1 of 18 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Comm unications Adapter enables an HGM300 Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network.
2 of 18 front side of the door. Position the adap ter board over the s tandoffs mounted on the HGM door. Install the five remaining 6- 32 screws through the board and into the standoffs and tighten. Connect power wiring from the HGM300’s 120V Auxiliary Power term inal block to the adapter board’s POWER terminal block.
3 of 18 If an RDM800 remote display IS to be used w ith the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cables must be run betw een the HGM300 and RDM800, so plan accordingly.
4 of 18.
5 of 18 Setting HGM Communication Address On Adapter See Figure 4 for the location of adapter dipswitch ‘A’. Switches 5-8 on the adapter’s ‘A ’ dipswitch are used to matc h the node address set on the HGM’s address dipswitch (on HGM main boa rd).
6 of 18.
7 of 18 Configuring the HGM300 with RDM800 or Laptop PC The only HGM parameters that are cha ngeable through LonWorks are the alarm thresholds. Configuring the HGM for refriger ant type and length of tubing for each zone (zero length to disable a zone ) must be done with the RDM800 remote display or a laptop PC.
8 of 18 HGM Alarm Acknowledge Options Two alarm acknowledge options are s upported—Auto Acknowledge and Network Acknowledge. In the Auto Acknowledge mode, the HGM will clear its alarm outputs the next tim e the alarmed zone is sampled and its PP M has dropped below the alarm thresholds.
9 of 18 LonWorks Objects and Network Variables The adapter contains one Node Object, sixteen Zone Objects, one Ge neral Status Object, and one Alarm Control Object.
10 of 18 Network output variable nvoStatus returns the information requested by nviRequest. The status response will indicate the status of the object that received the request. The status bits supported are list ed above under RQ_REPORT_MASK. One nvoStatus response will be returned for each nviRequest.
11 of 18 Objects 1-16 – Zone Objects There is one Zone Object for each sampling zone in the HGM300 (16 total): Network output variable nvoHgmZonePPM shows the m easured gas concentration for a particular zone.
12 of 18 CRITICAL FAULT Some critical fault pr events normal zone PPM m easurement. (View nvoHgmFaults for details on fault type) HGM BUSY Occurs with RDM800 insta lled when certain scr eens are displayed. COMM FAULT 1 Comm failure between HGM and adapter.
13 of 18 Object 17 – General Status Objec t The General Status Object provides info rmation about any HGM300 internal faults present and shows which zone is currently being sampled: Network output variable nvoHgmFaultAlert reports whenever ANY fault is detected within the HGM or adapter.
14 of 18 HGM Busy (if RDM800 attached a nd showing certain screens)(bit 4) Comm Fault 1 (communications fail ed between HGM and adapter)(bit 3) Comm Fault 2 (internal communicati ons failed within ada.
15 of 18 Object 18 – Alarm Control Object The Alarm Control Object provides information about any alarm s which are present in the HGM. It also provides mechanisms fo r acknowledging alarm s, and fo.
16 of 18 Network input variable nviSetZoneThresh allows Leak, Spill, and Eva cuate alarm thresholds (in PPM) to be set for each m onitoring zone. nviSetZoneThresh has four parameters to be set by the .
17 of 18 Network output variable nvoHgmZoneThresh displays the following in formation for the zone specified by nviGetZoneThresh: 1. Zone (1-16) whose alarm th resholds are being displayed 2. Leak Alarm Threshold in PPM (0-65535) 3. Spill Alarm Threshold in PPM (0-65535) 4.
18 of 18 LED 1 and LED 2 will normally show activ ity about every 15 seconds. Since the refrigerant monitoring process is fairly slow and new data is only available every 15 seconds or so, the adapter po lls the HGM at a slow rate to reduce the com munications burden on the HGM main processor.
デバイスBacharach LonWorks FT-10の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bacharach LonWorks FT-10をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBacharach LonWorks FT-10の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bacharach LonWorks FT-10の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bacharach LonWorks FT-10で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bacharach LonWorks FT-10を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBacharach LonWorks FT-10の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bacharach LonWorks FT-10に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBacharach LonWorks FT-10デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。