State IndustriesメーカーGFK-0827の使用説明書/サービス説明書
ページ先へ移動 of 103
GE F anuc Automation Programmable Control Pr oducts Series 90 -70 Hot Standby CPU Redundancy User’s Guide GFK -0827 December 1993.
GFL–002 W arnings, Cautions, and Notes as Used in this P ublication W ar ning W arning notices are used in this publication to emphasize that hazardous voltages, currents, temperatures, or other conditions that could cause personal injury exist in this equipment or may be associated with its use.
iii GFK-0827 Pr eface This manual is a reference to the hardware components, configuration and operation of the Hot Standby CPU Redundancy system for the Series 90 -70 Programmable Logic Controller .
Pr eface iv Hot Standby CPU Redundancy User ’ s Manual - December 1993 GFK-0827 Series 90-70 PLC R eference Manual (GFK -0265). Reference manual which describes operation, fault handling, and Logicmaster 90-70 programming instructions for the Series 90-70 PLC.
Contents v GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 Chapter 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hot Standby CPU Redundancy Product 1 .
Contents vi GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 Chapter 2 System Components 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Redundancy CPU 13 . . . . . . . . . . . . .
Contents vii GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 Chapter 3 Configuration 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuring a Hot Standby CPU Redundancy System 27 .
Contents viii GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 Chapter 4 Operation 55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 1: System Operation 55 .
Contents ix GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 Section 2: F ault Detection and Contr ol A ctions 72 . . . . . . . . . . . . . . . F ault Detection 72 . . . . . . . . . . . . . . . . . . . . . . . . .
Contents x GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 F igure 1. Example of a Local I/O Configuration with Expansion Racks in a Hot Standby CPU Redundancy System 5 . . . . . . . . . . . . . . . . . . . . . .
Contents xi GFK–0827 Series 90–70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 T able 1. Capacities for Redundancy CPU, IC697CPU780 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T able 2. V alid Operating Mode Selection 16 .
1 section level 1 1 figure bi level 1 table_big level 1 restart lowapp ARestart oddapp: ARestarts for autonumbers that do not restart in each chapter .
1 2 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 contains all redundant Genius Bus Controllers at Serial Bus Address 31; the Secondary PLC contains all redundant Genius Bus Controllers at Serial Bus Address 30.
1 3 GFK-0827 Chapter 1 Introduction F eatures of the Hot Standby CPU Redundancy Product Bumpless switching Synchronized CPUs 20 millisecond scan e xtension (nominal).
1 4 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 I/O Systems for Hot Standby CPU Redundancy Systems Both Series 90-70 Local I/O and Genius I/O systems can be present in a Hot Standby CPU Redundancy control system.
1 5 GFK-0827 Chapter 1 Introduction Y Y C B T M R C M G B C 31 PRIMARY UNIT SECONDARY UNIT 30 B L O C K B L O C K S C A N N E R REMOTE DROP I O I O I O I O I O I O P S I O I O P S P S B T M G B C B L .
1 6 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 for three consecutive Genius I/O bus scans, the outputs are then controlled by the Genius Bus Controller at serial bus address 30 (Genius Bus Controller in the Secondary PLC).
1 7 GFK-0827 Chapter 1 Introduction Redundancy CPU Module The same model of CPU must be installed in both the Primar y and Secondar y PLCs. This CPU, which is the only CPU that currently supports synchronized Hot Standby CPU redundancy , is the CPU 780 (catalog number IC697CPU780).
1 8 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 the two CPUs and provides the communications path for the transfer of I/O data between the two units. An RCM must be configured in both the Primar y PLC and the Secondar y PLC.
1 9 GFK-0827 Chapter 1 Introduction If the switch occurs due to a controlled condition such as toggling the unit selection switch on the Redundancy Communications Module or forcing a switch in the user logic program with a SVC_REQ, or because of a fault detected by the PLC CPU, then the switch- over will occur at the beginning of the ne xt sweep.
1 10 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Programming Considerations There are several features in the operation of the Redundancy CPU which are not supported or are different then operation of other CPUs.
1 11 GFK-0827 Chapter 1 Introduction The Primary Unit and the Secondary Unit must be configured separately . That is, the programming device should be connected directly to either the Primar y or the Secondar y Unit to configure that unit.
1 12 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Commonly Used Acronyms A list of acronyms used in this manual are defined for your convenience in the following table.
