State Water HeatersメーカーGPO 86-199の使用説明書/サービス説明書
ページ先へ移動 of 24
1 PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. PRINTED IN U.S.A. 0303 P ART NO.195092-000 COMMERCIAL OIL FIRED W A TER HEA TER FOR HOT W A TER SUPPL Y .
2 TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE USING APPLIANCE. This is a typical oil-fired heater for commercial water heating applications. The principal components of the heater are shown and identified here.
3 FEA TURES AND SPECIFICA TIONS ................................................... 2 APPROV ALS ....................................................................................... 3 IDENTIFICA TION Oil and Burner Nameplate Decal .................
4 OIL BURNER SPECIFICA TIONS The oil burner nameplate decal includes a series code which identifies the major features of the oil burner . The series number is the last three digits of the burner code number . T able 3 below describes the oil burner characteristics for each series number .
5 • The discharge opening of the relief valve should always be piped to an open drain. • Choose the point of major hot water usage, fuel supply and chimney . • Try to make hot water and oil piping as short as possible. • Insulate hot and cold water piping where heat loss and condensatio n may be a problem.
6 • When communicating with outdoors by means of vertical ducts, each opening shall have a free area of not less than one square inch per 4,000 Btu per hour (551 mm 2 /kW) (35 square inches per gallon of oil consumed per hour) of total input rating of all appliances in the enclosure.
7 MUL TIPLE HEA TER FLUES When two or more oil-fired water heaters are connected to a single chimney or vent there shall be sufficient draft available for safe combustion and removal of combustion products to the outdoors from each heater . Refer to local codes for connection details.
8 A TYPICAL HEA TER INST ALLA TION - FIGURE 9 Refer to pages 2, 3, and 4 in this manual for more information about burner series numbers and characteristics for adaptability to the following systems. SYSTEM TYPES Single Stage, Supply Line Only: The bottom of the oil storage tank must be above the level of the fuel unit, fig.
9 BURNER The burner assembly is mounted on the flange of the combustion chamber , fig. 13. NOTE: Be certain combustion chamber opening is aligned with opening in heater flange, fig. 13, before placing burner into heater . 1. Place the flange gasket and combustion chamber seal over the burner tube.
10 OPERA TION GENERAL Never operate the heater unless the tank is filled with water and a temperature and pressure relief valve is installed. FILLING 1. Oil burner electrical disconnect switch should be in the "OFF position 2. Close the heater drain valve.
11 DUAL-BULB THERMOST A T (COVER REMOVED) FIGURE 17 BURNER CERTIFICA TE (COMBUSTION TEST) The Commercial Standard CS75 Oil Burner Certificate form must be filled in and posted in the vicinity of the water heater . Instructions for filling in certificate are on the back of the certificate.
12 SEDIMENT REMOV AL W ater borne impurities consist of fine particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank. For convenience, sediment removal and lime scale removal should be performed at the same time.
13 • Observe interior through opening - a small flashlight may be used ef fectively . • If the interior still shows water scale, the deliming process should be continued. • T o check UN•LIME® for continued use or reuse, place some lime scale or white chalk into a glass with a small amount of the solution.
14 ONE TEMPERA TURE - ONE HEA TER VERTICAL STORAGE T ANK FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION SCALD PREVENTION HOT WA TER CAN SCALD IF USED CARELESSL Y OR IN UNANTICIPA T ED MANNER.
15 SINGLE TEMPERA TURE OR BOOSTER TWO TEMPERA TURE - ONE HEA TER HIGH TEMPERA TURE STORAGE WITH OR WITH OUT RECIRCULA TION RETURN LINE FROM 180°F (82.
16 TWO TEMPERA TURE - TWO HEA TERS HIGH TEMPERA TURE STORAGE WITH OR WITHOUT RECIRCULA TION * PIPE RELIEF V AL VE TO OPEN DRAIN NOTE: IF TEMPERED WA TER IS RECIRCULA TED, RETURN LINE SHOULD BE CONNECTED A T POINT "A" FOR MUL TIPLE HEA TER INST ALLA TION SEE MANIFOLD KIT SPECIFICA TIONS, P AGES 19.
17 TWO TEMPERA TURE - THREE HEA TERS (TWO PRE-HEA TERS/ONE BOOSTER) WITH OR WITHOUT CIRCULA TION TWO TEMPERA TURE - TWO HEA TERS (ONE PRE-HEA TER/ONE BOOSTER HEA TER) WITH OR WITHOUT RECIRCULA TION * PIPE RELIEF V A L VE TO OPEN DRAIN ** 140°F (60°C) TO 150°F (65.
18 TWO TEMPERA TURE-ONE HEA TER HIGH TEMPERA TURE ST ORAGE WITH RECIRCULA TION OF SANITIZING LOOP NOTE 1: T OGGLE SWITCH CONTROLS 180°F WA TER CIRCULA TION. INST ALL ON OR CLOSE T O DISHWASHING MACHINE . TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERA TION AND OPEN (OFF) WHEN DISHW ASHER IS NOT OPERA TING.
19 THREE UNIT MANIFOLD KIT (P ART NO. 78693) FOUR UNIT MANIFOLD KIT (P ART NO. 78694) CHECK LIST AND SERVICE INFORMA TION IMPORT ANT The installer may be able to observe and correct certain problems which might arise when the unit is put into operation or when it is refired after a prolonged shut-down.
20 8. Burner may not be firing at proper rate. • Check nozzle size. • Check fuel pump pressure setting. • GPO-199 . . . . . . . . . . . 1 10 psig (758 kPa) • All others . . . . . . . . . . . 100 psig (689.5 lPa) 9. Burner may be short cycling.
21 If the problem is not getting a spark to ignite the oil, check for the following: 1. Loose wiring. 2. Red ignition transformer . 3. Low voltage. 4. Crack in electrode porcelain insulators. 5. Electrodes carboned or out of adjustment. 6. Weak or no contact between bus bars and terminals of transformer .
22 TROUBLESHOOTING TROUBLE CAUSE REMEDY Oil level below intake line in supply tank. Fill tank with oil. Clogged strainer or filter . Remove and clean strainer . Replace filter element. Clogged nozzle. Replace nozzle. Air leak in intake line. T ighten all fittings in intake line.
23 COMMERCIAL OIL FIRED W A TER HEA TER MODEL GPO XX - 199, 245, 315, 385, 455 & 700 AND GPO XX - 315A, 385A, 455A & 700A ITEM NO. 13 ITEM NO. 25 REPLACEMENT P ARTS LIST CLEANOUT ASSEMBLY OIL STATE WATER HEATERS 500 Lindahl Parkway, Ashland City, TN 37015 Phone: 800-821-2017 • Fax: 800-644-9306 www.
24 GPO 86 GPO 86 GPO 84 GPO 75 GPO 75 GPO 69 ITEM DESCRIPTION 199 245 315 385(A) 455(A) 700(A) 1 .... *Anode ................................... 183523-42(2) ... 183523-42(2) ...... 183523-42(2) ....... 183523-39(3) ....... 183523-39(3) ..... 183523-39(4) 2 .
デバイスState Water Heaters GPO 86-199の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
State Water Heaters GPO 86-199をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはState Water Heaters GPO 86-199の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。State Water Heaters GPO 86-199の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。State Water Heaters GPO 86-199で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
State Water Heaters GPO 86-199を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はState Water Heaters GPO 86-199の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、State Water Heaters GPO 86-199に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちState Water Heaters GPO 86-199デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。