning 8 Conduit 7, 11 Configuration Relay Control 4 Sensitivity 3 Switches 3, 4 V erify Control 4 Configuration Switches 5 Connection 7 Connector Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 21 Instruction Manual T T esting 8 U Ultraviolet 3 V V erified Fire 2, 4, 5, 6 V erify Control 4 Relay 2, 4, 5, 6, 7, 15 V erify Control 6, 15 V ersions.
デバイスSierra Monitor Corporation 3100-01の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Sierra Monitor Corporation 3100-01をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSierra Monitor Corporation 3100-01の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Sierra Monitor Corporation 3100-01の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Sierra Monitor Corporation 3100-01で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Sierra Monitor Corporation 3100-01を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSierra Monitor Corporation 3100-01の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Sierra Monitor Corporation 3100-01に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSierra Monitor Corporation 3100-01デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。