2 section level 1 1 figure bi level 1 table_big level 1 13 GFK-0827 Chapter 2 System Components This chapter describes the hardware components for a Hot Standby CPU Redundancy system. It describes the modules required for the system and provides catalog numbers of the components.
2 14 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 C P U C P U B T M R C M G B C 31 PRIMAR Y UNIT SECONDAR Y UNIT 30 P S P S B T M R C M G B C Genius Bus CPU 780 Redundancy Communications Link Redundancy Communications Link a47002 Figure 3.
2 15 GFK-0827 Chapter 2 System Components timer is 10 milliseconds to 1000 milliseconds. The default value for the watchdog timer is 200 milliseconds. The watchdog timer resets at the beginning of each sweep. The fail wait time is included in the watchdog check.
2 16 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 CPU Mode Switch A three-position toggle switch is mounted near the top of the CPU board. This switch selects one of three operating modes for the CPU: RUN/ENABLED, RUN/DISABLED , or STOP .
2 17 GFK-0827 Chapter 2 System Components Memor y Protect K eyswitch The Memor y Protect k eyswitch is located at the top of the module and has two positions: ON and OFF .
2 18 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Serial Port Connector The 15-pin D -connector at the bottom of the module provides the connection to an RS-422/RS-485 serial port. Its port provides a serial connection to the W ork Station Inter face (WSI) board installed in the programming computer .
2 19 GFK-0827 Chapter 2 System Components Redundancy Communications Module The Re dundancy Communi c at i ons Mod ule (RCM), catal og numbe r IC 697RCM711, prov i des a communic a tions path for sh aring data betwe e n th e two CPUs in th e re dundant sys te m.
2 20 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 C B T M R C M 31 PRIMARY UNIT SECONDARY UNIT 30 P S P S B T M R C M Redundancy Communications Link Redundancy Communications Link G B C G B C P U C P U ( RACK 0 ) ( RACK 0 ) a47005 Figure 6.
2 21 GFK-0827 Chapter 2 System Components L OC AL SYSTEM ACTIVE Indicates whether the local unit is the controlling (or active) unit in a redundancy system.
2 22 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Bus T ransmitter Module A Bus T ransmitter Module (BTM), catalog number IC697BEM713, is required in both the P rimar y PLC CPU rack (rack 0) and the Secondary PLC CPU rack (rack 0) in a Hot Standby CPU Redundancy system.
2 23 GFK-0827 Chapter 2 System Components BTM Connectors The re are two conn e ctors on the front of th e BTM board. Th e top one provi des a parall e l c onnec ti on t o a W or k S tat i on I nterf ac e (WS I) boa rd ins ta l l ed in t he pr og ra mmer f or the Series 90-70 PLC .
2 24 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 I/O Bus Signal T ermination The I/O bus signals must be ter minated at the end of the bus.
2 25 GFK-0827 Chapter 2 System Components The Ho t St andby CPU Re dundancy system uses a si ngle Ge n ius bus and re qui res one GB C modul e in th e Pr i mar y PLC and one in the Se con dary PLC ; ho we ve r there can be multi ple Gen ius busses configured in th is man ne r in a system.
2 26 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 CH 1 OK The CH 1 OK LED is th e midd le LED. It ope rate s ide n tic al to th e Modul e OK LED in that it is ON.
3 section level 1 1 figure bi level 1 table_big level 1 27 GFK-0827 Chapter 3 Configuration This chapter describes how to configure a Series 90-70 PLC system for Hot Standby CPU Redundancy . Several parameters in addition to the normally configured CPU parameters must be configured for the Redundancy CPU 780.
3 28 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Redundancy System R equirements F or a redundant CPU configuration using the Hot-Standby Redundancy scheme to be valid, the following requirements must be true in both the Primary Unit and the Secondar y Unit in the redundancy system.
3 29 GFK-0827 Chapter 3 Configuration Screens for F ault Categor y Configuration A new F ault Category Configuration screen is displayed for the CPU 780.
3 30 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 The F ault T ype is shown at the left. The first column under F ault Categor y (CFG) shows which faults are FA T AL and which faults are DIA GNOSTIC for this CPU, when it is the only running CPU (i.
3 31 GFK-0827 Chapter 3 Configuration cable connecting the PLC to the programmer should only be plugged and unplugged when the programmer is powered up and offline.
3 32 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 The detail screen of the cur rently configured CPU module is displayed. The following screen shows the CPU module detail screen for the currently displayed module.
3 33 GFK-0827 Chapter 3 Configuration If the e xisting configuration does not require any modification to suit the redundant CPU configuration, the prompt ”REPLA CE displayed module ? (Y/N)” will be displayed beneath the softkey strip instead of the message bo x.
3 34 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 3. In a redundant CPU system, RCMs cannot be configured in expansion racks. 4. Rack 7 cannot be seen nor edited. Redund T ype This parameter specifies whether the CPU is configured as the primar y controller or the secondar y controller .
3 35 GFK-0827 Chapter 3 Configuration Constant Window Sweep Mode T o change the Sweep Mode, move the cursor to the Sweep Mode field and press the Ta b k ey until the desired mode is displayed. Below is the detail screen (page 2) of a redundant CPU configured for CNST WND (constant window) sweep mode.
3 36 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 set for SIMPLEX mode. The parameters on this screen are Ctrl Strgy (Control Strategy), F ail W ait and SHARED I/O . Ctrl Strgy This parameter specifies which type of control strategy is selected for a redundancy system.
3 37 GFK-0827 Chapter 3 Configuration T able 4. Shared I/O Data Parameters I/O P arameter Description and V alid Entries %I Ref Adr Starting address for redundant %I data region. Range is %I00001...%I12288. The starting address is bit aligned. Default value is %I00001.
3 38 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Note that the memor y for the Shared I/O data that is stored at configuration must be subtracted from the amount of memory on the configured expansion memory module.
3 39 GFK-0827 Chapter 3 Configuration Configuring a CPU Expansion Memor y Board T o configure a CPU e xpansion memory board for the CPU 780, press the expbd softkey (F9) and then the memory softkey (F1). P osition the cursor on the desired expansion memor y board and press Enter to select that board.
3 40 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Configuration of a Redundancy Communications Module As described previously , one Redundancy Communications Module (the Local unit) must be configured in rack 0 (can be in slots 2 to 9).
3 41 GFK-0827 Chapter 3 Configuration T o display the RCM catalog list, press the rcm softk ey (F3). The RCM catalog list is then displayed as shown below . Next, press the Enter key , the following screen is displayed to confir m that you have selected the RCM catalog entry .
3 42 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Configuration of a Genius Bus Controller F or this example, assume that a Genius Bus Controller has been configured in slot 3 of rack 0.
3 43 GFK-0827 Chapter 3 Configuration Serial Bus Address All redundant GB Cs in the Primar y CPU redundant system MUST be configured at SBA 31. In the sample screen on the previous page, the rack level GBC is configured at SBA 31. The Bus level GB C is automatically configured at SBA 30.
3 44 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Configuring a Primar y R edundant PLC The steps required for configuring a Primar y Redundant PLC are described below . The P rimar y PLC and the Secondary PLC must be configured separately .
3 45 GFK-0827 Chapter 3 Configuration Select the R edundancy CPU Module Move the cursor to the line for the Redundant CPU, IC697CPU 780, and press the Enter k ey . A message is displayed beneath the softkey selection strip: ”REPLA CE displayed module ? (Y/N)”.
3 46 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 P ress the PgDn key again to go to the next page of the CPU module.
3 47 GFK-0827 Chapter 3 Configuration P ress the Esc k ey twice to retur n to the rack level display , which now appears as shown below . Configure the R edundant Communications Module T o configure an RCM in rack 0, slot 2, move the cursor to slot 2 and press the bem softk ey (F3).
3 48 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Configure a Genius Bus Controller T o configure a Genius Bus Controller module in rack 0, slot 3, position the cursor on slot 3 and press the genius softkey (F2).
3 49 GFK-0827 Chapter 3 Configuration P ress the Esc key to retur n to the rack level screen. F rom the rack level screen press the zoom softkey (F10). The following bus level screen is displayed: T o view the Genius Bus Controller (block level) at SBA 30, position the cursor on BUS ADR 30 and press the zoom softk ey .
3 50 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 A t this point, Press the Esc k ey and the bus screen will appear as shown below . Configure Genius I/O Blocks W e will now configure a block for Bus A ddress 29.
3 51 GFK-0827 Chapter 3 Configuration When you have completed configuring Genius blocks, press the Esc key to go from the block level display back to the bus level display . The bus display will now appear as shown below . Configure the Bus T ransmitter Module P ress the Esc k ey to retur n to the rack level display .
3 52 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Configuring a Secondar y R edundant PLC This section describes the steps for configuration of a Secondar y PLC. The programmer for Logicmaster 90-70 software must be connected to the Secondary PLC in order to configure the Secondar y PLC.
3 53 GFK-0827 Chapter 3 Configuration P osition the cursor on rack 0, slot 1. Press the zoom softk ey (F10) to zoom into the CPU module configured in slot 1.
3 54 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 P ress the Esc k ey twice to save the changes you have just made. This completes the process of converting a Primar y PLC redundancy system configuration to a Secondar y PLC redundancy system configuration.
4 section level 1 1 figure bi level 1 table_big level 1 55 GFK-0827 Chapter 4 Operation This chapter discusses: the normal operation of a Hot Standby CPU Redundancy PLC system; what happens when a fault is detected and the system does not operate normally; how to restore the system to normal operation; on-line repair procedures.
4 56 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 4. System Configuration verified. 5. System inter rogated and initialized. 6. P resence of other CPU detected and RCMs initialized. 7. Complete user program verification.
4 57 GFK-0827 Chapter 4 Operation Resynchronization of the Redundant CPU Whenever a CPU is attempting to get back in synchronization with the currently active CPU, a resynchronization process will occur . This resynchronization process will occur any time a CPU per for ms a STOP to RUN mode transition.
4 58 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Hot-Standby R edundancy Control Strategy In the Hot-Standby Redundancy Control Strategy , the primar y CPU (designated by all GB Cs addressed at bus address 31), is always the prefer red CPU.
4 59 GFK-0827 Chapter 4 Operation Synchronous Scan The figure below shows the sweep components for the active and the backup CPUs. It shows the two communication points in the sweep. The first communication point is immediately after the inputs are scanned.
4 60 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 The transfer of the redundancy data during each sweep will be in blocks with each block checked for data integrity . The transfer red data will be held in a temporar y area by the back up CPU until all data has been received and verified from the active unit.
4 61 GFK-0827 Chapter 4 Operation through %P0008 on the backup unit will not change. %T0002 will be set whenever the operation is successful and the data can be used.
4 62 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 If the switch occurs due to a controlled condition such as toggling the RCM unit selection switch, forcing a sw.
4 63 GFK-0827 Chapter 4 Operation %S References for CPU R edundancy There are seven special %S references which reflect the status of the Redundancy units: %S33 through %S39.
4 64 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Redundancy CPU Considerations The Redundancy CPU (CPU 780) has several restrictions and differences in operation as compared to other Series 90-70 CPUs.
4 65 GFK-0827 Chapter 4 Operation Differences in Operation for CPU 780 The following features operate differently with the CPU 780 than they do with other Series 90-70 CPUs: RUN/DISABLED mode Configur.
4 66 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 F ollowing are several examples that illustrate the above guidelines. Each e xample gives the role of each unit, its current operating mode, and the state of the LEDs on the RCMs.
4 67 GFK-0827 Chapter 4 Operation E. Role switches are allowed on both units. Primary Unit Secondar y Unit Backup A ctive (see NOTE below) RUN/ENABLED RUN/ENABLED XO K XO K X LOC_RDY X LOC_RDY LOC_A CT X LOC_A CT X REM_RD Y X REM_RD Y X REM_A CT REM_A CT F .
4 68 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Specific fault actions are described in Section 2 of this Chapter . However , you can configure whether or not a stand-alone CPU (after failure of the other CPU) will stop if another fault occurs.
4 69 GFK-0827 Chapter 4 Operation Background User Checksum and Background Window Timing Instructions The following infor mation is provided to allow you to guarantee full coverage of the number of program words verified by the User Program Checksum per sweep and the Background W indow Diagnostics within a certain amount of time.
4 70 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Where the Background W indow T ime is the time in milliseconds that you should set the background window timer . The other elements in the for mula are described above in the calculation for words per sweep.
4 71 GFK-0827 Chapter 4 Operation Genius Bus Controller Switching Genius Bus Controllers will stop sending outputs to blocks when no data has been received from the PLC CPU for a period equal to two times the configured watchdog timeout.
4 72 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 Section 6: F ault Detection and Control A ctions This section describes how faults are handled in a Redundancy system.
4 73 GFK-0827 Chapter 4 Operation 3. faults and failures that are detected in the background. F aults and failures that are detected immediately are those that are identified within the current sweep.
4 74 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 PLC Fault T able The following table lists fault zoom Help text and messages for er ror codes associated with the redundancy fault group.
4 75 GFK-0827 Chapter 4 Operation F aulting RCMs, L osing Links, and T erminating Communications There are distinct differences between losing a redundant communications link, faulting an RCM, and terminating communications. F aulting the RCM module occurs only when a hardware related failure occurs such as a parity error or VME bus er ror .
4 76 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 In this case, if the RCM is at fault, it will need to be replaced before power is restored. T er minating Communications occurs when the two units get out of synchronization.
4 77 GFK-0827 Chapter 4 Operation F ault Actions in a CPU R edundancy System F ault actions in the Hot Standby CPU Redundancy System are handled differently than those in a non-redundancy (Simplex) system.
4 78 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 T able 10. Maskable Fault Group Actions F ault A ction F ault Gr oup Simplex Mode R edundant Mode User Configur.
4 79 GFK-0827 Chapter 4 Operation T able 11. Non-Maskable F ault Group Descriptions F ault Gr oup T able T ype Description SYS_BUS_F AIL CPU System bus failure. NO_USER_PRG CPU No User ’s Program on P ower -up. BAD_USER_RAM CPU Corrupted User RAM detected on P ower -up.
4 80 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 On-Line Repair W ith a Hot Standby CPU Redundancy system most system component failures can be repaired by replacing the failed component while the system is on-line.
4 81 GFK-0827 Chapter 4 Operation Power Supply The power supply has adequate inter nal fault detection which will cause it to automatically shut down if there is a failure. In an orderly shut down, the power supply will first assert the A CF AIL signal before it asserts the SYSREST signal.
4 82 Series 90-70 Hot Standby CPU Redundancy User ’ s Guide – December 1993 GFK-0827 If an RCM fault is detected, proceed as follows: STOP the unit with the suspected bad RCM. T ur n power off at that rack. Unplug the ter minated cable from the RCM and replace the module.
4 83 GFK-0827 Chapter 4 Operation Genius Bus Genius bus faults are not fatal to the PLC. However , if a bus fault e xists, it exists for both systems. There may be situations where one controller can communicate to more blocks than the other controller can.
A section level 1 1 figure_ap level 1 table_ap level 1 85 GFK -0827 Appendix A Redundancy Alter natives Redundancy Alternatives There are several redundancy alternatives for the Series 90-70 Programmable Logic Controller .
A 86 Series 90-70 Hot Standby CPU Redundancy User ’s Guide - December 1993 GFK -0827 HOT ST ANDBY (2 CPUS) OPTIONS SINGLE BUS REDUNDANT BUS LOW COST LOWEST COST I/O COUNT >512 IN/512 OUT VME ISO/.
A GFK -0827 87 Appendix A Redundancy Alter natives T able 13. R edundancy Options Option Ke y PLC Scan Sync Data Sync I/O System Output Selection Method R edund.
A 88 Series 90-70 Hot Standby CPU Redundancy User ’s Guide - December 1993 GFK -0827 Series 90-70 Redundancy Through Application Logic The following restrictions apply using the cur rent Series 90-70 for redundancy applications requiring synchronization ( these restrictions do not apply to the Hot Standby CP U Redundancy product ).
Index 89 GFK-0827 A A cronyms, list of , 12 A ctive and back up sweeps, 59 A ctive unit, 2 , 4 , 7 , 8 , 9 , 16 , 19 , 20 , 21 , 25 , 57 , 58 , 59 , 60 , 61 , 65 , 68 , 71 , 72 , 77 , 78 , 80 Appendix.
Index 90 GFK-0827 Connecting Logicmaster 90, 31 Connector , serial port, 18 Connectors, batter y , 17 Considerations, programming, 10 Considerations, redundancy CPU, 64 Constant sweep mode configurati.
Index 91 GFK-0827 Genius bus, multiple, 26 Genius I/O , bus controller , 24 Genius I/O system, 4 Grounding, programmer , 9 Guidelines for r un disabled mode, 66 H Help text, redundancy error codes, 74.
Index 92 GFK-0827 Operation, differences for cpu 780, 65 Operation of a cpu redundancy system, 55 OVR_PRE %S reference, 70 P P arallel bus termination, 80 PID and T imer function blocks, 70 PLC fault .
Index 93 GFK-0827 S S (%), references, 7 Scan time, effect of bumpless switching, 8 Scan, synchronous, 59 Screens for fault category , 29 Secondar y unit, 25 Sequence, power -up, 55 Serial bus address.
デバイスState Industries GFK-0827の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
State Industries GFK-0827をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはState Industries GFK-0827の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。State Industries GFK-0827の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。State Industries GFK-0827で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
State Industries GFK-0827を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はState Industries GFK-0827の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、State Industries GFK-0827に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちState Industries GFK-0827デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。